KIDDE KE-DM3010R-IP Excellence Series Intelligent Addressable Instruction Manual
- June 1, 2024
- Kidde
Table of Contents
Excellence Series Intelligent Addressable
Weatherproof Manual Call Point
Installation Sheet
KE-DM3010R-IP Excellence Series Intelligent Addressable
Description
The 3000 Series Intelligent Addressable Weatherproof Manual Call Point is
designed for outdoor use and supports the Kidde Excellence protocol.
All units are supplied with a resettable element – this can be replaced with a
breakable element, if required (order number N-MC-FE). See “Replacing the
resettable element” on page 3.
The series includes the following models.
Model | Description |
---|---|
KE-DM3010R-IP [1] | Red intelligent addressable weatherproof manual call point |
KE-DM3110R-IP [1] | Red intelligent addressable weatherproof manual call point |
with integrated short circuit isolator
[1] Also available in green.
Figures
Figure 1: Mounting holes and dimensions
Figure 2: Front assembly terminal block and DIP switch
Figure 3: Unlocking the front cover
Figure 4: Removing the front cover
Figure 5: Removing the resettable element
Figure 6: Replacing the front cover
Installation
Caution: This product must be installed and maintained by qualified
personnel adhering to all local or national installation requirements and any
other applicable regulations.
Addressing
Set the device address before installation using the DIP switch on the back of
the front assembly (see Figure 2).
The address range is 001-128. See the table on the last page of this
publication for DIP switch positions for each address.
Note: If you change the device address after installation, you must
disconnect the device from the loop power for at least one second and then
reconnect it for the new address to be recognised.
Installation
The manual call point is surface mounted. Remember to remove the protective
dust cover after commissioning.
Note: The dust cover may also be used to indicate when the unit is not
operational (for example, before commissioning, during maintenance, when
disabled, etc.)
To surface mount the manual call point:
-
Screw the supplied cable gland and sealing plugs into the three threaded cable knockouts in the backbox.
Ensure that the cable gland and plugs include the rubber seal. -
Fix the backbox onto the wall using 4 × M4 screws (not supplied) and feed the loop cable through the cable gland.
Depending on your installation requirements, the backbox can be installed with two cable knockouts at the top and one at the bottom or with one cable knockout at the top and two at the bottom.
See Figure 1 for the location of the mounting holes. -
Connect loop cable to the supplied terminal block, and then plug the terminal block into the PCB connector on the back of the front assembly (see Figure 2).
Use the supplied cable link to test cable continuity before the terminal block is plugged into the PCB connector on the back of the front assembly.
See “Wiring” below for terminal block connections and loop cable specifications. -
Unlock and remove the front cover.
To unlock the front cover, insert the key and turn it clockwise (two clicks), then pull the cover outwards from the bottom to remove it (see Figure 3 and Figure 4). -
Fix the front assembly to the backbox using the 4 screws supplied with the unit.
See Figure 5 for the location of the screw holes. -
Replace the front cover (see Figure 6).
Turn the key anticlockwise (two clicks) to lock the cover, and then remove the key.
Finally, test the manual call point (see “Testing” on page 3).
Wiring
For optimal system performance, use 0.13 to 3.31 mm² (0.40 to 2.05 mm)
twisted-pair cable with a maximum length of 2 km.
Wire the unit as described below. Observe the indicated polarity.
Terminal | Description |
---|---|
A+ | Positive line (+) |
B+ | Positive line (+) |
A– | Negative line (–) |
B– | Negative line (–) |
Device status
The device status is indicated by two colour changing LEDs on the front of the unit, as shown in the table below.
State | Indication |
---|---|
Alarm | Steady red LEDs [1] |
Isolation active | Steady yellow LEDs [2] |
Fault | Flashing yellow LEDs |
Communicating | Flashing green LEDs |
[1] This may also indicate an active Locate Device command from the control
panel.
[2] KE-DM3110-IP models only.
Maintenance and testing
Maintenance
The unit should be maintained and tested according to local or national
requirements and any other applicable regulations. Do not modify internal
wiring or circuitry.
Testing
To activate an alarm, push the resettable element or turn the key clockwise
(one click). To reset the device, turn the key anticlockwise (one click).
Reset the control panel after testing.
Replacing the resettable element
Replace the resettable element (or add the breakable element) as follows:
- Unlock and remove the front cover as described in “Installation” on page 2.
- Push the element up, and then pull it out (see Figure 5).
- Replace the resettable element (or add the breakable element, if required).
- Replace the front cover.
Analogue values
Analogue values for diagnosing and troubleshooting device status are shown in
the table below.
Value | Device Status |
---|---|
32 | Normal |
128 | Alarm |
Specifications
Electrical
Operating voltage | 17 to 38 VDC |
---|
Current consumption
Standby
KE-DM3010-IP
KE-DM3110-IP
Alarm
KE-DM3010-IP
KE-DM3110-IP| 180 µA
200 µA
2.8 mA
2.8 mA
Isolation
The following isolation specifications apply to KE-DM3110-IP models with an
integrated short circuit isolator.
Current consumption (isolation
active)| 1.5 mA
---|---
Isolation voltage
Minimum
Maximum| 14 VDC
15.5 VDC
Reconnect voltage
Minimum
Maximum| 14 VDC
15.5 VDC
Rated current
Continuous (switch closed)
Switching (short circuit)| 1 A
1 A
Leakage current| 1 mA max.
Series impedance| 0.06 Ω max.
Number of isolators per loop| 128 max.
Number of devices between isolators| 32 max.
Mechanical and environmental
IP rating [1] | IP67 |
---|
Backbox cable knockouts
Top/bottom [2]| 1 × threaded knockout (MK20)
2 × threaded knockout (MK20)
Wire size
Minimum
Maximum| 0.13 mm² (0.40 mm)
3.31 mm² (2.05 mm)
Operating environment
Operating temperature
Storage temperature
Relative humidity| −25 to +72°C
−25 to +72°C
10 to 95% (noncondensing)
Colour
Red
Green| RAL3028
RAL6024
Material
Body
Contacts| ABS, PC, PMMA, POM
Nickel plated H59, tin plated
QSn6.5-0.1, tin plated H65
Weight [3]| 267 g
Dimensions [3]| 108 × 108 × 69 mm
- When used with the supplied cable gland and plugs.
- Top/bottom location subject to installation orientation.
- Including the backbox, excluding cable gland and plugs.
Regulatory information
This section provides a summary on the declared performance according to the
Construction Products Regulation (EU) 305/2011 and Delegated Regulations (EU)
157/2014 and (EU) 574/2014.
For detailed information, see the product Declaration of Performance
(available at firesecurityproducts.com).
Conformity|
---|---
Notified/Approved body| 370
Manufacturer| Carrier Safety System (Hebei) Co. Ltd.,
80 Changjiang East Road, QETDZ,
Qinhuangdao, Hebei, China 066004.
Authorized EU manufacturing representative:
Carrier Fire & Security B.V., Kelvinstraat 7, 6003 DH Weert, Netherlands.
Year of first CE marking| 2022
Declaration of
Performance number [1] KE-DM3010-IP
KE-DM3110-IP| 03-0210-360-1083
03-0210-360-1093
EN 54 [1]| EN 54-11 Type A (Outdoor Use)
EN 54-17:2005
Product identification [1]| KE-DM3010R-IP, KE-DM3110R-IP,
KE-DM3010RS18-IP, KE-DM3110RS18IP,
KE-DM3010RS27-IP,
KE-DM3110RS27-IP
Intended use| See the product Declaration of Performance
Declared performance| See the product Declaration of Performance
****| 2012/19/EU (WEEE Directive): Products marked with this symbol cannot be
disposed of as unsorted municipal waste in the European Union. For proper
recycling, return this product to your localsupplier upon the purchase of
equivalent new equipment, or dispose of it at
designated collection points. For more information see: recyclethis.info.
[1] The Declaration of Performance only covers red manual call points.
Only red manual call points are covered by EN 54-11 and EN 54-17.
Contact information and product documentation
For contact information or to download the latest product documentation, visit
firesecurityproducts.com.
Product warnings and disclaimers
THESE PRODUCTS ARE INTENDED FOR SALE TO AND INSTALLATION BY QUALIFIED
PROFESSIONALS.
CARRIER FIRE & SECURITY B.V. CANNOT PROVIDE ANY ASSURANCE THAT ANY PERSON OR
ENTITY BUYING ITS PRODUCTS, INCLUDING ANY “AUTHORIZED DEALER” OR “AUTHORIZED
RESELLER”, IS PROPERLY TRAINED OR EXPERIENCED TO CORRECTLY INSTALL FIRE AND
SECURITY RELATED PRODUCTS.
For more information on warranty disclaimers and product safety information,
please check https://firesecurityproducts.com/policy/product-warning/ or
scan the QR code:
https://firesecurityproducts.com/policy/product-warning
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>