KIDDE COMMERCIAL KE-IO3101-M Intelligent Addressable High Voltage Relay Module Installation Guide

June 1, 2024
KIDDE COMMERCIAL

Excellence Series Intelligent Addressable High
Voltage Relay Module Installation Sheet

Installation Sheet

Figures
Figure 1: Device overview

KIDDE COMMERCIAL KE IO3101 M Intelligent Addressable High Voltage Relay
Module - Fig

  1. Mounting holes (×4)
  2. Loop terminal block
  3. Device status LED
  4. Test (T) button
  5. Output terminal block
  6. DIP switch
  7. Output status LED

Figure 2: Module installation (DIN rail)

Description

This installation sheet includes information on the KE-IO3101-M Intelligent Addressable High Voltage Relay Module (device type 1Onmi).
The module is loop powered and provides two unsupervised outputs (synchronized) with normally open (NO), normally closed (NC), and common (C) contacts. The module includes an integrated short circuit isolator and is suitable for indoor installation.
All 3000 Series modules support the Kidde Excellence protocol and are compatible for use with 2X-A Series fire alarm control panels with firmware version 5.0 or later.

Installation

WARNING: Electrocution hazard. To avoid personal injury or death from electrocution, remove all sources of power and allow stored energy to discharge before installing or removing equipment.
Caution: For general guidelines on system planning, design, installation, commissioning, use and maintenance, refer to the EN 54-14 standard and local regulations.
Installing the module
Always use the NeXT System Builder application to calculate the maximum number of modules that can be installed.
The module must be installed inside a compatible EN 62368-1 compliant protective housing (not supplied) − we recommend the N-IO-MBX-1 DIN Rail Module Box. Remember to earth the protective housing.
Note: An alternative protective housing may be used providing it meets the specifications indicated in “Protective housing” on page 3.
Mount the protective housing onto the wall using a suitable mounting system for the wall characteristics.
Install the module onto the DIN rail inside the protective housing as follows:

  1. Hook the module onto the top of the DIN rail.
  2. Push the module down to secure it onto the rail.

Wiring the module
Caution: All device wiring must comply with the flammability requirements stated in EN 62368-1 (clause 6.5).
Connect the loop wires to the module as shown below. See Table 2 for recommended cable specifications.
Table 1: Loop connection

Terminal Description
B− Negative line (–)
A− Negative line (–)
B+ Positive line (+)
A+ Positive line (+)

Table 2: Recommended cable specifications

Cable Specification
Loop 0.13 to 3.31 mm² (26 to 12 AWG) shielded or unshielded twisted-pair (52

Ω and 500 nF max.)
Output| 0.13 to 3.31 mm² (26 to 12 AWG) shielded or unshielded

Addressing the module
Set the device address using the DIP switch. The address range is 001-128.
The device address is the sum of the switches in the ON position, as shown below.
KIDDE COMMERCIAL KE IO3101 M Intelligent Addressable High Voltage Relay
Module - Addressing

Status indications

The device status is indicated by the Device status LED (Figure 1, item 3), as shown in the table below.
Table 3: Device status LED indications

State Indication
Isolation active Steady yellow LED
Device fault Flashing yellow LED
Test mode Fast flashing red LED
Located device [1] Steady green LED
Communicating [2] Flashing green LED
  1. Indicates an active Locate Device command from the control panel.
  2. This indication can be disabled from the control panel or the Configuration Utility application.

The output status is indicated by the Output status LED (Figure 1, item 7), as shown in the table below.
Table 4: Output status LED indications

State Indication
Active Flashing red LED (flashing only when polled, every 15 seconds)

Test mode [1] Active
Fault
Normal
Selected for test [2] Test activation| Steady red LED
Steady yellow LED
Steady green LED
Slow flashing green LED
Slow flashing red LED

  1. These indications are only visible when the module is in Test mode.
  2. Not activated.

Maintenance and testing

Maintenance and cleaning
Basic maintenance consists of a yearly inspection. Do not modify internal wiring or circuitry.
Clean the outside of the module using a damp cloth.
Testing
Test the module as described below.
See Figure 1 for the location of the Test (T) button, Device Status LED, and Output status LED. See Table 3 and Table 4 for status LED indications.
To perform the test:

  1. Press and hold the Test (T) button for at least 3 seconds (long press) until the Device status LED flashes red (fast flashing), and then release the button.
    The module enters Test mode.
    The Device status LED flashes red for the duration of the test.
    The Output status LED indicates the output state on entering Test mode: normal (steady green), active (steady red), or fault (steady yellow). The output can be tested in any of these states.

  2. Press the Test (T) button again (short press).
    If the output state is not activated, the Output status LED flashes green.
    If the output state is activated, the Output status LED flashes red.

  3. Press the Test (T) button again (short press) to start the test.
    If the output state in step 2 (above) was not activated, the Output status LED flashes red.
    If the output state in step 2 (above) was activated, the Output status LED flashes green.
    Check that any connected devices or equipment operate correctly.
    Press the Test (T) button again to switch the relay state again, if required.

  4. To stop the test and exit Test mode, press and hold the Test (T) button again for at least 3 seconds (long press).
    The module exits the test automatically after 5 minutes if the Test (T) button is not pressed.

After the test the output returns to its original state.
Note: The module exits Test mode automatically if the control panel sends a command to switch the relay (for example an alarm command) or if the control panel is reset.

Specifications

Electrical

Operating voltage 17 to 29 VDC (4 to 11 V pulsed)

Current consumption
Standby
Active| 300 µA at 24 VDC
2.5 mA at 24 VDC
Polarity sensitive| Yes
Number of relays| 2 × latched relays (NC, C, NO), combined
Relay contact rating| 1A at 60 VDC or 5A at 250 VAC (resistive load)

Isolation

Current consumption (isolation active) 2.5 mA

Isolation voltage
Minimum
Maximum| 14 VDC
15.5 VDC
Reconnect voltage
Minimum
Maximum| 14 VDC
15.5 VDC
Rated current
Continuous (switch closed)
Switching (short circuit)| 1.05 A
1.4 A
Leakage current| 1 mA max.
Series impedance| 0.08 Ω max.
Maximum impedance [1] Between the first isolator and  the control panel
Between each isolator| 13 Ω
13 Ω
Number of isolators per loop| 128 max.
Number of devices between isolators| 32 max.

  1. Equivalent to 500 m of 1.5 mm2 (16 AWG) cable.

Mechanical and environmental

IP rating IP30

Operating environment
Operating temperature
Storage temperature
Relative humidity| −22 to +55°C
−30 to +65°C
10 to 93% (noncondensing)
Colour| White (similar to RAL 9003)
Material| ABS+PC
Weight| 220 g
Dimensions (W × H × D)| 109 × 88 × 40 mm

Protective housing
The module must be installed inside a protective housing that complies with all applicable EN 62368-1 requirements (protection against electric shock, fireproof, etc.).
In addition to the above, the protective housing must meet the following specifications.

IP rating Min. IP30 (indoor installation)
Material Metal
Weight [1] Min. 4.75 kg

Regulatory information

This section provides a summary on the declared performance according to the Construction Products Regulation (EU) 305/2011 and Delegated Regulations (EU) 157/2014 and (EU) 574/2014.
For detailed information, see the product Declaration of Performance (available at firesecurityproducts.com).

Conformity ****
Notified/Approved body 370
Manufacturer Carrier Safety System (Hebei) Co. Ltd.,  80 Changjiang East

Road, QETDZ, Qinhuangdao 066004, Hebei, China.
Authorized EU manufacturing representative:
Carrier Fire & Security B.V., Kelvinstraat 7, 6003 DH Weert, Netherlands.
Year of first CE marking| 2023
Declaration of
Performance number| 12-0201-360-0003 [1]
EN 54| EN 54-17, EN 54-18
Product identification| KE-IO3101-M
Intended use| See the product Declaration of Performance
Declared performance| See the product Declaration of Performance
****| 2012/19/EU (WEEE Directive): Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union. For proper recycling, return this product to your local supplier upon the purchase of equivalent new equipment, or dispose of it at
designated collection points. For more information see: recyclethis.info.

  1. Certified installed inside the N-IO-MBX-1 DIN Rail Module Box

Contact information and product documentation
For contact information or to download the latest product documentation, visit firesecurityproducts.com.

Product warnings and disclaimers

THESE PRODUCTS ARE INTENDED FOR SALE TO AND INSTALLATION BY QUALIFIED PROFESSIONALS.
CARRIER FIRE & SECURITY B.V. CANNOT PROVIDE ANYASSURANCE THAT ANY PERSON OR ENTITY BUYING ITS PRODUCTS, INCLUDING ANY “AUTHORIZED DEALER” OR “AUTHORIZED RESELLER”, IS PROPERLY TRAINED OR EXPERIENCED TO CORRECTLY INSTALL FIRE AND SECURITY RELATED PRODUCTS.
For more information on warranty disclaimers and product safety information, please check https://firesecurityproducts.com/policy/productwarning/ or scan the QR code:

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

KIDDE COMMERCIAL User Manuals

Related Manuals