Honeywell H600A Humidity Control Himidify Instruction Manual

June 4, 2024
Honeywell

Honeywell H600A Humidity Control Himidify

APPLICATION
The H600 is a humidity control that controls humidification and dehumidification equipment within a range of 20 to 80 percent RH. It has an SPDT switch to operate humidification equipment on RH fall or dehumidification equipment on RH rise. The sensing element is a thin moisture-sensitive nylon ribbon wound around three bobbins. This construction enables the control to respond to small changes in relative humidity over a wide ambient temperature range. The differential is 4 to 6 percent RH and is not adjustable. All models have a locking cover, and the setting knob acts as the cover removal tool.

SPECIFICATIONS

Model: H600A Humidifier and Dehumidifier Control.
Switching : SPDT.

Table 1. Electrical Rating.

| Dehumidifier (Red to Yellow)| Humidifier (Red to Blue)
---|---|---
| 120 Vac| 240 Vac| 120 Vac| 240 Vac
Full Load| 7.5 A| 3.85 A| 4.4 A| 2.2 A
Locked Rotor| 45.0 A| 22.8 A| 26.4 A| 13.2 A
Resistive| —| —| 8.0 A| 4.0 A

INSTALLATION INSTRUCTIONS

  • Relative Humidity Range: 20-80 %.
  • Differential: 4-6 % RH, fixed.
  • Max. Ambient Temperature: 50 °C.
  • Set point adjustment: Removable knob.
  • Dimensions: See Figure 1.

Location
Select a location about 1.5m above the floor on an inside wall with good natural air circulation at average room temperatures.

Avoid:

  • hot spots due to concealed pipes, warm air ducts, radiator, appliances or exposure to sun;
  • cold spots due to location on an outside wall, an unheated room on the other side of partition or drafts from stairwells or doors;
  • dead spots due to lack of circulation behind doors or in corners.
    The ambient temperature of the location chosen must not exceed 50 °C.

H600A HUMIDITY CONTROL

Honeywell H600A Humidity Control Himidify-1

Mounting

  1. Use the setting knob to loosen the cover locking screw. Remove cover.
  2. Remove the backplate from the control assembly by loosening the captive mounting screw and sliding the control down and to the right (See Figures 2 and 3).
  3. Mount the backplate to the wall using the two screws provided.
  4. Attach control to backplate by slipping it under tabs and tightening the captive mounting screw (See Figure 2).
  5. Connect wires as shown in Figure 5.
  6. Replace cover and tighten the locking screw with setting knob supplied.

Honeywell H600A Humidity Control Himidify-2

Honeywell H600A Humidity Control Himidify-3

Honeywell H600A Humidity Control Himidify-4

WIRING

CAUTION
Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage.

Honeywell H600A Humidity Control Himidify-5

All wiring must comply with local electrical codes.
Follow equipment manufacturer’s instructions, if available; otherwise proceed as follows:
Insert wiring through hole in back plate or through conduit entry (see Figure 2). If conduit entry is not used, hole must be closed with the rubber plug provided. If the hole in the mounting plate is exposed to an opening in the wall, plug the opening to prevent drafts from affecting the humidistat operation.
Connect wires as shown in Figure 5.

SETTING
Adjust the relative humidity setting with the removable setting knob provided.

www.resideo.com

Resideo Technologies, Inc.
1985 Douglas Drive North, Golden Valley, MN 55422
1-800-468-1502
60-0080—03 M.S. Rev. 10-21 | Printed in United States

© 2021 Resideo Technologies, Inc. All rights reserved.
The Honeywell Home trademark is used under license from Honeywell International, Inc. This product is manufactured by Resideo Technologies, Inc. and its affiliates.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Honeywell User Manuals

Related Manuals