WARNING: Electrocution hazard. Ensure all power sources are disconnected before installation.
Caution: For system planning and installation guidelines, refer to EN 54-14 standards and local regulations.
- Surface mount the base using 2 x M4 screws.
- Remove the three cable knockouts before installation for cable entry.
- The mounting base includes an optional address tag for device identification.
Using the Address Tag
- Remove the address tag from the centre of the mounting base.
- Add the device address to the tag.
- Push the address tag into one of the slots in the mounting base.
Wiring
Refer to Figure 1 for wiring connections. Connections for each terminal are as follows:
- Terminal 1: [Connection Details]
- Terminal 2: [Connection Details]
- Terminal 3: [Connection Details]
- Terminal 4: [Connection Details]
- Terminal 5: [Connection Details]
- Terminal 6: [Connection Details]
- Terminal 7: [Connection Details]
FAQ
- Q: What should I do if I encounter difficulties during installation?
- A: If you face challenges during installation, it is recommended to consult a professional installer or contact customer support for assistance.
- Q: Can I use the mounting base with detectors from other series?
- A: The mounting base is specifically designed for use with the 3000 Series detectors mentioned in the manual. Compatibility with other series is not guaranteed.
Installation Sheet
Figure 1: Class A wiring
- Address tag
Figure 2: Address tag slots and cable knockouts
- Address tag
- Address tag slots
- Cable knockouts
Description
This installation sheet includes information on the 3000 Series standard mounting bases shown in the table below.
Model | Description |
---|---|
KE-DB3010W | Standard mounting base for 3000 Series intelligent addressable |
detectors (white)
KE-DB3010B| Standard mounting base for 3000 Series intelligent addressable
detectors (black)
- For recessed installation or mounting on rough surfaces or pipes, order the following optional accessories.
Accessory | Description |
---|---|
KE-DBA-RECW | Recess accessory for standard mounting base |
KE-DBA-AUXW | Deep accessory for standard mounting base |
Compatible detectors
- The mounting base is compatible for use with the following 3000 Series detectors.
Model | Description |
---|---|
KE-DP3120W | Intelligent addressable dual optical detector with integrated |
short circuit isolator (white)
KE-DP3020W| Intelligent addressable dual optical detector (white)
KE-DP3121W| Intelligent addressable dual optical/heat detector with integrated
short circuit isolator (white)
KE-DP3121B| Intelligent addressable dual optical/heat detector with integrated
short circuit isolator (black)
KE-DP3021W| Intelligent addressable dual optical/heat detector (white)
KE-DP3021B| Intelligent addressable dual optical/heat detector (black)
KE-DT3101W-HAB| Intelligent addressable class A/B heat detector with
integrated short circuit isolator (white)
KE-DT3001W-HAB| Intelligent addressable class A/B heat detector (white)
Installation
WARNING: Electrocution hazard. To avoid personal injury or death from
electrocution, remove all sources of power and allow stored energy to
discharge before installing or removing equipment.
Caution: For general guidelines on system planning, design, installation,
commissioning, use and maintenance, refer to the EN 54-14 standard and local
regulations.
Installing the mounting base
- Surface mount the base using 2 x M4 screws.
- Three cable knockouts are provided for cable entry (see Figure 2). Remove the knockouts before installation.
- The mounting base also includes an optional address tag for device identification (see Figure 1).
To use the address tag
- Remove the address tag from the centre of the mounting base (by breaking it off).
- Add the device address to the address tag.
- Push the address tag into one of the slots in the mounting base (see Figure 2).
Wiring
- Wire the mounting base as shown in Figure 1. Connections for each terminal are shown below.
Terminal | Description |
---|---|
1 | Remote indicator negative (–) |
2 | Negative line (A–) |
3 | Negative line (B–) |
4 | Positive line (B+) |
5 | Positive line (A+) |
6 | Remote indicator positive (+) |
7 | Earth |
Specifications
Number of terminals | 7 |
---|---|
Remote indicator terminals | Yes |
Application | Indoor use |
Polarity sensitive | Yes |
Operating environment Operating temperature Storage temperature Relative humidity|
−10 to +65°C
−30 to +75°C
10 to 93% (noncondensing)
Colour
KE-DB3010W KE-DB3010B
|
White (similar to RAL 9016) Black (similar to RAL 9011)
Material| Polycarbonate resin PC-6620
Weight| 55 g
Dimensions| Ø 100 × 17 mm
Regulatory information
Conformity | **** |
---|---|
Manufacturer | Dongguan Fyrnetics Co., Ltd., No.1 Rongwen Road, Changan, |
Dongguan 523842, Guangdong, China.
Authorized EU manufacturing representative:
Carrier Fire & Security B.V., Kelvinstraat 7, 6003 DH Weert, Netherlands.
CONTACT
Contact information and product documentation
- For contact information or to download the latest product documentation, visit firesecurityproducts.com.
Product warnings and disclaimers
- THESE PRODUCTS ARE INTENDED FOR SALE AND INSTALLATION BY QUALIFIED PROFESSIONALS. CARRIER FIRE & SECURITY B.V. CAN NOT PROVIDE ANY ASSURANCE THAT ANY PERSON OR ENTITY BUYING ITS PRODUCTS, INCLUDING ANY “AUTHORIZED
- DEALER” OR “AUTHORIZED RESELLER”, IS PROPERLY TRAINED OR EXPERIENCED TO CORRECTLY INSTALL FIRE AND SECURITY-RELATED PRODUCTS.
- For more information on warranty disclaimers and product safety information, please check https://firesecurityproducts.com/policy/product-warning/ or scan the QR code:
References