SENECA ZE-4DI-2AI-2DO ModBUS mixed IO Modules Instruction Manual
- June 3, 2024
- SENECA
Table of Contents
- SENECA ZE-4DI-2AI-2DO ModBUS mixed IO Modules
- CONTACT INFORMATION
- MODULE LAYOUT
- TECHNICAL SPECIFICATIONS
- INSTALLATION REGULATIONS
- ModBUS CONNECTION RULES
- CONNECTOR IDC10
- USB PORT (Z-4DI-2AI-2DO)
- SETTING THE DIP-SWITCHES
- WEB SERVER
- ELECTRICAL CONNECTIONS
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
SENECA ZE-4DI-2AI-2DO ModBUS mixed IO Modules
PRELIMINARY WARNINGS
The word WARNING preceded by the symbol indicates conditions or actions
that put the user’s safety at risk.
The word ATTENTION preceded by the symbol indicates conditions or actions
that might damage the instrument or the connected equipment. The warranty
shall become null and void in the event of improper use or tampering with the
module or devices supplied by the manufacturer as necessary for its correct
operation, and if the instructions contained in this manual are not followed.
WARNING: The full content of this manual must be read before any
operation. The module must only be used by qualified electricians. Specific
documentation is available via QR-CODE shown on page 1.
The module must be repaired and damaged parts replaced by the Manufacturer.
The product is sensitive to electrostatic discharges. Take appropriate
measures during any operation.
Electrical and electronic waste disposal (applicable in the European Union and
other countries with recycling). The symbol on the product or its packaging
shows the product must be surrendered to a collection centre authorized to
recycle electrical and electronic waste.
CONTACT INFORMATION
Technical support support@seneca.it
Product information sales@seneca.it
This document is the property of SENECA srl. Copies and reproduction are
prohibited unless authorised. The content of this document corresponds to the
described products and technologies.
Stated data may be modified or supplemented for technical and/or sales
purposes.
MODULE LAYOUT
Single module dimensions LxHxD: 17.5 x 102.5 x 111 mm; Weight: 110 g;
Enclosure: PA6, black
Double module dimensions LxHxD: 35 x 102.5 x 111 mm; Weight: 110 g; Enclosure:
PA6, black
LED SIGNALS ON THE FRONT PANEL (ZE-4DI-2AI-2DO)
LED | STATUS | MEANING |
---|---|---|
IP / PWR | ON | Module powered IP address acquired |
IP / PWR | Flashing | Module powered Waiting for IP address from the DHCP server |
Tx/Rx | Flashing | Data transmission and reception on at least one Modbus port |
ETH TRF | Flashing | Packet transmission on Ethernet port |
ETH LNK | ON | Ethernet port connected |
DI1, DI2, DI3, DI4 | On / Off | Status of digital input 1, 2, 3, 4 |
DO1, DO2 | On / Off | Status of output 1, 2 |
FAIL | Flashing | Outputs in fail condition |
LED SIGNALS ON THE FRONT PANEL (Z-4DI-2AI-2DO)
LED | STATUS | MEANING |
---|---|---|
PWR | ON | Module powered |
Tx/Rx | Flashing | Data transmission and reception on at least one Modbus port: |
COM 1 port, COM 2 port
DI1, DI2, DI3, DI4| On / Off| Status of digital input 1, 2, 3, 4
DO1, DO2| On / Off| Status of output 1, 2
FAIL| Flashing| Outputs in fail condition
LED SIGNALS ON THE FRONT PANEL (ZE-2AI)
LED | STATUS | MEANING |
---|---|---|
IP / PWR | ON | Module powered and IP address acquired |
IP / PWR | Flashing | Module powered Waiting for IP address from the DHCP server |
FAIL | ON | At least one of the two analogue inputs is out of scale (underscale- |
overscale)
ETH TRF| Flashing| Packet transmission on Ethernet port
ETH LNK| ON| Ethernet port connected
Tx1| Flashing| Modbus packet transmission from device to COM 1 port
Rx1| Flashing| Modbus packet reception on COM 1 port
Tx2| Flashing| Modbus packet transmission from device to COM 2 port
Rx2| Flashing| Modbus packet reception on COM 2 port
TECHNICAL SPECIFICATIONS
-
CERTIFICATIONS
https://www.seneca.it/products/ze-4di-2ai-2do/doc/CE_declaration
https://www.seneca.it/products/z-4di-2ai-2do/doc/CE_declaration
https://www.seneca.it/products/ze-2ai/doc/CE_declaration -
INSULATION
-
**
**
-
ENVIRONMENTAL CONDITIONS
Temperature: 25 ÷ + 70°C
Humidity: 30% ÷ 90% non condensing
Altitude: Up to 2000 m above sea level
Storage temperature: -30 ÷ +85°
Protection rating: IP20.
-
ASSEMBLY
IEC EN60715, 35mm DIN rail in vertical position. -
CONNECTIONS
Removable 3-way screw terminals, 5 mm pitch for cable up to 2.5 mm2 Rear connector IDC10 for DIN bar 46277 RJ45 micro USB (Z-4DI-2AI-2DO) -
POWER SUPPLY
Voltage: 11 ÷ 40Vdc; 19 ÷ 28Vac 50 ÷ 60Hz
Absorption: Typical: 1,5 W @ 24Vdc, Max: 4 W (ZE-4DI-2AI-2DO Z-4DI-2AI- 2DO)
Absorption: Typical: 1,5 W @ 24Vdc, Max: 2 W (ZE-2AI) -
DIGITAL INPUTS only ZE-4DI-2AI-2DO Z-4DI-2AI-2DO
Number of channels 4. Configurable PNP or NPN.
Voltage input OFF < 4V, ON > 8V (max. 24 Vdc ).
Current input 20 mA. Max frequency 5 KHz.
Absorbed current 3mA@12Vdc, 10mA @24Vdc.
-
COUNTERS only ZE-4DI-2AI-2DO Z-4DI-2AI-2DO
4 32bit resettable counters on non-volatile memory. -
DIGITAL OUTPUTS only ZE-4DI-2AI-2DO Z-4DI-2AI-2DO
Number of channels 2.
SPDT free contact relay.
Max. voltage 250Vac. Max. current 2 A.
-
ANALOGUE INPUTS
Number of channels 2. Voltage/Current configurable
Input Voltage 0÷30 V. Precision 0.1% of full scale, Resolution: 16 bit
Current input 0 ÷ 20mA– precision 0.1% of full scale, Resolution: 16bit
Input protection 40V / 25mA -
COMMUNICATION PORTS
RS485 COM1 on IDC10 connector. RS485 or RS232 M10-M11-M12.
Ethernet 100 base T RJ45 front (ZE-4DI-2AI-2DO, ZE-2AI) side micro USB port (Z -4DI-2AI-2DO)
INSTALLATION REGULATIONS
The module has been designed for vertical installation on a DIN 46277 rail.
For optimal operation and long life, adequate ventilation must be provided.
Avoid positioning ducting or other objects that obstruct the ventilation
slots. Avoid mounting modules over heat-generating equipment. Installation in
the bottom part of the electrical panel is recommended.
CAUTION
These are open type devices intended for installation in a final casing/panel
that offers mechanical protection and protection against the spread of fire.
ModBUS CONNECTION RULES
- Install the modules in the DIN rail (120 max)
- Connect the remote modules using cables of an appropriate length. The following table shows cable length data:
- Bus length: maximum length of the Modbus network according to the Baud Rate. This is the length of the cables that connect the two farthest modules
- Derivation length: maximum length of a derivation 2 m For maximum performance, it is recommended to use special shielded cables, designed specifically for data communication.
CONNECTOR IDC10
Power supply and Modbus interface are available using the Seneca DIN rail bus,
via the IDC10 rear connector, or the Z-PC-DINAL-17.5 accessory
Back connector (IDC 10)
The illustration shows the meanings of the various IDC10 connector pins if
signals are to be sent via them directly.
USB PORT (Z-4DI-2AI-2DO)
The module is designed to exchange data according to the modes defined by the
MODBUS protocol. It has a micro USB connector on the front panel and can be
configured using applications and/or software programs.
The USB serial port uses the following communication parameters: 115200,8,N,1.
The USB communication port responds exactly like the serial ports, with the
exception of the communication parameters. Check that the device in
question is included in the list of products supported by the Easy Setup APP
FACTORY IP ADDRESS
The default module IP address is static: 192.168.90.101
SETTING THE DIP-SWITCHES
WARNING
The DIP-switch settings are read only at boot time. At each change, perform a
restart.
SW2 DIP-SWITCH:
Through DIP-SWITCH-SW1 it is possible to set the IP configuration of the device:
ATTENTION
DIP3 and DIP4, on models where they are present, must remain OFF. If set
otherwise, the instrument will not operate correctly. RS232/RS485 SETTING:
RS232 or RS485 configuration on terminals 10-11-12 (serial port 2)
WEB SERVER
To access the maintenance Web Server with 192.168.90.101 factory IP address
type:
http://192.168.90.101
Default user: admin, Default password: admin.
CAUTION
DO NOT USE DEVICES WITH THE SAME IP ADDRESS IN THE SAME ETHERNET NETWORK.
ELECTRICAL CONNECTIONS
Attention: the upper power supply limits must not be exceeded, as this might
cause serious damage to the module.
To meet the electromagnetic immunity requirements:
- use shielded signal cables;
- connect the shield to a preferential instrumentation earth system;
- separate shielded cables from other cables used for power installations (transformers, inverters, motors, induction ovens, etc.).
POWER SUPPLY
- The power supply is connected to terminals 2 and 3.
- The supply voltage must be between:
- 11 and 40Vdc (indifferent polarity), or between 19 and 28 Vac.
- The power supply source must be protected from any failures in the module by means of a suitably sized fuse.
ANALOGUE INPUTS
- The module has two analogue inputs that can be configured via software as voltage or current.
- For the configuration software, see the user manual
DIGITAL INPUTS (ONLY ZE-4DI-2AI-2DO and Z-4DI-2AI-2DO)
DIGITAL OUTPUTS (ONLY ZE-4DI-2AI-2DO and Z4DI-2AI-2DO)
COM2 SERIAL PORT
References
- seneca.it/products/z-4di-2ai-2do/doc/CE_declaration
- seneca.it/products/ze-2ai/doc/CE_declaration
- seneca.it/products/ze-4di-2ai-2do/doc/CE_declaration
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>