TX1000D 3K Dual Input UPS System User Manual Product Information
- June 1, 2024
- TX1000D
Table of Contents
3K Dual Input UPS System
Product Information
Specifications
- Product Name: Dual input 1K//2K/3K Online UPS
- Product Type: Uninterruptible Power Supply System
- Version: 1.0
Product Usage Instructions
Installation and Setup
Follow the steps below for proper installation and setup of the
UPS:
-
Rear Panel View: Refer to the manual for a
detailed illustration of the rear panel view. -
Setup the UPS: Connect the UPS following the
provided instructions to ensure proper functionality.
Troubleshooting
If you encounter any issues with the UPS, refer to the
troubleshooting section in the manual for guidance on resolving
common problems.
Storage and Maintenance
Proper storage and maintenance are essential for the longevity
of the UPS. Follow the guidelines in the manual for storing and
maintaining the unit.
FAQ (Frequently Asked Questions)
Q: What precautions should I take when working with UPS
batteries?
A: When working with UPS batteries, follow
these precautions:
-
Remove watches, rings, or other metal objects.
-
Use tools with insulated handles.
-
Wear rubber gloves and boots.
-
Do not lay tools or metal parts on top of batteries.
-
Disconnect charging source and load before installing or
maintaining the battery. -
Remove battery grounds during installation and maintenance to
reduce the likelihood of shock. -
When changing batteries, install the same number and type of
batteries recommended by the manufacturer.
User Manual
Dual input 1K//2K/3K Online UPS
Uninterruptible Power Supply System
Version: 1.0
Table of Contents
1. Important Safety Warning ……………………………………………………………………….. 1 1-1.
Transportation ………………………………………………………………………………………. 1 1-2. Preparation
………………………………………………………………………………………….. 1 1-3.
Installation…………………………………………………………………………………………… 1 1-4.
Operation…………………………………………………………………………………………….. 1 1-5. Maintenance, service and
faults………………………………………………………………… 2
2. Installation and setup ……………………………………………………………………………… 4 2-1. Rear panel
view…………………………………………………………………………………….. 4 2-2. Setup the UPS
………………………………………………………………………………………. 5
3. Operations ……………………………………………………………………………………………… 9 3-1. Button operation
…………………………………………………………………………………… 9 3-2. LCD Panel
……………………………………………………………………………………………. 9 3-3. Audible
Alarm……………………………………………………………………………………… 11 3-4. LCD display wordings
index……………………………………………………………………. 11 3-5. UPS Setting
………………………………………………………………………………………… 12 3-6. Operating Mode Description
…………………………………………………………………… 17 3-7. Faults Reference
Code…………………………………………………………………………… 17 3-8. Warning indicator
………………………………………………………………………………… 18
4. Troubleshooting…………………………………………………………………………………….. 19 5. Storage and
Maintenance……………………………………………………………………….. 20 6. Specifications
……………………………………………………………………………………….. 21
1. Important Safety Warning
Please comply with all warnings and operating instructions in this manual
strictly. Save this manual properly and read carefully the following
instructions before installing the unit. Do not operate this unit before
reading through all safety information and operating instructions carefully.
1-1. Transportation Please transport the UPS system only in the original
package to protect against shock and impact.
1-2. Preparation Condensation may occur if the UPS system is moved directly
from cold to warm environment. The UPS system must be absolutely dry before
being installed. Please allow at least two hours for the UPS system to
acclimate the environment. Do not install the UPS system near water or in
moist environments. Do not install the UPS system where it would be exposed to
direct sunlight or near heater. Do not block ventilation holes in the UPS
housing.
1-3. Installation Do not connect appliances or devices which would overload
the UPS system (e.g. laser printers) to the UPS output sockets. Place cables
in such a way that no one can step on or trip over them. Do not connect
domestic appliances such as hair dryers to UPS output sockets. The UPS can be
operated by any individuals with no previous experience. Connect the UPS
system only to an earthed shockproof outlet which must be easily accessible
and close to the UPS system. Please use only VDE-tested, CE-marked (or UL-
marked for 100/110/115/120/127 VAC models) mains cable (e.g. the mains cable
of your computer) to connect the UPS system to the building wiring outlet
(shockproof outlet). Please use only VDE-tested, CE-marked (or UL-marked for
100/110/115/120/127 VAC models) power cables to connect the loads to the UPS
system. When installing the equipment, it should ensure that the sum of the
leakage current of the UPS and the connected devices does not exceed 3.5mA.
Temperature Rating – Units are considered acceptable for use in a maximum
ambient of 40°C (104°F). For Pluggable Equipment – The socket-outlet shall be
installed near the equipment and shall be easily accessible.
1-4. Operation Do not disconnect the mains cable on the UPS system or the
building wiring outlet (shockproof socket outlet) during operations since this
would cancel the protective earthing of the UPS system and of all connected
loads. The UPS system features its own, internal current source (batteries).
The UPS output sockets or output terminals block may be electrically live even
if the UPS system is not connected to the building wiring outlet. In order to
fully disconnect the UPS system, first press the OFF/Enter button to
disconnect the mains. Prevent no fluids or other foreign objects from inside
of the UPS system.
1
1-5. Maintenance, service and faults The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel. Caution – risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet), components inside the UPS system are still connected to the battery and electrically live and dangerous. Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS-capacitors. Only persons are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries. Caution – risk of electric shock. The battery circuit is not isolated from the input voltage. Hazardous voltages may occur between the battery terminals and the ground. Before touching, please verify that no voltage is present!
Caution – Do not dispose of batteries in a fire. The batteries may explode.
Caution – Do not open or mutilate batteries. Released electrolyte is harmful to the
skin and eyes. It may be toxic.
Batteries may cause electric shock and have a high short-circuit current. Please take the precautionary measures specified below and any other measures necessary when working with batteries:
a) Remove watches, rings, or other metal objects.
b) Use tools with insulated handles.
c) Wear rubber gloves and boots.
d) Do not lay tools or metal parts on top of batteries.
e) Disconnect charging source and load prior to installing or maintaining the
battery.
f) Remove battery grounds during installation and maintenance to reduce
likelihood of shock. Remove the connection from ground if any part of the
battery is determined to be grounded.
When changing batteries, install the same number and same type of batteries or
battery packs.
Manufacture
Type
Rated
Toplite (Guangzhou)
NPW45-12
12 V dc, 9.0 Ah
Technology Battery Co Ltd (MH29104)
UXW460-12 NPW36-12 UXW360-12
12 V dc, 9.0 Ah 12 V dc, 7.2 Ah 12 V dc, 7.2 Ah
NPW45-12 FR
12 V dc, 7.0 Ah
UXW460-12/FR
12 V dc, 7.0 Ah
NPW36-12 FR
12 V dc, 7.0 Ah
CSB Battery Co Ltd
UXW360-12/FR
12 V dc, 7.0 Ah
(MH14533)
GP1272 UPS 12460 F2
12 V dc, 7.2 Ah 12 V dc, 9.0 Ah
UPS 12360 6
12 V dc, 6.5 Ah
UPS 12360 7
12 V dc, 6.5 Ah
HR 1234W
12 V dc, 8.5 Ah
HR 1234W FR
12 V dc, 8.5 Ah
2
Yuasa Battery (Guangdong) NPW45-12
12 V dc, 8.0 Ah
Co Ltd (MH29616)
NPW45-12FR
12 V dc, 8.0 Ah
For UPS with internally mounted battery
a) Instructions shall carry sufficient information to enable the replacement of the
battery with a suitable manufacturer and catalogue number.
b) Safety instructions to allow access by Service Personnel shall be stated in the
installation/service handbook.
c) If batteries are to be installed by Service Personnel, instructions for
interconnections, including terminal torque, shall be provided.
Do not attempt to dispose of batteries by burning them. This could cause battery explosion. Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and eyes. It may be toxic. Please replace the fuse only with the same type and amperage in order to avoid fire hazards. Do not dismantle the UPS system.
3
2. Installation and setup
NOTE: Before installation, please inspect the unit. Be sure that nothing
inside the package is damaged. Please keep the original package in a safe
place for future use. 2-1. Rear panel view
1. Programmable outlets: connect to non-critical loads. 2. Output
receptacles: connect to mission-critical loads. 3. AC input 4.
