KIDDE COMMERCIAL KE-IO3101-M Intelligent Addressable High Voltage Relay Module Installation Guide
- June 1, 2024
- KIDDE COMMERCIAL
Table of Contents
Excellence Series Intelligent Addressable High
Voltage Relay Module Installation Sheet
Installation Sheet
Figures
Figure 1: Device overview
- Mounting holes (×4)
- Loop terminal block
- Device status LED
- Test (T) button
- Output terminal block
- DIP switch
- Output status LED
Figure 2: Module installation (DIN rail)
Description
This installation sheet includes information on the KE-IO3101-M Intelligent
Addressable High Voltage Relay Module (device type 1Onmi).
The module is loop powered and provides two unsupervised outputs
(synchronized) with normally open (NO), normally closed (NC), and common (C)
contacts. The module includes an integrated short circuit isolator and is
suitable for indoor installation.
All 3000 Series modules support the Kidde Excellence protocol and are
compatible for use with 2X-A Series fire alarm control panels with firmware
version 5.0 or later.
Installation
WARNING: Electrocution hazard. To avoid personal injury or death from
electrocution, remove all sources of power and allow stored energy to
discharge before installing or removing equipment.
Caution: For general guidelines on system planning, design, installation,
commissioning, use and maintenance, refer to the EN 54-14 standard and local
regulations.
Installing the module
Always use the NeXT System Builder application to calculate the maximum number
of modules that can be installed.
The module must be installed inside a compatible EN 62368-1 compliant
protective housing (not supplied) − we recommend the N-IO-MBX-1 DIN Rail
Module Box. Remember to earth the protective housing.
Note: An alternative protective housing may be used providing it meets
the specifications indicated in “Protective housing” on page 3.
Mount the protective housing onto the wall using a suitable mounting system
for the wall characteristics.
Install the module onto the DIN rail inside the protective housing as follows:
- Hook the module onto the top of the DIN rail.
- Push the module down to secure it onto the rail.
Wiring the module
Caution: All device wiring must comply with the flammability requirements
stated in EN 62368-1 (clause 6.5).
Connect the loop wires to the module as shown below. See Table 2 for
recommended cable specifications.
Table 1: Loop connection
Terminal | Description |
---|---|
B− | Negative line (–) |
A− | Negative line (–) |
B+ | Positive line (+) |
A+ | Positive line (+) |
Table 2: Recommended cable specifications
Cable | Specification |
---|---|
Loop | 0.13 to 3.31 mm² (26 to 12 AWG) shielded or unshielded twisted-pair (52 |
Ω and 500 nF max.)
Output| 0.13 to 3.31 mm² (26 to 12 AWG) shielded or unshielded
Addressing the module
Set the device address using the DIP switch. The address range is 001-128.
The device address is the sum of the switches in the ON position, as shown
below.
Status indications
The device status is indicated by the Device status LED (Figure 1, item 3), as
shown in the table below.
Table 3: Device status LED indications
State | Indication |
---|---|
Isolation active | Steady yellow LED |
Device fault | Flashing yellow LED |
Test mode | Fast flashing red LED |
Located device [1] | Steady green LED |
Communicating [2] | Flashing green LED |
- Indicates an active Locate Device command from the control panel.
- This indication can be disabled from the control panel or the Configuration Utility application.
The output status is indicated by the Output status LED (Figure 1, item 7), as
shown in the table below.
Table 4: Output status LED indications
State | Indication |
---|---|
Active | Flashing red LED (flashing only when polled, every 15 seconds) |
Test mode [1] Active
Fault
Normal
Selected for test [2] Test activation| Steady red LED
Steady yellow LED
Steady green LED
Slow flashing green LED
Slow flashing red LED
- These indications are only visible when the module is in Test mode.
- Not activated.
Maintenance and testing
Maintenance and cleaning
Basic maintenance consists of a yearly inspection. Do not modify internal
wiring or circuitry.
Clean the outside of the module using a damp cloth.
Testing
Test the module as described below.
See Figure 1 for the location of the Test (T) button, Device Status LED, and
Output status LED. See Table 3 and Table 4 for status LED indications.
To perform the test:
-
Press and hold the Test (T) button for at least 3 seconds (long press) until the Device status LED flashes red (fast flashing), and then release the button.
The module enters Test mode.
The Device status LED flashes red for the duration of the test.
The Output status LED indicates the output state on entering Test mode: normal (steady green), active (steady red), or fault (steady yellow). The output can be tested in any of these states. -
Press the Test (T) button again (short press).
If the output state is not activated, the Output status LED flashes green.
If the output state is activated, the Output status LED flashes red. -
Press the Test (T) button again (short press) to start the test.
If the output state in step 2 (above) was not activated, the Output status LED flashes red.
If the output state in step 2 (above) was activated, the Output status LED flashes green.
Check that any connected devices or equipment operate correctly.
Press the Test (T) button again to switch the relay state again, if required. -
To stop the test and exit Test mode, press and hold the Test (T) button again for at least 3 seconds (long press).
The module exits the test automatically after 5 minutes if the Test (T) button is not pressed.
After the test the output returns to its original state.
Note: The module exits Test mode automatically if the control panel sends a
command to switch the relay (for example an alarm command) or if the control
panel is reset.
Specifications
Electrical
Operating voltage | 17 to 29 VDC (4 to 11 V pulsed) |
---|
Current consumption
Standby
Active| 300 µA at 24 VDC
2.5 mA at 24 VDC
Polarity sensitive| Yes
Number of relays| 2 × latched relays (NC, C, NO), combined
Relay contact rating| 1A at 60 VDC or 5A at 250 VAC (resistive load)
Isolation
Current consumption (isolation active) | 2.5 mA |
---|
Isolation voltage
Minimum
Maximum| 14 VDC
15.5 VDC
Reconnect voltage
Minimum
Maximum| 14 VDC
15.5 VDC
Rated current
Continuous (switch closed)
Switching (short circuit)| 1.05 A
1.4 A
Leakage current| 1 mA max.
Series impedance| 0.08 Ω max.
Maximum impedance [1] Between the first isolator and the control panel
Between each isolator| 13 Ω
13 Ω
Number of isolators per loop| 128 max.
Number of devices between isolators| 32 max.
- Equivalent to 500 m of 1.5 mm2 (16 AWG) cable.
Mechanical and environmental
IP rating | IP30 |
---|
Operating environment
Operating temperature
Storage temperature
Relative humidity| −22 to +55°C
−30 to +65°C
10 to 93% (noncondensing)
Colour| White (similar to RAL 9003)
Material| ABS+PC
Weight| 220 g
Dimensions (W × H × D)| 109 × 88 × 40 mm
Protective housing
The module must be installed inside a protective housing that complies with
all applicable EN 62368-1 requirements (protection against electric shock,
fireproof, etc.).
In addition to the above, the protective housing must meet the following
specifications.
IP rating | Min. IP30 (indoor installation) |
---|---|
Material | Metal |
Weight [1] | Min. 4.75 kg |
Regulatory information
This section provides a summary on the declared performance according to the
Construction Products Regulation (EU) 305/2011 and Delegated Regulations (EU)
157/2014 and (EU) 574/2014.
For detailed information, see the product Declaration of Performance
(available at firesecurityproducts.com).
Conformity | **** |
---|---|
Notified/Approved body | 370 |
Manufacturer | Carrier Safety System (Hebei) Co. Ltd., 80 Changjiang East |
Road, QETDZ, Qinhuangdao 066004, Hebei, China.
Authorized EU manufacturing representative:
Carrier Fire & Security B.V., Kelvinstraat 7, 6003 DH Weert, Netherlands.
Year of first CE marking| 2023
Declaration of
Performance number| 12-0201-360-0003 [1]
EN 54| EN 54-17, EN 54-18
Product identification| KE-IO3101-M
Intended use| See the product Declaration of Performance
Declared performance| See the product Declaration of Performance
****| 2012/19/EU (WEEE Directive): Products marked with this symbol cannot be
disposed of as unsorted municipal waste in the European Union. For proper
recycling, return this product to your local supplier upon the purchase of
equivalent new equipment, or dispose of it at
designated collection points. For more information see:
recyclethis.info.
- Certified installed inside the N-IO-MBX-1 DIN Rail Module Box
Contact information and product documentation
For contact information or to download the latest product documentation, visit
firesecurityproducts.com.
Product warnings and disclaimers
THESE PRODUCTS ARE INTENDED FOR SALE TO AND INSTALLATION BY QUALIFIED
PROFESSIONALS.
CARRIER FIRE & SECURITY B.V. CANNOT PROVIDE ANYASSURANCE THAT ANY PERSON OR
ENTITY BUYING ITS PRODUCTS, INCLUDING ANY “AUTHORIZED DEALER” OR “AUTHORIZED
RESELLER”, IS PROPERLY TRAINED OR EXPERIENCED TO CORRECTLY INSTALL FIRE AND
SECURITY RELATED PRODUCTS.
For more information on warranty disclaimers and product safety information,
please check https://firesecurityproducts.com/policy/productwarning/ or scan
the QR code: