KIDDE 10SDR Smoke Alarm Battery Powered User Guide

June 5, 2024
Kidde

KIDDE Logo User Guide
Photoelectric Smoke Alarm
Model 10SDRKIDDE 10SDR Smoke Alarm Battery
Powered SMOKE ALARM

10SDR Smoke Alarm Battery Powered

Helps Reduce Cooking Nuisance Alarms

  • 2 AA BATTERIES
  • Self-TeSTing (See SecTion 9)
  • eaSy inSTallaTion (mounTing brackeT included)

Thank you for Purchasing this kidde Smoke alarm
This model is powered by two AA batteries. It also contains HUSH TM silence nuisance alarms, and “self-testing” features (see section 9).
Teach children how to respond to the alarm and that they should never play with the unit. Your Kidde Smoke Alarm was designed for use in a residential environment.
It is not designed for use in a recreational vehicle (RV) or boat.
Note: Please thoroughly read this user guide and save the document for future reference and to pass on to any subsequent owner. Images are representative only.
Actual product may vary slightly.
The National Fire Protection Association (NFPA) and the manufacturer recommend replacing this alarm after ten years. to temporarily
Product Support: 1-800-880-6788
Please write down the below information and have this at hand when you call.
date code (on back):
date of Purchase:

Where Purchased:
date to replace:

Smoke alarm: What to do When the alarm Sounds

The smoke alarm pattern is three long beeps, a 1.5 second pause, and three long beeps repeating. The red LED blinks in time with the alarm pattern.

  • Alert small children in the home as well as anyone else that might have difficulty recognizing the importance of the alarm sounding or that might have difficulty leaving the area without help.
  • Plan two ways out! Leave immediately by your escape plan. Don’t waste time getting dressed or picking up valuables.
  • While leaving, don’t open any inside door without first feeling its surface. If hot, or if you see smoke seeping through cracks, don’t open that door! Instead, use your alternate exit. If the inside of the door is cool, place your shoulder against it, open it slightly and be ready to slam it shut if heat and smoke rush in.
  • If the escape route requires you to go through smoke, stay close to the floor where the air is cleaner. Crawl if necessary, and breathe shallowly through a cloth, wet if possible.
  • Once outside, go to your selected meeting place and make sure everyone is there.
  • Call the f ire department or 911 from your cell phone outside, or from your neighbor’s home-not from yours!
  • Don’t return to your home until the f ire officials say that it is all right to do so.
    Note: See Section recognizing nuisance alarms, for nuisance alarm situations.

Other alarm Visual and audible indicators

Operational Mode| Visual Indications| Audible Indications| Action/Note
---|---|---|---
Normal (standby)| Red LED blinks approx every 60 sec.| |
Test (button press when no alarm condition is present)
(Note: Test is very loud, stand a few feet away.)| Red LED blinks in time with alarm pattern.| • Single beep.
• 3 long beeps, pause, 3 long beeps.
• Single beep.| Perform button press once a week to verify proper alarm operation.
Smoke Alarm Memory (unit has experienced a smoke alarm event)| Red LED blinks every 15 sec.| | NOTE: Alarm memory is only retained for 24 hrs. Push test button to clear Alarm Memory.
Smoke Alarm HushTM Mode| Red LED blinks every 2 sec.| Smoke alarm pattern stops.
(If there is too much smoke to allow HushTM : Smoke alarm pattern continues.)| This feature is to be used only when a known alarm condition, such as smoke from cooking, activates the alarm. Push button again to cancel HushTM.

if you require further information please contact Product Support at 1-800-880-6788 or write us at: kidde, 1016 corporate Park drive, mebane, nc 27302. our internet address is www.kidde.com.

Troubleshooting guide

Trouble Condition| Visual Indications
| Audible Indications| Action
---|---|---|---
Normal (standby)| Red LED blinks approx every 60 sec.| |
Low Battery| Red LED blinks every 60 sec| Chirp every 60 sec| * Push button once to silence for 24 hrs. (Push button again to clear HushTM and perform a test.)

  • Replace batteries as soon as possible. Note: 7 days after Low Battery begins, the chirps cannot be silenced.
    Smoke Sensor Fault| Red LED blinks every 60 sec| 3 chirps every 60 sec.| * See Cleaning Your Alarm section.
  • Push button once to attempt to reset the unit.
  • If error continues, remove, dispose unit, and replace as soon as possible.
    Memory Fault| Red LED blinks 3 times every 60 sec| 3 chirps every 60 sec.| * Push button once to attempt to reset the unit.
  • If error continues, remove, dispose unit, and replace as soon as possible.
    End of Unit Life| Red LED blinks twice every 60 sec| 2 chirps every 60 sec.| * Push button once to silence for 24 hrs. (Push button again to clear HushTM.)
    Note: 7 days after End of Unit Life begins, the chirps cannot be silenced. Replace immediately!
  • Remove, dispose unit, and replace as soon as possible.
    MCU Failure| None| Constant Tone| Replace alarm as soon as possible.
    Stuck Button| Red LED blinks
    4 times every 60 sec.| 3 chirps every 60 sec|
    Push button to dislodge it from being stuck. If button cannot be unstuck, remove, dispose unit, and replace as soon as possible.

Introduction, Product features and Specifications

Introduction
This alarm detects products of combustion using a photoelectric sensor.
Ten (10) years af ter the unit was installed, powered up, and tested, this unit will automatically alert you that it is time to replace the unit. This is called “End of Unit Life” mode. See Troubleshooting Guide.
To help identify the date to replace the unit, a label has been affixed to the side of the alarm. Write the “Install date” in the space provided, and then write in the
“Replace by” date (10 years from initial power up) in permanent marker on the label prior to installing the unit.
Product Features and Specifications:

  • Powered by two AA batteries
  • Reduced nuisance alarms
  • Self-testing (see section 9)
  • Easy installation
  • Smoke Alarm HushTM
  • Smoke Sensor: Photoelectric
  • Temperature Operating Range: 40°F (4.4°C) to 100°F (37.8°C)
  • Humidity Operating Range: up to 95% RH non-condensing
  • Audible Alarm: 85+ dB at 10’, 3.0 to 3.5 KHz pulsing alarm

limitations of Smoke Alarms

WARNING: PLEASE READ CAREFULLY AND THOROUGH

  • Life safety from fire in residential occupancies is based primarily on early notification to occupants of the need to escape, followed by the appropriate egress actions by those occupants.

  • There are situations where a smoke alarm may not be effective to protect against f ire as stated in the NFPA Standard 72. For instance:
    a) smoking in bed
    b) leaving children home alone
    c) cleaning with flammable liquids, such as gasoline

  • Fire warning systems for dwelling units are capable of protecting about half of the occupants in potentially fatal fires. A smoke alarm may not be effective in some situations, such as during incendiary fires where the fire grows so rapidly that an occupant’s egress is blocked even with properly located smoke alarms, or when victims are intimate with the fire (for example, when a person’s clothes catch fire while cooking), too old or young, or physically or mentally impaired such that they cannot escape even when warned early enough that escape should be possible. For these people, additional strategies such as protection-in-place or assisted escape or rescue are necessary. *

  • A battery powered alarm must have a battery of the specified type, in good condition and installed properly (this model includes two AA replaceable batteries).

  • This model meets the latest residential smoke alarm standards, which includes enhanced resistance to nuisance alarms from cooking. Industry experts recommend that both ionization and photoelectric smoke alarms be installed to help ensure optimal detection of the various types of fires that can occur within the home. Ionization sensing alarms may detect invisible fire particles (associated with fast flaming fires) sooner than photoelectric alarms. Photoelectric sensing alarms may detect visible fire particles (associated with slow smoldering fires) sooner than ionization alarms.

  • This device requires a continuous supply of electrical power from a healthy battery or AC connection, depending on the model. It will not work without power.

  • Smoke alarms must be tested regularly to make sure the battery and the alarm circuits are in good operating condition.

  • Smoke alarms cannot provide an alarm if smoke does not reach the alarm. Therefore, smoke alarms may not sense fires starting in chimneys, within walls, on roofs, on the other side of a closed door or other obstructions.

  • If the alarm is located outside the bedroom or on a different floor, it may not wake up a sound sleeper.

  • The use of alcohol or drugs may also impair one’s ability to hear the smoke alarm. For optimal detection, a smoke alarm should be installed in each sleeping area on every level of a home.
    This alarm is not intended to alert hearing impaired individuals. * reference national fire Protection association (nfPa) standard 72

Recommended Locations for Smoke Alarms

  • Locate smoke alarms in all sleeping areas. Try to monitor the exit path as the bedrooms are usually farthest from the exit. If more than one sleeping area exists, locate additional alarms in each sleeping area.
  • Locate additional alarms in stairways, because stairways act like chimneys for smoke and heat.
  • Locate at least one alarm on every floor level.
  • Locate an alarm in every bedroom.
  • Locate an alarm in every room where electrical appliances are operated (i.e. portable heaters or humidifiers).
  • Locate an alarm in every room where someone sleeps with the door closed. The closed door may prevent an alarm not located in that room from waking the sleeper.
  • Smoke, heat, and combustion products rise to the ceiling and spread horizontally. Mounting the smoke alarm on the ceiling in the center of the room places it closest to all points in the room. Ceiling mounting is preferred in ordinary residential construction.
  • For all alarm locations, be sure to choose a f lat, solid surface for mounting, with no holes or gaps under the mounting bracket.

KIDDE 10SDR Smoke Alarm Battery Powered - CEILINGKIDDE 10SDR Smoke Alarm Battery Powered -COVER
1.

NFPA 72 states: “Smoke alarms in rooms with ceiling slopes greater than 1 ft in 8 ft (0.3m in 2.4 m) horizontally shall be located on the high side of the room.” NFPA 72 states: “A row of detectors shall be spaced and located within 3 fIt (0.9m) of the peak of the ceiling measured horizontally.”

  • For mobile home installation, select locations carefully to avoid thermal barriers that may form at the ceiling. For more details, see MOBILE HOME INSTALLATION section.
  • When mounting the alarm on the wall, use an inside wall with the top edge of a maximum of 12” (30.5 cm) below the ceiling.
  • Put smoke alarms at both ends of a bedroom hallway or large room if the hallway or room is more than 30 feet (9.1 m) long.
  • Install Smoke Alarms on sloped, peaked or cathedral ceilings at or within 3f t (0.9m) of the highest point (measured horizontally).
    This equipment should be installed in accordance with the National Fire Protection Association’s 72 (National Fire Protection Association, Batterymarch Park, Quincy, MA 02269).

Mobile Home Installation
Modern mobile homes have been designed and built to be energy efficient. Install smoke alarms as recommended above. In older mobile homes that are not well insulated compared to present standards, extreme heat or cold can be transferred from the outside to the inside through poorly insulated walls and roof. This may create a thermal barrier which can prevent the smoke from reaching an alarm mounted on the ceiling. In such units, install the smoke alarm on an inside wall with the top edge of the alarm a maximum of 12” (30.5 cm) below the ceiling. If you are not sure about the insulation in your mobile home, or if you notice that the outer walls and ceiling are either hot or cold compared to the room air temperature, install the alarm on an inside wall. NFPA 72 (National Fire Protection Association) requires smoke alarms be installed in each sleeping area.
WARNING: TEST YOUR ALARM OPERATION AFTER MOBILE HOME HAS BEEN IN , STORAGE OR UNOCCUPIED, AND AT LEAST ONCE A WEEK DURING USE.

locations to avoid

(See Figures 6-A, 6-B, & 6-C for recommended locations.)

  • In the garage. Products of combustion are present when you start your automobile.
  • Normal cooking may cause nuisance alarms. If a kitchen alarm is desired, it should have an alarm silence feature and should not be installed within 6 ft of cooking appliances.
  • Do not install within 6 ft of heating appliances.
  • Less than 4” (10cm) from the peak of an “A” frame type ceiling.
  • In an area where the temperature may fall below 40ºF or rise above 100ºF, such as garages and unfinished attics.
  • In dusty areas. Dust particles may cause nuisance alarms or a failure to alarm.
  • In very humid areas (above 95% RH, non-condensing) as moisture or steam can cause nuisance alarms.
  • In insect-infested areas.
  • Smoke alarms should not be installed within 3 f t (.9m) of the door to a bathroom containing a tub or shower, forced air supply ducts used for heating or cooling, ceiling or whole house ventilating fans, or other high air flow areas.
  • Near lights. Electronic “noise” generated by the lights may cause nuisance alarms.
  • Do not install near vents, flues, or chimneys.
  • Do not install near fans, doors, windows or areas directly exposed to the weather.
  • Do not install DC (battery only) alarms on top of AC electrical junction boxes.
  • Avoid installing where the unit will be exposed to direct sunlight.
    Note: Smoke alarms are not to be used with detector guards unless the combi- nation (alarm and detector guard) has been evaluated and found suitable for that purpose.

Installation and Activation

After selecting the proper location for your alarm, attach the mounting bracket to the wall or ceiling. To ensure aesthetic alignment of the alarm with the hallway, or wall, the “A” line on the mounting bracket should be parallel with the hallway when ceiling mounted, or horizontal when wall mounted.(Figures 8-B and 8-C)
NOTE: If needed, you can knock out the thin plastic centers of one or both of the knockout areas to give alternate hole locations for wall anchors.

  • Pull out the battery pull tab first to activate the batteries (see Figure 8-A). Battery activation is confirmed with a beep. If the beep does not occur when the battery pull tab is removed, remove the batteries and reinstall them. Confirm the battery activation beep.
    NOTE: If either battery compartment is empty, the alarm cannot mount on the mounting bracket.

  • Install the alarm fully on the mounting bracket by rotating the alarm in a clockwise direction. (Figure 8-D)
    NOTE: The alarm will mount to the bracket in 2 positions.

  • The alarm is now activated! Af ter installation / activation, test your alarm as described in Operation and Testing section.

WARNING : FAILURE TO PROPERLY INSTALL AND ACTIVATE THIS ALARM WILL PREVENT PROPER OPERATION OF THIS ALARM AND WILL PREVENT 14 TS RESPONSE TO FIRE HAZARDS.

NOTE: A dust cover has been installed on the alarm. Keep the dust cover on until all construction has been completed for at least 24 hours (drywall, painting, varishing, mounting plate install etc). Construction dust and chemicals can cause contamination and false alarms.

WARNING: DUST COVER MUST BE REMOVED FOR ALARM TO OPERATE.
Kidde alarms are not designed, agency tested or certified for recessed mounting and should not be installed in this manner. Recessed mounting impedes smoke entry into the smoke chamber, which may prevent the alarm from sounding ina timely manner. This could endanger the lives of occupants in the residence. Kidde alarms are designed, tested and certified for wall ( applicable) and ceiling surface mount only.

Operation and Testing

‘This model meets the latest residential smoke alarm standards, which includes enhanced resistance to nuisance alarms from cooking.
Operation
The alarm is operating once It is activated and testing is complete (see “Testing” below). When products of combustion (smoke) are sensed, the unit sounds a loud alarm. See Section for alarm signal descriptions.
Testing
IMPORTANT: Retell canned smoke products vary by manufacturer and produce in- consistent results. If the unit does not alarm when canned smoke is applied conduct a push-to-test to verify proper operation. Over-application of canned smoke can permanently damage the alarm.
Self-Testing
This model is equipped with internal, self-testing components that are always checking to ensure the device Is operating as expected. (Weekly manual testing is still required. See below)
Manual Testing
NOTE: When pushing the Test button, use only your finger o thumb. Using any other instrument(s) such as a broom handie s strictly prohibited, as it may damage the alarm. Test your alarm weekly by pressing and releasing the button quickly. A quick beep will confirm the button has been pushed followed by the test sequence. See Other Alarm Visual and Audible Indicators table. The alarm will sound f the electronic circuitry, horn, and batteries are working. If the alarm does not sound, or gives erratic. or low volume sound, the unit must be replaced
WARNING: DUE TO THE LOUDNESS OF THE ALARM, ALWAYS STAND /ABOUT 2.5 FEET AWAY FROM THE UNIT OR USE EAR PROTECTION WHEN TESTING.
WARNING: DO NOT USE AN OPEN FLAME TO TEST YOUR ALARM,
YOU COULD DAMAGE THE ALARM OR IGNITE COMBUSTIBLE MATERIALS AND START A STRUCTURE FIRE.
Chirping
When End of Unit Life or Low Battery chirping begins, you can temporarily silence these chirps by pressing the button. Other fault/error chirps cannot be silenced Take appropriate action as described in the Troubleshooting Guide.
WARNING: REPLACE UNIT AS SOON AS POSSIBLE WHEN IN END OF UNIT LIFE MODE. SEVEN (7) DAYS AFTER END OF UNIT LIFE BEGINS, THE NOTIFICATIONS CANNOT BE SILENCED, AND SMOKE DETECTION CANNOT BE GUARANTEED. REPLACE IMMEDIATELY!

Recognizing Nuisance Alarms

Smoke Nuisance
This model meets the Iratest residential smoke alarm standards, which includes enhanced resistance to nuisance alarms from cooking.
HUSH™:
If you know why the alarm is sounding, and you can verify that it s not a life threatening situation, you can push the button to silence the alarm for 8-10 minutes. If the smoke s not too dense, that unit will silence. After the Hus™ period, the smoke alarm will automatically reset and sound the alarm if particles of combustion are still present. You can use Hush™ repeatedly unti the air has been cleared of the condition causing the alarm.
NOTE: Dense smoke will override Hush™ and sound a continuous alarm. If no fire is present, check to see if one of the reasons listed in “Locations to avoid” may have caused the alarm. If a fire is discovered, get out and call the fire department or 911, Cigarette smoke will not normally cause the unit to alarm, unless the smoke s blown directly into the alarm. Combustion particles from cooking may set off the alarm fit is located too close to a cooking appliance. Large quantities of combustible particles are generated from spills or when broiling. Using the fan on a range hood which vents to the outside (non-recirculating type) wil also help prevent nuisance alarms from occurring by removing these combustible products from the kitchen

Batteries

This alarm is powered by two replaceable AA batteries. Under normal conditions, fresh batteries will last at least one year.
NOTE: Constant exposre to high or low humidity or temperatures may reduce battery lfe.
WARNING: THE ALARM IS SEALED AND THE COVER IS NOT REMOVABL
Low Battery
This alarm is equipped with a low battery monitor circuit If the battery capacity is nearing the point where it can no longer provide adequate power for all alarm func- tions, the low battery condition will occur. See Trouble- shooting Guide. The batteries must be replaced within 7 days of the first occurrence of the “Low Battery Warning’ to provide continuous alarm detection .

Replace batteries with one of the following approved brands:
Energizer E91, Gold Peak 15A o Golden Power GLRGA.
These batteries can be purchased at your local retaller.
WARNING: Use only the batteries specified. Use of different batteries may have a detrimental effect on the alarm. Do not mix old and new batteries. Do not mix alkaline, standard, or rechargeable batteries
NOTE: Do not use lithium batteries in this unit. A good safety measure is to replace the batteries at least once a year, of at the same time you change your clocks for daylight saving time. A missing or improperly installed battery will render the unit inoperable.
WARNING: Failure to install batteries in the correct orientation will prevent proper operation of this alarm and will prevent its response to fire hazards.

Cleaning Your Alarm

Your Alarm Should be Cleaned at Least Once a Year
You can cleanthe interior of your alarm (sensing chamber) by using compressed air or avacuum cleaner hose and blowing of vacutiming thro ligh the openings around the perimeter of the alarm. The outside of the alarm can be wiped with a clean, dry cloth. Do not use water, detergents or cleaners as they may damage the alarm. If the alarm is in Fault mode, the alarm may be in need of cleaning. After leaning, press the button. If the failt does not clear, the alarm needs to be replaced.

  • Never use detergent or other solvents to clean the unit
  • Avoid spraying air freshener, hair spray, or other aerosols near the alarm.
  • Do not use a hair dryer to clean the alarm, as it may damage the alarm and impact performance
  • Do not paint the unit. Paint wil seal the vents and interfere with the sensor’s ability to detect smoke.
  • Never attempt to disassemble the unit to clean inside. This action will void your warranty.

WARNING: REINSTALL THE ALARM AS SOON AS POSSIBLE TO ENSURE CONTINUOUS DETECTION.

Good Safety Habits

Develop and Practice a Plan of escape
Prepare and practice a home escape plan twice a year, including drills at night.
Know two ways out of every room (door & window) and identify a meeting place outside the home where everyone will gather once they have exited the residence.
When two people have reached the meeting place, one should leave to call 911 while the second person stays to account for additional family members. Establish a rule that once you’re out, you never re-enter under any circumstance!

  • Make a floor plan indicating all doors and windows and at least two (2) escape routes from each room. Stories above ground level may need a rope or chain ladder.
  • Have a family meeting and discuss your escape plan, showing everyone what to do in case of f ire and where to meet af ter they leave the house.
  • Ensure that small children hear the alarm and wake when it sounds. They must wake up in order to execute the escape plan. Practice allows all occupants to test your plan before an emergency. You may not be able to reach your children. It is important they know what to do.
  • Familiarize everyone with the sounds of the smoke alarm and train them to leave your home when they hear it.
  • Current studies have shown smoke alarms may not awaken all sleeping individuals, and that it is the responsibility of individuals in the household that are capable of assisting others to provide assistance to those who may not be awakened by the alarm sound, or to those who may be incapable of safely evacuating the area unassisted.
  • Install and maintain f ire extinguishers on every level of the home and in the kitchen, basement and garage. Know how to use a f ire extinguisher prior to an emergency.

Fire Prevention

Never smoke in bed orleave cooking food unattended Teach children never to play Play with matches or lighters! Train everyone in the home to recognize the smoke: alarm pattern and to leave the home using their escape planchet’s heard. Know how to do “Stop, Drop and Roll” f clothes catch on fire, and how to craw! low under smoke. Install and maintain fire extinguishers on every evel of the home and in N the kitchen, basement and garage.
For your information, the national fire Protection association’s Standard 72 reads: Where required by other governing laws, codes, or standards for a specific type of occupancy, approved single and multiple-station smoke alarms shall be installed as follows:

  1. In all sleeping rooms and guest rooms
  2. Outside of each separate dwelling unit sleep- ing area, within 21 f t (6.4 m) of any door to a sleeping room, with the distance measured along a path of travel
  3. On every level of a dwelling unit, including basements
  4. On every level of a residential board and care occupancy (small facility), including basements and excluding crawl spaces and unfinished attics
  5. In the living area(s) of a guest suite
  6. In the living area(s) of a residential board and care occupancy (small facility)

NFPA (National Fire Protection Association)
fire Safety in the Home: NFPA 72 is intended to provide reasonable safety for persons in family living units. Reasonable f ire safety can be produced through the following three-point program: (1) Minimizing fire hazards (2) Providing fire-warning equipment (3) Having and practicing an escape plan.
Smoke Detection – Are More Alarms Desirable?
The required number of smoke alarms might not provide reliable early warning pro- tection for those areas separated by a door from the areas protected by the required smoke alarms. For this reason, it is recommended that the resident consider the use of additional smoke alarms for those areas for increased protection. The additional areas include the basement, bedrooms, dining room, furnace room, utility room, and hallways not protected by the required smoke alarms. The installation of smoke alarms in attics (finished or unfinished), garages, or within 6’ of a heating or cooking appliance is not normally recommended, as these locations occasionally experience conditions that can result in improper operation.
California State Fire Marshal
Early warning f ire detection is best achieved by the installation of f ire detection equipment in all rooms and areas of the household as follows: A smoke alarm installed in each separate sleeping area (in the vicinity, but outside the bedrooms), heat or smoke detectors in the living rooms, dining rooms, bedrooms, kitchens, hallways, attics, furnace rooms, closets, utility and storage rooms, basements and attached garages.
FCC
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
WARNING! Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate this device.
Reference National Fire Protection Association (NFPA) standard 72 NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
-Reorient or relocate the receiving antenna.
-Increase the separation between the equipment and receiver.
-Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
-Consult the dealer or an experienced radio/TV technician for help.

Service and Warranty

Ten-year Limited Warranty
Kidde warrants that the enclosed alarm (but not the batteries) will be free from defects in material and workmanship or design under normal use and service for a period of ten years from the date of purchase. The obligation of Kidde under this warranty is limited to repairing or replacing the alarm or any part which we find to be defective in material, workmanship or design (part replacement only, no installation), free of charge, upon receiving the alarm with proof of date of purchase, postage and return postage prepaid, to Warranty Service Department, Kidde, 1016 Corporate Park Drive, Mebane, NC 27302. Before shipping, remove the batteries from the battery compartment.
This warranty shall not apply to the alarm if it has been damaged, modified, abused or altered after the date of purchase or if it fails to operate due to improper maintenance or inadequate power. Any implied warranties arising out of this sale, including but not limited to the implied warranties of description, merchantability and fitness for a particular purpose, are limited in duration to the above warranty period. In no event shall the Manufacturer be liable for loss of use of this product or for any indirect, special, incidental or consequential damages, or costs, or expenses incurred by the consumer or any other user of this product, whether due to a breach of contract, negligence, strict liability in tort or otherwise. The Manufacturer shall have no liability for any personal injury, property damage or any special, incidental, contingent or consequential damage of any kind resulting from gas leakage, smoke, f ire or explosion. Since some states do not allow limitations of the duration of an implied warranty or do not allow the exclusion or limitation of incidental or consequential damages, the above limitations or exclusions may not apply to you. While this warranty gives you specific legal rights, you may also have other rights which vary from state to state.
The above warranty may not be altered except in writing signed by both parties hereto.
Your Kidde Alarm is not a substitute for property, f ire, disability, life or other insurance of any kind. Appropriate insurance coverage is your responsibility. Consult your insurance agent. Opening the unit will void the warranty. If there are any differences between this printed warranty and the online limited warranty, then the terms of the online warranty supersede those in this user guide or other printed materials. Visit www.kidde.com for the latest warranty statement.

QUESTIONS OR FOR MORE INFORMATION
Call Kidde Product Support line at 1-800-880-6788
or contact us at www.kidde.com
kidde
1016 Corporate Park Drive, Mebane, NC 27302
©2024 Kidde. All Rights Reserved.