Network/Fax/Modem surge protection 5. USB communication port 6. RS-232
communication port 7. SNMP intelligent slot 8. Emergency power off function
connector (EPO) 9. External battery connector
4
2-2. Operating principle The operating principle of the UPS is shown as below
The UPS is composed of mains input, input isolation transformer EMI/RFI
filters, rectifier/PFC, inverter, battery charger, DC-to-DC converter,
battery, dynamic bypass and UPS output.
2-3. Setup the UPS Before installing the UPS, please read below to select
proper location to install UPS. 1. UPS should be placed on the flat and clean
surface. Place it in an area away from vibration,
dust, humidity, high temperature, flammable liquids, gases, corrosive and
conductive contaminants. Install the UPS indoors in a clean environment, where
it is away from window and door. Maintain minimum clearance of 100mm in the
bottom of the UPS to avoid dust and high temperature.
2. Maintain an ambient temperature range of 0ºC to 45ºC for UPS optimal operation. For
every 5ºC above 45ºC, the UPS will derate 12% of nominal capacity at full load. The
highest working temperature requirement for UPS operation is 50ºC.
eration at full
power with connected loads for UPS normal operation is listed as below:
4. Place UPS: in a well-
required to maintain minimum clearance of 100mm in the front of the UPS and
300mm in the back and two sides of the UPS for heat dissipation and easy-
maintenance.
5
5. Connect to External Battery Pack
When connecting external battery packs, please be sure to connect polarity correctly. Connect positive pole of battery pack to positive pole of external battery connector in UPS and negative pole of battery pack to negative pole of external battery connector in UPS. Polarity misco positive pole of battery pack and positive pole of external battery connector in UPS to prevent damage to battery packs from internal fault.
The required specification of breaker: voltage 1.25 x battery voltage/set; current 50A
Please choose battery size and connected numbers according to backup time requirement and
UPS specifications.
in the
temperature range of 15ºC to 25ºC.
Step 1: External battery connection Follow the right chart to make external battery connection.
Step 2: UPS input connection Plug the UPS into a two-pole, three-wire,
grounded receptacle only. Avoid using extension cords.
For 200/208/220/230/240VAC models: The power cord is attached to the UPS. The
input plug is a BRAZILIAN 20A for 1K/2K models, Terminal for 3K model. For
100/110/115/120/127VAC models: The power cord is attached to the UPS. The
input plug is a BRAZILIAN 20A for 1K/2K models, Terminal for 3K model. Note:
Check if the site wiring fault indicator lights up in LCD panel. It will be
illuminated when the UPS is plugged into an improperly wired utility power
outlet (Refer to Troubleshooting section). Please also check if there is a
circuit breaker against overcurrent and short circuit between the mains and AC
input of the UPS for safety operation. The recommended protection value as
following: For 200/208/220/230/240VAC models: 20A for the 1K/2K models, 30A
for the 3K models. For 100/110/115/120/127VAC models: 20A for the 1K/2K
models, 30A for the 3K models.
6
Step 3: UPS output connection There two kinds of outputs: programmable outlets
and general outlets. Please connect non-critical devices to the programmable
outlets and critical devices to the general outlets. During power failure, you
may extend the backup time to critical devices by setting shorter backup time
for non-critical devices.
Step 4: Communication connection Communication port:
To allow for unattended UPS shutdown/start-up and status monitoring, connect
the communication cable one end to the USB/RS-232 port and the other to the
communication port of your PC. With the monitoring software installed, you can
schedule UPS shutdown/start-up and monitor UPS status through PC.
The UPS is equipped with intelligent slot perfect for either SNMP or AS400
card. When installing either SNMP or AS400 card in the UPS, it will provide
advanced communication and monitoring options.
Step 5: Network connection
Connect a single modem/phone/fax line into surgeequipment with another
modem/fax/phone line
cable.
Step 6: Disable and enable EPO function This UPS is equipped with EPO
function. By default, the UPS is delivered from factory with Pin 1 and pin 2
closed (a metal plate is connected to Pin 1 and Pin2) for UPS normal
operation. To activate EPO function, remove two screws on EPO port and metal
plate will be removed. Note: The EPO function logic can be set up via LCD
setting. Please refer to program 16 in UPS setting for the details.
normal operation as default.
To activate EPO function, remove these two screws.
Step 7: Turn on the UPS Press the ON/Mute button on the front panel for two
seconds to power on the UPS.
Note: The battery charges fully during the first five hours of normal
operation. Do not expect full battery run capability during this initial
charge period.
7
Step 8: Install software For optimal computer system protection, install UPS
monitoring software to fully configure UPS shutdown. Use supplied RS-232 or
USB communication cable to connect RS-232/USB port of UPS and RS-232/USB port
of PC. Then, follow below steps to install monitoring software. 1. Insert the
included installation CD into CD-ROM drive and then follow the on-screen
instructions to proceed software installation. If there no screen shows 1
minute after inserting the CD, please execute setup.exe file for initiating
software installation. 2. Follow the on-screen instructions to install the
software. 3. When your computer restarts, the monitoring software will appear
as an orange plug icon located in the system tray, near the clock.
8
3. Operations
3-1. Button operation
Button
Function
ON/Mute Button
OFF/Enter Button
Select Button
ON/Mute + Select Button
Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds to turn
on the UPS. Mute the alarm: After the UPS is turned on in battery mode, press
and hold this button for at least 3 seconds to disable or enable the alarm
uations when warnings or errors occur. Up key: Press this button to display
previous selection in UPS setting mode. Switch to UPS self-test mode: Press
ON/Mute buttons for 3 seconds to enter UPS self-testing while in AC mode, ECO
mode, or converter mode.
Turn off the UPS: Press and hold this button at least 2 seconds to turn off
the UPS. UPS will be in standby mode under power normal or transfer to Bypass
mode if the Bypass enable setting by pressing this button. Confirm selection
key: Press this button to confirm selection in UPS setting mode.
Switch LCD message: Press this button to change the LCD message for input
voltage, input frequency, input current, battery voltage, battery current,
battery capacity, ambient temperature, output voltage, output frequency, load
current and load percent. Setting mode: Press and hold this button for 3
seconds to enter UPS setting mode when Standby and Bypass mode. Down key:
Press this button to display next selection in UPS setting mode.
Switch to bypass mode: When the main power is normal, press ON/Mute and Select
buttons simultaneously for 3 seconds. Then UPS will enter to bypass mode. This
action will be ineffective when the input voltage is out of acceptable range.
Exit setting mode or return to the upper menu: When working in setting mode,
press ON/Mute and Select buttons simultaneously for 0.2 seconds
buttons at the same time to exit the setting mode.
3-2. LCD Panel
9
Display
Function
Backup time information
Indicates the estimated backup time.
H: hours, M: minute, S: second.
Configuration and fault information
Indicates the configuration items, and the configuration items are listed in
details in section 3-5.
Indicates the warning and fault codes, and the codes are listed in details in
section 3-7 and 3-8.
Mute operation
Indicates that the UPS alarm is disabled.
Input, Battery, Temperature, Output & Load information IIndicate the input
voltage, input frequency, input current, battery voltage, battery current,
battery capacity, ambient temperature, output voltage, output frequency, load
current and load percent.
k: kilo, W: watt, V: voltage, A: ampere, %: percent, : centigrade degree, Hz:
frequency
Load information Indicates the load level by 0-24%, 25-49%, 50-74% and
75-100%.
Indicates overload.
Programmable outlets information Indicates that programmable management
outlets are working.
Mode operation information Indicates the UPS connects to the mains. Indicates
the battery is working. Indicates charging status Indicates the bypass circuit
is working. Indicates the ECO mode is enabled. Indicates the AC to DC circuit
is working. Indicates the PFC circuit is working. Indicates the inverter
circuit is working.
Indicates the UPS is working in converter mode.
Indicates the output is working. Battery information
Indicates the battery level by 0-24%, 25-49%, 50-74%, and 75-100%.
Indicates low battery.
10
3-3. Audible Alarm Battery Mode Low Battery Overload Fault Bypass Mode
Sounding every 5 seconds Sounding every 2 seconds
Sounding every second Continuously sounding Sounding every 10 seconds
3-4. LCD display wordings index
Abbreviation
Display content
ENA
DIS
ESC
HLS
LLS
AO
AC
EAT
RAT
OK
ON
BL
OL
OI
NC
OC
SF
EP
TP
CH
BF
BV
FU
BR
EE
Meaning Enable Disable Escape High loss Low loss Active open Active close Estimated autonomy time Running autonomy time OK ON Battery Low Over Load Over input current Battery No Connect Over Charge Site wiring fault EPO Temperature Charger Battery Fault Bypass Out Range Bypass frequency unstable Battery Replace EEPROM error
11
3-5. UPS Setting
There are three parameters to set up the UPS. P
Refer to below table. Parameter 2 is the setting options or values for each
program.
Note Software UPS Configuration Tool can program the following setting.
01: Output voltage setting
Interface
Setting
Parameter 2: Output voltage
For 200/208/220/230/240 VAC models, you may choose the
following output voltage:
200: presents output voltage is 200Vac
208: presents output voltage is 208Vac
220: presents output voltage is 220Vac
230: presents output voltage is 230Vac (Default)
240: presents output voltage is 240Vac
For 100/110/115/120/127 VAC models, you may choose the
following output voltage:
100: presents output voltage is 100Vac
110: presents output voltage is 110Vac
115: presents output voltage is 115Vac
120: presents output voltage is 120Vac (Default)
127: presents output voltage is 127Vac
02: Frequency Converter enable/disable
Interface
Setting
Parameter 2: Enable or disable converter mode. You may
choose the following two options:
CF ENA: converter mode enable
CF DIS: converter mode disable (Default)
03: Output frequency setting
Interface
Setting
Parameter 2: Output frequency setting.
You may set the initial frequency on battery mode:
BAT 50: presents output frequency is 50Hz
BAT 60: presents output frequency is 60Hz
If converter mode is enabled, you may choose the following
output frequency:
CF 50: presents output frequency is 50Hz
CF 60: presents output frequency is 60Hz
12
04: ECO enable/disable
Interface
Setting
Parameter 2: Enable or disable ECO function. You may
choose the following two options:
ENA: ECO mode enable
DIS: ECO mode disable (Default)
05: ECO voltage range setting
Interface
Setting
Parameter 2: Set the acceptable high voltage point and
low voltage point for ECO mode by pressing Down key or Up
key.
HLS: High loss voltage in ECO mode in parameter 2.
For 200/208/220/230/240 VAC models, the setting range in
parameter 3 is from +7V to +24V of the nominal voltage.
(Default: +12V)
For 100/110/115/120/127 VAC models, the setting range in
parameter 3 is from +3V to +12V of the nominal voltage.
(Default: +6V)
LLS: Low loss voltage in ECO mode in parameter 2.
For 200/208/220/230/240 VAC models, the setting range in
parameter 3 is from -7V to -24V of the nominal voltage.
(Default: -12V)
For 100/110/115/120/127 VAC models, the setting voltage
in parameter 3 is from -3V to -12V of the nominal voltage.
(Default: -6V)
06: Bypass enable/disable when UPS is off
Interface
Setting
Parameter 2: Enable or disable Bypass function. You may
choose the following two options:
ENA: Bypass enable
DIS: Bypass disable (Default)
07: Bypass voltage range setting
Interface
Setting
Parameter 2: Set the acceptable high voltage point and
acceptable low voltage point for Bypass mode by pressing
the Down key or Up key.
HLS: Bypass high voltage point
For 200/208/220/230/240 VAC models:
230-264: setting the high voltage point in parameter 3
from 230Vac to 264Vac. (Default: 264Vac)
For 100/110/115/120/127 VAC models:
120-140: setting the high voltage point in parameter 3
from 120Vac to 140Vac. (Default: 132Vac)
LLS: Bypass low voltage point
For 200/208/220/230/240 VAC models:
180-220: setting the low voltage point in parameter 3 from
13
180Vac to 220Vac. (Default: 180Vac) For 100/110/115/120/127 VAC models:
90-115: setting the low voltage point in parameter 3 from
90Vac to 115Vac. (Default: 90Vac)
08: Bypass frequency range setting
Interface
Setting
Parameter 2: Set the acceptable high frequency point and
acceptable low frequency point for Bypass mode by pressing
the Down key or Up key.
HLS: Bypass high frequency point
For 50Hz output frequency models:
51-55Hz: setting the frequency high loss point from 51Hz
to 55HZ(Default: 53.0Hz)
For 60Hz output frequency models:
61-65Hz: setting the frequency high loss point from 61Hz
to 65Hz(Default: 63.0Hz)
LLS: Bypass low Frequency point
For 50Hz output frequency models:
45-49Hz: setting the frequency low loss point from 45Hz to
49HZ(Default: 47.0Hz)
For 60Hz output frequency models:
55-59Hz: setting the frequency low loss point from 55Hz to
59Hz(Default: 57.0Hz)
09: Programmable outlets enable/disable
Interface
Setting
Parameter 2: Enable or disable programmable outlets.
ENA: Programmable outlets enable
DIS: Programmable outlets disable (Default)
10: Programmable outlets setting
Interface
Setting
Parameter 2: Set up backup time limits for programmable
outlets.
0-999: setting the backup time limits in minutes from 0-999
for programmable outlets which connect to non-critical
devices on battery mode. (Default: 999)
11: Autonomy limitation setting
Interface
Setting
Parameter 2: Set up backup time on battery mode for
general outlets.
0-999: setting the backup time in minutes from 0-999 for
general outlets on battery mode.
DIS: Disable the autonomy limitation and the backup time
will depend on battery capacity. (Default)
Note: When setting as 0 , the backup time will be only 10
seconds.
14
12: Battery total AH setting
Interface
Setting
Parameter 2: Set up the battery total AH of the UPS.
7-999: setting the battery total capacity from 7-999 in AH.
Please set the correct battery total capacity if external
battery bank is connected.
13: Maximum charger current setting
Interface
Setting
Parameter 3: Set up the maximum charger current. 1/2/4/6/8: setting the maximum charger current in 1/2/4/6/8 Ampere. (Default: 2A) Note: Please set the appropriate charger current based on battery capacity used. The recommended charging current is 0.1C~0.3C of battery capacity as following table for reference.
Battery capacity(AH) Total charging current (A)
7~20
2
20~40
4
40~60
6
60~80
8
80~100
10
14: Charger boost voltage setting
Interface
Setting
Parameter 2: Set up the charger boost voltage. 2.25-2.40: setting the charger boost voltage from 2.25 V/cell to 2.40V/cell. (Default: 2.36V/cell)
15: Charger float voltage setting
Interface
Setting
Parameter 2: Set up the charger float voltage.
2.20-2.33: setting the charger float voltage from 2.20
V/cell to 2.33V/cell. (Default: 2.28V/cell)
16: EPO logic setting
Interface
Setting
Parameter 2: Set up the EPO function control logic.
AO: Active Open (Default). When AO is selected as EPO
logic, it will activate EPO function with Pin 1 and Pin 2 in
open status.
AC: Active Close. When AC is selected as EPO logic, it will
activate EPO function with Pin 1 and Pin 2 in close status.
17: External output isolation transformer connection
Interface
Setting
15
Parameter 2: Allow or disallow external output isolation transformer connection.
ENA:
an external
output isolation transformer.
DIS:
external
output isolation transformer. (Default)
18: Display setting for autonomy time
Interface
Setting
Parameter 2: Set up the display setting for autonomy time
EAT: If EAT is selected, it will display the remaining
autonomy time. (Default)
RAT: If RAT is selected, it will show accumulated autonomy
time so far.
19: Acceptable input voltage range setting
Interface
Setting
Parameter 2: Set the acceptable high voltage point and
acceptable low voltage point for input voltage range by
pressing the Down key or Up key.
HLS: Input high voltage point
260/270/280: setting the high voltage point in parameter
2. (Default: 280Vac)
LLS: Input low voltage point
60/65/70/75/80: setting the low voltage point in
parameter 2. (Default: 60Vac)
00: Exit setting Interface
Setting Exit the setting mode.
16
3-6. Operating Mode Description
Operating mode Description
Online mode
When the input voltage is within acceptable
range, UPS will provide pure and stable AC power
to output. The UPS will also charge the battery at
online mode.
ECO mode
Energy saving mode:
When the input voltage is within voltage
regulation range, UPS will bypass voltage to
output for energy saving. The UPS will also
charge the battery at ECO mode.
