Dwyer P-AVLV-B Series AVLV Low Air Velocity Transmitter User Guide
- June 15, 2024
- Dwyer
Table of Contents
- Dwyer P-AVLV-B Series AVLV Low Air Velocity Transmitter
- Product Information – Series AVLV Low Air Velocity Transmitter with
- Specifications
- Installation **
- PROGRAMMING MENUS
- APPENDIX III: BACnet MS/TP Operation **
- BACnet MS/TP DIP Switch Settings
- APPENDIX IV: Programming Via BACnet MS/TP Communication Protocol
- APPENDIX VI: Property Tables
- APPENDIX III: Menu Flow Chart **
- Averaging Menu
- FAQ
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Dwyer P-AVLV-B Series AVLV Low Air Velocity Transmitter
Product Information – Series AVLV Low Air Velocity Transmitter with
BACnet Communication
The Series AVLV Low Air Velocity Transmitter quickly and accurately measures air velocity or volumetric flow in imperial or metric units. Simultaneous current and voltage outputs on all models provide universal inputs to monitoring equipment while the output range, units, and 0-5/10 VDC output can be configured via local DIP switches. The optional integral display, or the portable remote display tool, provide a convenient way to locally monitor process values and configure the unit. Models are available in 1% and 2% accuracy models and low velocity ranges to suit a variety of needs, and the optional BACnet MS/TP or Modbus® RTU/ASCII communication protocol allows units to be daisy-chained while providing access to all of the velocity and flow data, as well as additional information such as air temperature. The lower ranges in these high accuracy units allow for applications in quality intensive environments, such as the pharmaceutical industry.
ACCURACY CHART
Velocity Range| **Accuracy Rating**
20 to 100 FPM (0.15 to 0.5 m/s)
20 to 200 FPM (0.15 to 1.0 m/s)
20 to 300 FPM (0.15 to 1.5 m/s)
20 to 400 FPM (0.15 to 2.0 m/s)| ± (2% of reading + 0.04 m/s [7.9 FPM])
± (1% of reading + 0.04 m/s [7.9 FPM])
± (2% of reading + 0.04 m/s [7.9 FPM])
± (1% of reading + 0.04 m/s [7.9 FPM])
± (2% of reading + 0.05 m/s [9.8 FPM])
± (1% of reading + 0.05 m/s [9.8 FPM])
± (2% of reading + 0.06 m/s [11.8 FPM])
± (1% of reading + 0.06 m/s [11.8 FPM])
Accuracy dependent on model selected when ordering.
Specifications
- Service: Clean air and non-combustible, compatible gases.
- Wetted Materials: Consult factory.
- Range: 100, 200, 300, 400 FPM (0.5, 1, 1.5, 2.0 m/s); field selectable.
- Accuracy: See accuracy chart.
- Humidity Limits: 5 to 95% RH, non-condensing.
- Output Signals: 4-20 mA, 0-5 VDC, 0-10 VDC.
- Response Time (90%): 4 s, typical; 1 s at constant temperature.
- Zero and Span Adjustments : Digital push buttons.
- Output Load Resistance: Current output: 0 to 1100 max.; Voltage output: Minimum load resistance 1 k.
- Current Consumption: 60 mA max.
- Display: 5 digit LCD (optional).
- Electrical Connections: Analog – Power and output: four wire removable European 16 to 26 AWG.
- Supported Communication Baud Rates: 9600, 19200, 38400, 57600, 76800, 115200 (optional).
- Device Load: 1/8 unit load.
- Electrical Entry: 1/2 NPS thread; Accessory – Cable gland for 5 to 10 mm diameter cable, A-151.
- Enclosure Rating: NEMA 4X (IP66).
- Mounting Orientation: Flow direction must be parallel to the sensor tip.
- Weight: 6.0 oz (160 g).
- Agency Approval: BTL, CE.
Installation **
**
Duct Mount:
The transmitter should be mounted away from fans, corners, heating and
cooling coils, and other equipment that will affect the measurement of the air
velocity. It is recommended that the AVLV is mounted 10 duct diameters
downstream of any disturbances and 5 duct diameters upstream of any
disturbances, if possible.
- Mark and drill a 0.750-0.938 (20-24 mm) diameter hole into the duct.
- Insert and center the duct mount flange in the previously drilled hole and mark location of the three mounting screw holes.
- Remove the mounting flange and drill or punch the mounting holes in the marked locations.
- Fasten the flange to the duct using three #8 x 1/2 pan head sheet metal screws. Do not over tighten screws.
- Insert the AVLV probe into the duct mount flange and set the desired insertion depth.
- Note the flow direction and unit alignment as shown on sensor tip and product label, tighten probe retention set screw on the duct mount flange screw to affix the probe in place.
