KIDDE COMMERCIAL KE-DT3101WHAB Intelligent Addressable Class A and B Heat
Detector
Specifications
- Model: KE-DT3101WHAB
- Device type: Intelligent addressable class A/B heat detector
- Description:
- KE-DT3101WHAB: Intelligent addressable class A/B heat detector with integrated short circuit isolator (white)
- KE-DT3001W-HAB: Intelligent addressable class A/B heat detector (white)
- Detector Type: Fixed temperature/rate-of-rise sensor
- Compatibility: Supports Kidde Excellence protocol, compatible with 2X-A Series fire alarm control panels with firmware version 5.0 or later, backwards compatible with 2000 Series devices
Installation Instructions
WARNING: Electrocution hazard. Ensure all power sources are removed before installation.
Caution: Follow EN 54-14 standard and local regulations for system planning, design, installation, commissioning, use, and maintenance.
Mounting Base Installation:
- Install and wire the mounting base following the instructions provided.
Detector Head Installation:
- Insert the detector head into the mounting base.
- Rotate the detector head clockwise until it locks into position.
- To lock the detector into the base, remove the locking tab before installation.
Addressing the Detector:
- Set the device address using the rotary dials on the detector head within the range of 001-128.
- Use X10 dial for tens and X1 dial for ones.
Device Status:
State | Indication |
---|---|
Alarm | Steady red LED |
Prealarm | Flashing red LED |
Isolation active | Steady yellow LED |
Device fault | Flashing yellow LED |
Located device | Steady green LED |
Communicating | Flashing green LED |
Detector Sensitivity:
Configure sensitivity settings at the control panel or using the Configuration Utility application.
Sensitivity Settings:
- Setting 1: Class A2S
- Setting 2 (default): A2R BR
- Setting 3: –
Heat Sensitivity Settings:
Frequently Asked Questions
Q: How do I know if the detector is functioning correctly?
A: The device status is indicated by the status LED. Refer to the user manual for LED indications.
Q: Can I disable certain device indications?
A: Yes, certain indications can be disabled from the control panel or Configuration Utility application.
Q: What is the default sensitivity setting?
A: The default sensitivity setting is Setting 2 (A2R BR) for both Day and Night modes.
Installation Sheet
Figures
Figure 1: Locking tab and status LED
- Locking tab
- Status LED
Figure 2: Inserting the detector head into the mounting base
Description
This installation sheet includes information on the 3000 Series Intelligent Addressable Class A/B Heat Detectors shown in the table below.
Model | Device type | Description |
---|---|---|
KE-DT3101W- HAB | HDni | Intelligent addressable class A/B heat detector with |
integrated short circuit isolator (white)
KE-DT3001W- HAB| HDn| Intelligent addressable class A/B heat detector (white)
The detectors use a fixed temperature/rate-of-rise sensor to detect heat.
The detectors determine whether to signal a fire alarm condition by monitoring
the temperature of the surrounding air and analysing the data to determine
whether to initiate an alarm.
All 3000 Series detectors support the Kidde Excellence protocol and are compatible for use with 2X-A Series fire alarm control panels with firmware version 5.0 or later. The detectors are backwards compatible with 2000 Series devices.
Installation
WARNING: Electrocution hazard. To avoid personal injury or death from electrocution, remove all sources of power and allow stored energy to discharge before installing or removing equipment.
Caution: For general guidelines on system planning, design, installation, commissioning, use and maintenance, refer to the EN 54-14 standard and local regulations.
Install and wire the mounting base, as described in the installation sheet
supplied with the base.
Installing the detector head
Insert the detector head into the mounting base and rotate it clockwise until
it snaps into the locked position (see Figure 2).
The detector may be locked into the mounting base if required. To do this,
remove the locking tab before installation (see Figure 1).
To remove a locked detector:
- Insert a small screwdriver into the locking tab slot (Figure 1).
- Press and rotate the detector anticlockwise.
Addressing the detector
Set the device address using the rotary dials on the detector head. The
address range is 001-128.
Use the X10 dial to set the tens and the X1 dial to set the ones, as shown in
the figures below.
Device status
The device status is indicated by the status LED (Figure 1, item 2), as shown in the table below.
State | Indication |
---|---|
Alarm | Steady red LED |
Prealarm | Flashing red LED |
Isolation active [1] | Steady yellow LED |
Device fault | Flashing yellow LED |
Located device [2] | Steady green LED |
Communicating [3] | Flashing green LED |
[1] KE-DT3101W-HAB only. [2] Indicates an active Locate Device command from the control panel. [3] This indication can be disabled from the control panel or the Configuration Utility application.
Detector sensitivity
Configure the detector sensitivity at the control panel or using the Configuration Utility application.
Sensitivity settings
The available sensitivity settings are shown below.