LCD display
Frequency Converter mode Battery mode
Bypass mode
Standby mode
When input frequency is within 40 Hz to 70 Hz, the UPS can be set at a
constant output frequency, 50 Hz or 60 Hz. The UPS will still charge battery
under this mode.
When the input voltage is beyond the acceptable range or power failure, the
UPS will backup power from battery and alarm is sounding every 5 seconds.
When input voltage is within acceptable range but UPS is overload, UPS will
enter bypass mode or bypass mode can be set by front panel. Alarm is sounding
every 10 seconds.
UPS is powered off and no output supply power, but still can charge batteries.
Fault mode
When a fault has occurred, the ERROR icon and the fault code will be displayed.
3-7. Faults Reference Code
Fault event
Fault code Icon Fault event
Fault code Icon
Bus start fail
01
x Battery voltage too high 27
x
Bus over
02
x Battery voltage too low 28
x
Bus under
03
x Charger output short
2A
x
Inverter soft start fail 11
x Over temperature
41
x
Inverter voltage high 12
x Overload
43
Inverter voltage Low 13
x Charger failure
45
x
Inverter output short 14
x Over input current
49
x
17
3-8. Warning indicator Warning Low Battery Overload Over input current Battery
is not connected
Over Charge
Icon (flashing)
Code
Alarm Sounding every 2 seconds Sounding every second Sounding 2 beep every 10 seconds Sounding every 2 seconds Sounding every 2 seconds
EPO enable
Sounding every 2 seconds
Over temperature
Sounding every 2 seconds
Charger failure
Sounding every 2 seconds
Battery fault
Sounding every 2 seconds (At this time, UPS is off to remind users something wrong with battery)
Out of bypass voltage range
Sounding every 2 seconds
Bypass frequency unstable
Sounding every 2 seconds
Battery replacement
Sounding every 2 seconds
EEPROM error
Sounding every 2 seconds
Note 1 : When the fault is happened on line mode, the UPS must transfer to bypass mode except Inverter short circuit if the
input voltage within the range of bypass mode.
18
4. Troubleshooting
If the UPS system does not operate correctly, please solve the problem by
using the table below.
Symptom
No indication and alarm even though the mains is normal.
Possible cause The AC input power is not connected well.
The AC input is connected to the UPS output.
Remedy
Check if input power cord firmly connected to the mains.
Plug AC input power cord to AC input correctly.
The icon and the warning
code flashing on LCD display and alarm is sounding every 2 seconds.
The icon ,
and the
warning code flashing on LCD display and alarm is sounding every 2 seconds.
Fault code is shown as 27 on LCD display and alarm is continuously sounding.
Fault code is shown as 28 on LCD display and alarm is continuously sounding.
The icon , and the
warning code flashing on LCD display and alarm is sounding every second.
Fault code is shown as 49 on LCD display and alarm is continuously sounding.
Fault code is shown as 43 and the icon is lighting on LCD display. Alarm is
continuously sounding.
EPO function is activated.
The external or internal battery is incorrectly connected.
Battery voltage is too high or the charger is fault.
Battery voltage is too low or the charger is fault.
UPS is overload
UPS is overloaded. Devices connected to the UPS are fed directly by the
electrical network via the Bypass. After repetitive overloads, the UPS is
locked in the Bypass mode. Connected devices are fed directly by the mains.
UPS is over input current.
The UPS shut down automatically because of overload at the UPS output.
Set the circuit in closed position to disable EPO function.
Check if all batteries are connected well.
Contact your dealer.
Contact your dealer.
Remove excess loads from UPS output. Remove excess loads from UPS output.
Remove excess loads from UPS output first. Then shut down the UPS and restart
it.
Remove excess loads from UPS output.
Remove excess loads from UPS output and restart it.
19
Symptom Fault code is shown as 14 on LCD display and alarm is continuously
sounding.
Fault code is shown as 01, 02, 03, 11, 12, 13 and 41 on LCD display and alarm
is continuously sounding.
Battery backup time is shorter than nominal value.
Possible cause The UPS shut down automatically because short circuit occurs on
the UPS output. A UPS internal fault has occurred. There are two possible
results: 1. The load is still supplied, but directly from AC power via bypass.
2. The load is no longer supplied by power. Batteries are not fully charged
Batteries defect
Remedy Check output wiring and if connected devices are in short circuit
status.
Contact your dealer
Charge the batteries for at least 5 hours and then check capacity. If the
problem still persists, consult your dealer. Contact your dealer to replace
the battery.
Fault code is shown as 2A on LCD display and alarm is continuously sounding.
Fault code is shown as 45 on LCD display. At the same time, alarm is
continuously sounding.
The short circuit occurs on the charger output.
The charger does not have output and battery voltage is less than 10V/PC.
Check if battery wiring of connected external pack is in short circuit status.
Contact your dealer.
5. Storage and Maintenance
Operation
The UPS system contains no user-serviceable parts. If the battery service life
(3~5 years at 25°C ambient temperature) has been exceeded, the batteries must
be replaced. In this case, please contact your dealer.
Be sure to deliver the spent battery to a recycling facility or ship it to your dealer in the replacement battery packing material.
Storage
Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry
location. During storage, recharge the battery in accordance with the following table:
Storage Temperature
Recharge Frequency
Charging Duration
-25°C – 40°C
Every 3 months
1-2 hours
40°C – 45°C
Every 2 months
1-2 hours
20
6. Specifications
MODEL
1K Tower
2K Tower
3K Tower
CAPACITY*
INPUT
Low Line Transfer
Voltage Range
Low Line Comeback High Line Transfer
High Line Comeback
Frequency Range Phase
Power Factor
THDi
OUTPUT
Output voltage
AC Voltage Regulation
Frequency Range
(Synchronized Range)
Frequency Range
Current Crest Ratio
Harmonic Distortion
Transfer AC Mode to Batt. Mode
Time
Inverter to Bypass
Waveform (Batt. Mode)
EFFICIENCY
AC Mode
ECO Mode
Battery Mode
BATTERY
Battery Type
Numbers
Standard Recharge Time
Model
Charging Current
1000VA/900W
2000VA/1800W
3000VA / 2700W
180VAC/160VAC/140VAC/60VAC ± 5 % or 90VAC/80VAC/70VAC/60VAC ± 5 % ( based on
load percentage 100% – 80 % / 80 % – 70 % / 70 – 60 % / 60 % – 0)
195VAC/175VAC/155VAC/70VAC ± 5 % or 100VAC/90VAC/80VAC/70VAC ± 5 %
280 VAC ± 5 %
270 VAC ± 5 %
45Hz ~ 65 Hz Single phase with ground
0.99 @ full load
17% @ 220-230VAC or 110~120VAC THDU < 1.6% @ input and full linear load
condition
200/208/220/230/240VAC or 100/110/115/120/127 VAC ± 1% (Batt. Mode)
47 ~ 53 Hz or 57 ~ 63 Hz
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz (Batt. Mode) 3:1
2 % THD (Linear Load) ; 4 % THD (Non-linear Load) Zero
< 4 ms Pure Sinewave
78% @ full charged battery 85% @ full charged battery
86% max
83% @ full charged battery
84% @ full charged battery
90% @ full charged battery
87% max
88% max
12V/7AH
12V/9AH
12V/9AH
3
4
6
3 hours recover to 95% capacity for internal battery@ 2A charging current
default 2A, max. 8A adjustable
Charging Voltage
41.0 VDC ± 1%
54.7 VDC ± 1%
82.1 VDC ±1%
PHYSICAL
Standard Model
Dimension, D X W X H (mm)
Net Weight (kgs)
ENVIRONMENT
Operation Humidity
Noise Level
MANAGEMENT
23
Less than 55dBA @ 1 Meter (With fan speed control)
421 X 190 X 318 27
20-95 % RH @ 0- 40°C (non-condensing)
525 x190 x 318 39.3
Less than 65dBA @ 1 Meter (With fan speed control)
Smart RS-232 or USB
Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix and MAC
Optional SNMP
Power management from SNMP manager and web browser
- Derate capacity to 80% of capacity in Frequency converter mode and to 80% when the output voltage is adjusted to 100VAC, 200VAC or
208VAC.
** Product specifications are subject to change without further notice.
21