Electrical Connection:
The Series AVLV is powered and simultaneously transmits a two-wire 4-20 mA
current output and a three-wire 0-5 VDC or 0-10 VDC voltage output via a
removable four conductor terminal block. The transmitter power supply common
is used to reference the current and voltage outputs so either current,
voltage, or current and voltage may be wired according to the application. The
range of the voltage output can be selected using the on board DIP switches as
described in the Analog DIP Switch Settings section of this manual.
Power Supply:
Choose a power supply with a voltage and current rating sufficient to meet
the power specifications under all operating conditions. If the power supply
is unregulated, make sure the output voltage remains within the required
voltage range under all power line conditions. Ripple on the supply should not
exceed 100 mV.
CAUTION
DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS. PERMANENT DAMAGE NOT COVERED
BY WARRANTY WILL RESULT.
Current Output Operation
CAUTION
DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS. PERMANENT DAMAGE NOT COVERED
BY WARRANTY WILL RESULT.
The terminal block is removable, and each of the terminals are labeled
underneath the terminal block on the circuit board. As the power supply and
outputs share the same common signal (GND), the outputs may have separate
wires but must effectively join at terminal 2 of the transmitter, as shown in
Figure 1.
The connections to the transmitter are made to terminals 1, 2, and 3 (PWR, GND, and IOUT respectively) on the terminal block as shown in Figure 4.
Although low loop resistances are recommended, the absolute maximum current
loop load resistance, RMAX , is defined by the following the equation:
RMAX = (VPS – 2.0) / 0.02 where VPS is the power supply voltage
For a 24 VDC nominal power supply, this evaluates to RMAX = 1100 ohms.
Shielded two wire cable is recommended for current output loop wiring. Ground
the shield at the power supply end only. The maximum length of connecting wire
between the current transmitter and the receiver is a function of wire size
and receiver resistance. That portion of the total current loop resistance
represented by the resistance of the connecting wires themselves should not
exceed 10% of the receiver resistance. For extremely long runs (over 1,000
ft.), it is desirable to select receivers with higher resistances in order to
keep the size and cost of the connecting leads as low as possible. In
installations where the connecting run is no more than 100 ft, connecting lead
wire as small as No. 22 Ga. can be used.
Voltage Output Operation
CAUTION
DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS. PERMANENT DAMAGE NOT COVERED
BY WARRANTY WILL RESULT.
The terminal block is removable, and each of the terminals are labeled
underneath the terminal block on the circuit board. The voltage output and the
power supply must have separate wire leads that are only joined at terminal 2
of the transmitter, as shown in Figure 2.
Additional error may occur for the voltage output if a single wire is used or if the wires are joined at the power supply or receiver. The connections to the transmitter are made to terminals 1, 2, and 4 (PWR, GND, and VOUT respectively) on the terminal block as shown in Figure 4. Figure 2: Voltage output wiring The minimum receiver load is 1 kΩ. The resistance due to the wire should be low compared to the receiver load resistance. While the voltage at the terminal block remains unchanged with a 10 mA current flow, resistive losses in the wiring do cause errors in the voltage delivered to the receiver. For a 1% accurate gauge, the resistance of the wires should be less than 0.1% of the value of the receiver load resistance. This will keep the error caused by the current flow below 0.1%. The output across VOUT and COM will be either 0-5 VDC, 0-10 VDC, or the inverse depending on the DIP switch setting. See the Analog DIP Switch Settings section for more information.
Simultaneous Current and Voltage Output Operation
CAUTION
DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS. PERMANENT DAMAGE NOT
COVERED BY WARRANTY WILL RESULT.
The terminal block is removable, and each of the terminals are labeled
underneath the terminal block on the circuit board. The voltage output and the
power supply must have separate wire leads that are only joined at terminal 2
of the transmitter, as shown in Figure 3.
Additional error may occur for the voltage output if a single wire is used or if the wires are joined at the power supply or receiver. The connections to the transmitter are made to terminals 1, 2, 3 and 4 (PWR, GND, IOUT, and VOUT respectively) on the terminal block as shown in Figure 4, which reflects both the 4-20 mA and 0-5/10 VDC outputs in the same circuit. Details of each output are detailed in their electrical connection sections.
ANALOG DIP SWITCH SETTINGS
The analog output DIP switches (SW1) are located above the terminal blocks on
the left are as shown in Figure 4.
A small screw driver or pen can be used to change the position of the switches as required.
CAUTION
All power should be turned off to the transmitter before adjusting the DIP
switch settings to avoid electrical shock.
Factory Default Settings (DIP SW1 – All Switches ON)
- Range = Highest Range Setting (400 FPM)
- Units = Imperial (FPM)
- Voltage Output Range = 0-10 VDC
- Direct / Reverse Output Action = Direct
Setting the Air Velocity Range
The range of the instrument is selected by using DIP switches 1 and 2 on SW1.
Table 1 shows the maximum full scale value for the selected range and unit.
Refer to Setting the Engineering Units section for information on setting the
unit.
DIP Switch SW1 | Full Scale Range |
---|---|
1 | 2 |
ON | ON |
ON | OFF |
OFF | ON |
OFF | OFF |
Table 1: DIP Switch SW1 Settings for Full Scale Range
Setting the Engineering Units
The Series AVLV can be configured to indicate velocity in imperial (FPM, CFM)
or metric (m/s, m3/h) units using DIP switches 4 and 5 on SW1, and Table 2
shows the values. The units will be displayed on the optional LCD display if
connected.
DIP Switch SW1 | Units |
---|---|
4 | 5 |
ON | ON |
ON | OFF |
OFF | ON |
OFF | OFF |
DIP Switch SW1 Settings for Units
The default operating mode is velocity, but changes can be made, such as flow
mode, via the menu system while an optional display or remote display
accessory is connected. Please refer to Appendix VII for a full menu flow
chart.
Setting the Output Voltage Range
Voltage Output can be either 0-5 VDC or 0-10 VDC depending on the position of
DIP Switch 6 ON SW1.
- When the switch is in the ON position, the output will be 0-10 VDC.
- When the switch is in the OFF position, the output will be 0-5 VDC.
Setting the Input / Output Action
The output will either follow the process directly (DIRECT) or inverted
(REVERSED) based on the position of DIP Switch 7 on SW1.
- When the switch is in the ON position, the output directly follows the input (i.e. output increases as the input increases).
- When the switch is in the OFF position, the output acts in reverse of the input (i.e. output decreases as the input increases).
CALIBRATION
NOTICE: There is a 5 second delay from the time the zero or span calibration
buttons are released until the time that the change in calibration takes
place. This delay is used to reduce vibration or disturbances of the user
related to the button presses.
- The security level that is set in the Programming Menu section of the manual will determine which calibrations, if any, may be adjusted by the user.
Zero Calibration
The zero calibration can be set by covering the sensor to ensure no air flow
and pressing the zero button for 3 seconds. If either the remote or local LCD
is present, the display will read ZERO and then sequence back to the home
display.
SPAN Calibration
The span calibration can be adjusted only after setting the zero adjustment.
It must be completed within 5 minutes of the last zero calibration. The span
calibration button will be ignored until the zero calibration is completed.
Place the sensor in airflow that matches the maximum selected range of the
transmitter. Press and hold the span button for 3 seconds. If either the
remote or local LCD is present, the display will read SPAN and then sequence
back to the home display. If the span calibration is attempted before
adjusting the zero calibration, the FAIL error message will be displayed
briefly before returning to the home display.
LCD Display
The Series AVLV can be ordered with an optional, integral LCD. It comes with a
housing cover and overlay to protect the display. The display will plug into
the pins as shown in Figure 5.
If the display is not needed for normal operation, the transmitter can be ordered without the LCD. Another option for models that do not have a display would be to use a Model A-435-A remote display tool which can plug into the connector shown in Figure 6.
The remote display tool has two buttons that function identically to the buttons on the PCB.
Display Error Messages
OVER = The air velocity is greater than the maximum span value causing an Over
Range Error
UNDER= The air velocity is less than the minimum span value causing an Under
Range Error
FAIL= When the span or zero buttons are pressed, the air velocity value is out
of the range to allow a correct setting. This may be due to a sensor failure.
Err1 = The sensor is damaged.
PROGRAMMING MENUS
Home Menu
During normal operation, the display will be in the Home Menu and will display
the current measured pressure and the engineering units.
Menu Access Security
While in the Home Menu, press and hold the Zero and Span buttons
simultaneously until SECUR appears on the display in order to access the other
programming menus. Upon releasing the buttons, the display will indicate the
current security level. If the current security level is the security level
desired (i.e. Security Level 0), press and hold the span button for 3 seconds
to enter the Velocity or Air Flow Menu. If the security level is not the
desired level, the security level can be changed temporarily to a lower
security level or permanently to a higher level of security by pressing the
zero button. A security code will appear on the display, and it can be changed
to one of the codes listed in Table 3. The span button chooses which digit and
the zero button increments the value of that digit. Pressing and holding the
span button will store the value. The level of access to the programming menus
and the calibration is limited based on the security level. Table 3 details
the level of access for each security level.
Security Level | Setting | Access |
---|---|---|
View Menu | Edit Menu | Span |
0 | 000 | Yes |
1 | 111 | Yes |
2 | 222 | No |
3 | 333 | No |
Security Settings
Mode Selection / Digital Dampening Menu
From the home display, pressing the span and zero button simultaneously for 3
seconds will access the Menu Security Level. If the level is set to 0 or 1,
pressing and holding the span button for 3 seconds, a second time, will access
the Mode Selection Menu. The display will default to air velocity when first
powered up. Pressing the zero button will cycle to air flow. Once the desired
mode is displayed, pressing and holding the span button for 3 seconds will
save the selected mode and display the digital dampening or averaging
parameter. This parameter stabilizes the output and the display by averaging
the readings. There are 2.5 readings taken each second and the user can select
the number of seconds that they would like to average, up to 240 seconds. The
display and the output will continue to update at a rate of 2.5 updates per
second, but the moving average is used for these updates.
Velocity Mode
K-Factor Adjustment
If the Velocity Mode was selected, pressing and holding the span after
adjusting the digital dampening will enter the Velocity Mode and the
transmitter will display the engineering unit that has been selected by the
DIP switch. Pressing and holding the span button for 3 seconds will enter the
K – Factor adjustment. The K – Factor can be adjusted between 0.001 to 9.999.
The K-Factor can be adjusted by pressing the span button to select the digit
and pressing the zero button to increment the value of the digit. Pressing and
holding the span button for 3 seconds will enter the Maximum Output Adjustment
parameter.
Flow Mode
K-Factor Adjustment
If the Flow Mode was selected, pressing and holding the span after adjusting
the digital dampening will enter the Flow Mode and the transmitter will
display the engineering unit that has been selected by the DIP switch.
Pressing and holding the span button for 3 seconds will enter the K–Factor
adjustment. The K–Factor can be adjusted between 0.001 to 9.999. The K-Factor
can be adjusted by pressing the span button to select the digit and pressing
the zero button to increment the value of the digit. Pressing and holding the
span button for 3 seconds will enter the Area Adjustment parameter.
Area Adjustment
For flow applications, the area is multiplied by the velocity to determine the
volumetric air flow. The area will be listed in either CFM or m3/h depending
on the DIP switch settings. The units will appear on the display at the time
of adjustment. The area can be adjusted by pressing the span button to select
the digit and pressing the zero button to increment the value of the digit.
Pressing and holding the span button for 3 seconds will enter the Maximum
Output Adjustment parameter.
Maximum Output Adjustment
The maximum output can be equivalent to air velocity or air flow. After
adjusting the K-Factor, the display will indicate if the adjustment is set for
velocity or air flow. Pressing the zero button will toggle between the
selections. Pressing and holding the span button for 3 seconds will enter the
maximum output adjustment. The maximum output can be adjusted by pressing the
span button to select the digit and pressing the zero button to increment the
value of the digit. Pressing and holding the span button for 3 seconds will
save this value and go to the Security Update Menu.
Security Update / Save Changes Menu
The Security Update Menu allows the security level to be set either higher or
lower than the current security level setting. This security level will be
displayed the next time the Menus are accessed from the home screen. Pressing
the zero button cycles through the security levels. Pressing and holding the
span button for 3 seconds accepts the new security level and gives the option
to save all the menu changes. Pressing the zero button will toggle between yes
and no. Yes will save the changes made to all menu items and no will discard
all the changes made to all menu items. If the display is set to yes, pressing
and holding the span will save the menu items and return the display to the
home position.
FACTORY DEFAULT PROCEDURE
In order to reset all of the menu settings back to their factory programmed
values, press and hold both the span and zero buttons simultaneously for 10
seconds until FACt is displayed on the LCD. Upon releasing the buttons, the
unit will be factory defaulted. Since resetting the transmitter will wipe out
all changes, it is necessary to zero (and possibly span) the transmitter
before taking measurements.
MAINTENANCE/REPAIR
Upon final installation of the Series AVLV Air Velocity Transmitter, no
routine maintenance is required besides zeroing the transmitter occasionally.
Besides routine calibration and installation of the LCD, the Series AVLV is
not field serviceable, and it is not possible to repair the unit. Field repair
should not be attempted and may void warranty.
WARRANTY/RETURN
Refer to “Terms and Conditions of Sales” in our catalog and on our website.
Contact customer service to receive a Return Goods Authorization number before
shipping the product back for repair. Be sure to include a brief description
of the problem plus any additional application notes.
APPENDIX I: Air Velocity / Air Flow Calculations
Velocity in m/s is then calculated from the equation:
Velocity (m/s) = Velocity (FPM) x 0.00508
Flow in m3/h is then calculated using the below equation:
Flow (CFM) = Area (ft2) x K-Factor x Velocity (FPM)
Flow (m3/h) = Flow (CFM) x 1.6992
APPENDIX II: Maximum Flow
Max Flow | Max K Factor x Area |
---|---|
CFM | m 3 /h |
5885000 | 9999000 |
Maximum flow values
APPENDIX III: BACnet MS/TP Operation **
**
NOTICE
Wiring should comply with Electrical Characteristics of Generators and
Receivers for Use in Balanced Digital Multipoint Systems, TIA/EIA-485-A-1998,
Telecommunications Industry Association, 1998.
- Wiring should comply with ANSI/ASHRAE Standard 135-2010 BACnet A Data Communication Protocol for Building Automation and Control Networks, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., 2010.
- Communications wiring must be in a daisy-chain fashion. Star connections are not permitted.
- Cable shield must be connected to earth ground at one location only.
Figure 7 shows how to connect the AVLV in a network containing a common power supply. Use a cable containing two twisted pairs. One pair is to be used for D1(+) and D0(-). The other pair is to be used for power and common. This configuration is not suitable for AC supplies. Use a DC supply only. Care should be taken that there are not too many devices powered from the same supply as voltage drops will occur in the wiring. If you have many devices, or have long cable runs, the local supply configuration may be a better choice.
Figure 8 shows how to connect the AVLV in a network containing individual local supplies. Use a cable containing a twisted pair and a single conductor. The pair is to be used for D1(+) and D0(-). The single conductor is to be used for common. Both AC and DC supplies are suitable for this configuration.
In either configuration you must use shielded cable. The AVLV has a shield terminal for a convenient location to make connections. It is not electrically connected to the AVLV. Connect the shield to earth ground at one location only to prevent ground loops. All devices in the network should be daisy chained. Star connections and T connections are not permitted. The D1(+) and D0(-) lines must be terminated at both ends with a 120 ohm resistor. If the AVLV is an end device it has an on-board resistor that may be used. See BACnet MS/TP DIP Switch Settings to enable it. The network must be biased properly. If needed, there are bias resistors on-board the AVLV. No more than two sets of bias resistors should be enabled in the network. See BACnet DIP Switch Settings to enable them.
BACnet MS/TP DIP Switch Settings
Use the middle DIP Switch SW2 to configure the BACnet MS/TP MAC communication protocol address of the device. The LCD will show the address when the transmitter is powered on. Valid addresses range from 0 to 127. By default, the device is shipped with the address 127 (as shown in Figure 10).
A valid and unused address should be set before connecting to an existing network. However, the address can be changed while the device is operational. If the address is changed, the device will stop responding to the currently configured address immediately. The device waits 15 seconds after the last switch change before applying the new address. The device will not function properly if an invalid address is set. The red LED will periodically blink once indicating an invalid address. The LCD will display A Err when the transmitter is powered on if the address is invalid. See Appendix V for setting the BACnet MS/TP MAC address of the device. Use the right DIP Switch SW3 to configure other hardware and software options.
Switch | On | Off |
---|
1-2 – Display Units Selection 3-4 – Reserved
5 – Reset BACnet Configuration to Factory Defaults
6 – D1(+) Network Resistor
7 – D0(-) Network Resistor
8 – Terminating resistor| Reset settings at Power On 511Ω Pull-up to 5V 511Ω
Pull-down to GND 120Ω between D0(-) and D1(+)| Settings Preserved Pull-up not
connected Pull-down not connected Open
DIP switch SW3 functions
APPENDIX IV: Programming Via BACnet MS/TP Communication Protocol
Supported Baud Rates | Data Size | Parity | Stop Bits |
---|
9600
19200
38400
57600
76800
115200| 8| None| 1
Supported BACnet communication protocol MS/TP configurations
Auto-Baud Serial Configuration
Auto-baud serial configuration enables the device to determine the baud rate
directly from the serial traffic. This allows a device to be quickly and
easily deployed after a valid BACnet Communication Protocol MS/TP address is
chosen. To activate auto-baud serial configuration, set a valid BACnet
Communication Protocol MS/TP address using the left DIP switch SW2, connect
the serial bus and power wires, and then apply power. The device will power up
and begin examining the serial bus for communication. The Red LED will
repeatedly flash twice, indicating that auto-baud serial configuration is in
progress. If the device is setup offline or away from the main network, it is
necessary to generate BACnet Communication Protocol MS/TP traffic in order to
configure the serial communication. Initiating a WhoIs command is a good
method to generate BACnet Communication Protocol MS/TP traffic and verify the
device is working properly. Note that while serial configuration is in
progress, the device may not respond to requests. The device may require
multiple requests to complete the serial configuration process. The auto-baud
serial configuration process will complete once a WhoIs or Read Property
command is successfully received and processed. The auto-baud serial
configuration procedure is started after a power-cycle and after a change to
the MS/TP address.
BACnet MS/TP Communication Protocol Object Overview
**Object Type| Dynamically Creatable| Dynamically
Deletable| Object Identifier| ****Object Name**
---|---|---|---|---
Device Analog Input
Analog Value
Binary Value| No No
No
No| No No
No
No| 607xxx AI1 AI2 AI3 AI4 AV1 AV2 AV3 AV4 BV1 BV2 BV3| AVLV Velocity Velocity
FPM Velocity MPS Temperature F Temperature C Flow CFM Flow CMH Flow Area SqFt
Flow Area SqM Zero
Span
Restore Factory Pressure Values
Supported BACnet MS/TP communication protocol objects
Device Information
The default device object identifier is 607xxx, where xxx is replaced by the
MS/TP MAC address set by the middle DIP switch SW2. The object identifier
value will change as the MS/TP MAC address changes. However, if a specific
object identifier is written via BACnet MS/TP Communication Protocol, then
that value is stored and changes to the MS/TP MAC address will no longer
affect the object identifier. See Appendix VI for the device object property
tables.
NOTICE
Changes to Max Master and Max Info frames require a power cycle/reset to take
effect.
Accessing the Measurements
The analog input object AI1 through AI4 are for viewing Air Velocity or
Temperature in the desired engineering units. The object property tables for
these analog input objects can be found in Appendix VI.
Analog value object AV1 through AV4 are for viewing the Air Flow or Flow Area
calculated values in the desired engineering units. The object property tables
for the analog value objects can be found in Appendix VI.
Zero Calibration
Zero calibration can be done either with the push buttons or using BACnet
MS/TP communications. The unit should have no air flowing through it. When
using BACnet MS/TP communications, the binary value object (BV1) will be used
to signal the transmitter to zero the reading. The present value of this
object will be set to ACTIVE (1) to initiate the re-calibration of the zero
point of the sensor. The zero function will only work if the current velocity
is within ±2% of the span velocity of the previous zero. If the current
velocity is outside of this valid band, the zero function will fail and the
present value will be changed to INACTIVE (0). The zero function takes at most
10 seconds to complete. If after this time the present value remains ACTIVE
(1), then the command was executed successfully. The object property tables
for the binary value objects can be found in Appendix VI.
Span Calibration
In order to adjust the span calibration, place the unit in a flow with air
velocity that is associated with the maximum end of the transmitter range. The
binary value object (BV2) will be used to signal the transmitter to adjust
span. The present value will be set to ACTIVE (1) to initiate the span
calibration. The span calibration can be adjusted only after setting the zero
adjustment. It must be completed within 5 minutes of the last zero
calibration. The span calibration command will fail until the zero calibration
is completed and the present value will be returned to INACTIVE (0). The span
function takes at most 10 seconds to complete. If after this time, the present
value remains ACTIVE (1), then the command was executed successfully. The
object property tables for the binary value objects can be found in Appendix
VI.
Reset factory Defaults
Present values for the zero, span, and area can be restored to the factory
settings using the binary value object (BV3). The present value will be set to
ACTIVE (1) to initiate the factory default procedure. The factory default
takes at most 10 seconds to complete. If after this time, the present value
remains ACTIVE (1), then the command was executed successfully. The object
property tables for the binary value objects can be found in Appendix VI.
BACnet MS/TP Communication Protocol Services
Device Communication Control Service (DM-DCC-B)
This device supports the Device Communication Control Service BIBB. The
optional time duration in minutes is also supported. This device is configured
with a password that must be provided to successfully execute this command.
The password is “Dwyer”.
Reinitialize Device Service (DM-RD-B)
This device supports the Reinitialize Device Service BIBB. The supported
device states are COLDSTART and WARMSTART. All other states return error. This
device is configured with a password that must be provided to successfully
execute this command. The password is “Dwyer”.
APPENDIX V: Setting BACnet Communication Protocol MS/TP MAC Address of Unit
Switch Position| 1| 2| 3| 4| 5| 6| 7|
8
---|---|---|---|---|---|---|---|---
Address Value| 128| 64| 32| 16| 8| 4| 2| 1
Device objects
The address assignment is determined by adding the values for each of the
switches that are in the ON position. The transmitter comes from the factory
with all of the DIP switches, except position 1, in the ON position as shown
in Figure 10. The address of the transmitter would be 127 as it would be
64+32+16+8+4+2+1 = 127. Another example would be if the address desired was
008, the only DIP switch position in the ON position would be position 5 as
shown in Figure 11.
NOTICE: Though the minimum possible address would be address 0 when all the DIP switch positions were set to OFF, and the maximum possible address would be address 255 when all of the DIP switches were set to ON, but the transmitter only has valid address from 0 to 127. Any address outside of this range will give an error code.
APPENDIX VI: Property Tables
Property | Default Value | Property Data Type | Access |
---|
Object Identifier Object Name Object Type Present Value Status Flags Event
State Reliability Out Of Service Units| AI1
Velocity FPM ANALOG_INPUT (0)
Current reading 0 NORMAL (0) NOFAULT DETECTED(0) FALSE (0) Feet-per-minute
(77)| BACnet Object Identifier Character String BACnet Object Type Real BACnet
Status Flags BACnet Event State BACnet Reliability
Boolean BACnet Engineering Units| Read Read Read Read Read Read Read
Read/Write Read
Analog input – Velocity FPM
Property | Default Value | Property Data Type | Access |
---|---|---|---|
Object Identifier | 607xxx | BACnet Object Identifier | Read/Write |
Object Name | “AVLV Velocity” | Character String(32) | Read/Write |
Object Type | DEVICE(8) | BACnet Object Type | Read |
System Status | Operational(0) | BACnet Device Status | Read |
Vendor Name | “Dwyer Instruments, LLC” | Character String | Read |
Vendor Identifier | 607 | Unsigned | Read |
Model Name | “AVLV” | Character String | Read |
Firmware Revision | “1.0.14” | Character String | Read |
Application Software Version | “3.1.2.0” | Character String | Read |
Location | Character String(32) | Read/Write | |
Description | “Thermal Anemometer” | Character String(32) | Read/Write |
Protocol Version | 1 | Unsigned | Read |
Protocol Revision | 12 | Unsigned | Read |
Protocol Services Supported | See PICS | BACnet Services Supported | Read |
Protocol Object Types Supported | See Table 7 | BACnet Object Types Supported |
Read
Object List| See Table 7| BACnet Array| Read
Maximum APDU Length Accepted| 128| Unsigned| Read
Segmentation Supported| NO_SEGMENTATION (3)| BACnet Segmentation| Read
APDU Timeout| 0| Unsigned| Read
Number of APDU Retries| 0| Unsigned| Read
Max Master| 127| Unsigned| Read/Write
Max Info Frames| 1| Unsigned| Read/Write
Device Address Binding| Empty| BACnet Address Binding| Read
Database Revision| 0| Unsigned| Read
Serial Number (1000)| | Character String| Read
Sensor Serial Number (1001)| | Character String| Read
Device objects
Property | Default Value | Property Data Type | Access |
---|
Object Identifier Object Name Object Type Present Value Status Flags Event
State Reliability
Out Of Service Units| AI2
Velocity MPS ANALOG_INPUT (0)
Current reading 0
NORMAL (0) NOFAULT DETECTED(0) FALSE (0)
Meters-per-second
(74)| BACnet Object Identifier Character String BACnet Object Type Real BACnet
Status Flags BACnet Event State BACnet Reliability
Boolean BACnet Engineering Units| Read Read Read Read Read Read Read
Read/Write Read
Analog input – Velocity MPS
Property | Default Value | Property Data Type | Access |
---|
Object Identifier Object Name Object Type Present Value Status Flags Event
State Reliability
Out Of Service Units| AI3
Temperature F ANALOG_INPUT (0)
Current reading 0
NORMAL (0) NOFAULT DETECTED(0) FALSE (0)
Degrees-fahrenheit
(64)| BACnet Object Identifier Character String BACnet Object Type Real BACnet
Status Flags BACnet Event State BACnet Reliability
Boolean BACnet Engineering Units| Read Read Read Read Read Read Read
Read/Write Read
Analog input – Temperature F
Property | Default Value | Property Data Type | Access |
---|
Object Identifier Object Name Object Type Present Value Status Flags Event
State Reliability
Out Of Service Units| AI4
Temperature C ANALOG_INPUT (0)
Current reading 0
NORMAL (0) NOFAULT DETECTED(0) FALSE (0)
Degrees-celsius (206)| BACnet Object Identifier Character String BACnet Object
Type Real BACnet Status Flags BACnet Event State BACnet Reliability
Boolean BACnet Engineering Units| Read Read Read Read Read Read Read
Read/Write Read
Analog input – Temperature C
Property | Default Value | Property Data Type | Access |
---|
Object Identifier Object Name Object Type Present Value Status Flags Event
State Reliability Out Of Service Units| AV1
Flow CFM ANALOG_VALUE (2) Current reading 0 NORMAL (0) NOFAULT DETECTED(0)
FALSE (0) Cubic-feet-per-minute (84)| BACnet Object Identifier Character
String BACnet Object Type Real BACnet Status Flags BACnet Event State BACnet
Reliability Boolean BACnet Engineering Units| Read Read Read Read Read Read
Read Read/Write Read
Analog value – Flow CFM
Property | Default Value | Property Data Type | Access |
---|
Object Identifier Object Name Object Type Present Value Status Flags Event
State Reliability Out Of Service Units| AV2
Flow CMH ANALOG_VALUE (2) Current reading 0
NORMAL (0) NOFAULT DETECTED(0) FALSE (0) Cubic-meters-per-hour (135)| BACnet
Object Identifier Character String BACnet Object Type Real BACnet Status Flags
BACnet Event State BACnet Reliability Boolean BACnet Engineering Units| Read
Read Read Read Read Read Read Read/Write Read
Analog value – Flow CMH
Property | Default Value | Property Data Type | Access |
---|
Object Identifier Object Name Object Type Present Value Status Flags Event
State Reliability
Out Of Service Units| AV3
Flow Area SqFt ANALOG_VALUE (2)
1
0
NORMAL (0) NOFAULT DETECTED(0) FALSE (0)
Square-feet (1)| BACnet Object Identifier Character String BACnet Object Type
Real BACnet Status Flags BACnet Event State BACnet Reliability
Boolean BACnet Engineering Units| Read Read Read Read Read Read Read
Read/Write Read
Analog value – Flow area SqFt
Property | Default Value | Property Data Type | Access |
---|
Object Identifier Object Name Object Type Present Value Status Flags Event State Reliability
Out Of Service Units
| AV4
Flow Area SqM ANALOG_VALUE (2)
1
0
NORMAL (0) NOFAULT DETECTED(0) FALSE (0)
Square-meters (0)| BACnet Object Identifier Character String BACnet Object
Type Real BACnet Status Flags BACnet Event State BACnet Reliability
Boolean BACnet Engineering Units| Read Read Read Read/Write Read Read Read
Read/Write Read
Analog value – Flow area SqM
Property | Default Value | Property Data Type | Access |
---|
Object Identifier Object Name Object Type Present Value Status Flags Event State Reliability
Out Of Service
| BV1
Zero BINARY_VALUE (5)
ACTIVE (1)
0
NORMAL (0) NOFAULT DETECTED(0) FALSE (0)| BACnet Object Identifier Character
String BACnet Object Type BACnet Binary PV BACnet Status Flags BACnet Event
State BACnet Reliability
Boolean| Read Read Read Read/Write Read Read Read
Read/Write
Binary value – Zero
Property | Default Value | Property Data Type | Access |
---|
Object Identifier Object Name Object Type Present Value Status Flags Event
State Reliability
Out Of Service| BV2
Span BINARY_VALUE (5)
INACTIVE (0)
0
NORMAL (0) NOFAULT DETECTED(0) FALSE (0)| BACnet Object Identifier Character
String BACnet Object Type BACnet Binary PV BACnet Status Flags BACnet Event
State BACnet Reliability
Boolean| Read Read Read Read/Write Read Read Read
Read/Write
Binary value – Span
Property | Default Value | Property Data Type | Access |
---|
Object Identifier Object Name
Object Type Present Value Status Flags Event State Reliability
Out Of Service| BV3
Restore Factory Pressure Values BINARY_VALUE (5)
INACTIVE (0)
0
NORMAL (0) NOFAULT DETECTED(0) FALSE (0)| BACnet Object Identifier Character
String
BACnet Object Type BACnet Binary PV BACnet Status Flags BACnet Event State
BACnet Reliability
Boolean| Read Read
Read Read/Write Read Read Read
Read/Write
Binary value – Restore factory default values
APPENDIX III: Menu Flow Chart **
**
BUTTON PRESS LEGEND
- = PRESS ZERO BUTTON
- = PRESS SPAN BUTTON
- = PRESS AND HOLD ZERO BUTTON
- = PRESS AND HOLD SPAN BUTTON
- = PRESS AND HOLD ZERO AND SPAN BUTTONS
MENU CONVENTIONS
IN HOME POSITION:
IN MENU DISPLAY:
Averaging Menu
Velocity Mode Menu
Flow Mode Menu
Security Menu
FAQ
-
What kind of gases is the AVLV Low Air Velocity Transmitter compatible with?
The AVLV Low Air Velocity Transmitter is compatible with clean air and non- combustible gases. For specific compatibility information, please consult the factory. -
Can I configure the output range and units of the AVLV Transmitter?
Yes, the output range, units, and 0-5/10 VDC output can be configured via local DIP switches. -
What are the supported communication baud rates for the AVLV Transmitter?
The AVLV Transmitter supports baud rates of 9600, 19200, 38400, 57600, 76800, and 115200 (optional). -
Is there an optional display available for the AVLV Transmitter?
Yes, there is an optional 5 digit LCD display available for the AVLV Transmitter.
©Copyright 2023 Dwyer Instruments, LLC
DWYER INSTRUMENTS, LLC
- P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
- Phone: 219/879-8000
- Fax: 219/872-9057
- dwyer-inst.com
- e-mail: info@dwyermail.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>