Setting | Class |
---|---|
1 | A2S |
2 (default) | A2R |
3 | BR |
The default sensitivity setting is the same for Day mode and Night mode.
Heat sensitivity settings are based on the following temperature ranges.
Application temperature | Static response temperature |
---|---|
Class | Description |
A2S | Fixed temperature |
A2R | Rate-of-rise |
BR | Rate-of-rise |
Maintenance and testing
Maintenance and cleaning
Basic maintenance consists of a yearly inspection. Do not modify internal
wiring or circuitry.
Clean the outside of the detector using a damp cloth. If required, clean the
inside of the detector (to remove dust and debris) using a vacuum cleaner.
Testing
Always test detectors after installation to ensure that the detector
communicates with the control panel. If the detector does not communicate with
the control panel, check that duplicate addresses have not been assigned.
Specifications
Electrical
Operating voltage | 17 to 29 VDC (4 to 11 V pulsed) |
---|
Current consumption Standby
KE-DT3101W-HAB KE-DT3001W-HAB
Alarm
KE-DT3101W-HAB KE-DT3001W-HAB
| ****
180 µA at 24 VDC
120 µA at 24 VDC
4.75 mA at 24 VDC
4.75 mA at 24 VDC
Polarity sensitive| Yes
Remote indicator alarm output| 8 mA max.
Remote indicator cable length| 30 m max.
Isolation
Isolation specifications only apply to KE-DT3101W-HAB models with an
integrated short circuit isolator.
Current consumption (isolation active) | 5 mA |
---|
Isolation voltage
Minimum Maximum
|
14 VDC
15.5 VDC
Reconnect voltage Minimum Maximum|
14 VDC
15.5 VDC
Rated current|
Continuous (switch closed)| 1.05 A
Switching (short circuit)| 1.4 A
Leakage current| 1 mA max.
Series impedance| 0.08 Ω max.
Maximum impedance [1]|
Between the first isolator and| 13 Ω
the control panel|
Between each isolator| 13 Ω
Number of isolators per loop| 128 max.
Number of devices between isolators| 32 max.
[1] Equivalent to 500 m of 1.5 mm2 (16 AWG) cable.
Mechanical and environmental
IP rating | IP20 |
---|---|
Compatible mounting bases | KE-DB3010W |
Application | Indoor use |
Operating environment Operating temperature Storage temperature Relative humidity| ****
−10 to +65°C
−30 to +75°C
10 to 93% (noncondensing)
Colour| White (similar to RAL 9016)
Material| Brass, ABS+PC, ABS, PS
Weight| 110 g
Dimensions| Ø 100 × 54 mm
Regulatory information
This section provides a summary on the declared performance according to the
Construction Products Regulation
(EU) 305/2011 and Delegated Regulations (EU) 157/2014 and (EU) 574/2014.
For detailed information, see the product Declaration of Performance
(available at firesecurityproducts.com).
Conformity|
---|---
Notified/Approved body| 0370
Manufacturer| Dongguan Fyrnetics Co., Ltd., No.1 Rongwen Road, Changan,
Dongguan 523842, Guangdong, China.
Authorized EU manufacturing representative:
Carrier Fire & Security B.V., Kelvinstraat 7, 6003 DH Weert, Netherlands.
Year of first CE marking| 2023
Declaration of Performance number
KE-DT3101W-HAB KE-DT3001W-HAB
|
12-0101-360-0005
12-0101-360-0006
EN 54
KE-DT3101W-HAB KE-DT3001W-HAB
|
EN 54-5, EN 54-17
EN 54-5
Product identification| KE-DT3101W-HAB, KE-DT3001W-HAB
Intended use| See the product Declaration of Performance
Declared performance| See the product Declaration of Performance
| 2012/19/EU (WEEE Directive): Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union. For proper recycling, return this product to your local supplier upon the purchase of equivalent new equipment, or dispose of it at designated collection points. For more information see: recyclethis.info.
Contact information and product documentation
For contact information or to download the latest product documentation, visit firesecurityproducts.com.
Product warnings and disclaimers
THESE PRODUCTS ARE INTENDED FOR SALE TO AND INSTALLATION BY QUALIFIED
PROFESSIONALS. CARRIER FIRE & SECURITY B.V. CANNOT PROVIDE ANY ASSURANCE THAT
ANY PERSON OR ENTITY BUYING ITS PRODUCTS, INCLUDING ANY “AUTHORIZED DEALER” OR
“AUTHORIZED RESELLER”, IS PROPERLY TRAINED OR EXPERIENCED TO CORRECTLY INSTALL
FIRE AND SECURITY RELATED PRODUCTS.
For more information on warranty disclaimers and product safety information, please check https://firesecurityproducts.com/policy/product-warning/ or scan the QR code: