Carrier 50VL-K30 Residential Packaged Air Conditioner Instruction Manual
- June 1, 2024
- Carrier
Table of Contents
- Carrier 50VL-K30 Residential Packaged Air Conditioner
- Installation Instructions
- Safety Considerations
- Introduction
- Receiving and Installation
- CAUTION – NOTICE TO RIGGERS PRUDENCE – AVIS AUX MANIPULATEUR
- Pre-Start-up
- Step 2 – Start-Up Cooling Section And Make Adjustments
- Continuous Fan Operation
- CONNECTION WIRING DIAGRAM DANGER: ELECTRICAL SHOCK HAZARD DISCONNECT
- Maintenance
- troubleshooting
- PRESTART-UP (Insert check mark in box as each item is completed)
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Carrier 50VL-K30 Residential Packaged Air Conditioner
Specifications
- Type: Packaged Air Conditioner
- Installation: Outdoor
- Discharge Openings: Horizontal and Downflow
Installation Instructions:
Before proceeding with the installation of the packaged air conditioner, ensure compliance with regional efficiency standards and safety regulations. Always refer to the provided instruction manual and follow the steps outlined below:
Safety Considerations
- Follow all safety codes and wear appropriate safety gear.
- Use a fire extinguisher and adhere to local building codes.
Pressure Relief and Refrigerant Handling:
- Relieve pressure and recover all refrigerant before servicing or disposal.
- Do not vent refrigerant into the atmosphere as per federal regulations.
Installation Instructions
IMPORTANT: Effective January 1, 2015, all split system and packaged air
conditioners must be installed pursuant to applicable regional efficiency
standards issued by the Department of Energy.
NOTE: Read the entire instruction manual before starting the installation.
NOTE: Installer: Make sure the Owner’s Manual and Service Instructions are
left with the unit after installation.
Fig. 1 – Unit 50VL
Safety Considerations
Improper installation adjustment, alteration, service, maintenance, or use can
cause explosion, fire, electrical shock, or other conditions which may cause
death, personal injury, or property damage. Consult a qualified installer,
service agency, or your distributor or branch for information or assistance.
The qualified installer or agency must use factory-authorized kits or
accessories when modifying this product Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work
gloves. Use quenching cloth for brazing operations. Have a fire extinguisher
available. Read these instructions thoroughly and follow all warnings or
cautions included in literature and attached to the unit. Consult local
building codes, the current editions of the National Electrical Code (NEC)
NFPA 70.
In Canada refer to the current editions of the Canadian electrical Code CSA
C22.1.
Recognize safety information. This is the safety-alert symbol . When you see
this symbol on the unit and in instructions or manuals, be alert to the
potential for personal injury. Understand these signal words; DANGER, WARNING,
and CAUTION. These words are used with the safety-alert symbol. DANGER
identifies the most serious hazards which will result in severe personal
injury or death. WARNING signifies hazards which could result in personal
injury or death. CAUTION is used to identify unsafe practices which may result
in minor personal injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced installation, reliability,
or operation.
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing system, always turn off main power to system
and install lockout tag. There may be more than one disconnect switch. Turn
off accessory heater power switch if applicable.
WARNING
PERSONAL INJURY AND ENVIRONMENTAL HAZARD Failure to relieve system pressure
could result in personal injury and/or death.
- Relieve pressure and recover all refrigerant before servicing existing equipment, and before final unit disposal. Use all service ports and open all flow-control devices, including solenoid valves.
- Federal regulations require that you do not vent refrigerant into the atmosphere. Recover during system repair or final unit disposal.
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
When removing access panels (see Fig. 20) or performing maintenance functions
inside your unit, be aware of sharp sheet metal parts and screws. Although
special care is taken to reduce sharp edges to a minimum, be extremely careful
and wear appropriate clothing, safety glasses and gloves when handling parts
or reaching into the unit.
WARNING
PERSONAL INJURY AND PROPERTY DAMAGE HAZARD
For continued performance, reliability, and safety, the only approved
accessories and replacement parts are those specified by the equipment
manufacturer. The use of non-manufacturer approved parts and accessories could
invalidate the equipment limited warranty and result in fire risk, equipment
malfunction, and failure. Please review manufacturer’s instructions and
replacement part catalogs available from your equipment supplier.
Introduction
This packaged air conditioner is fully self-contained and designed for outdoor installation (See Fig. 1). See Fig. 2 and Fig. 3 for unit dimensions. All unit sizes have discharge openings for both horizontal and downflow configurations, and are factory shipped with all downflow duct openings covered. The unit may be installed either on a rooftop or on a ground-level cement slab. (See Fig. 4 for roof curb dimensions.)
UNIT SIZE
| ****
CATALOG NUMBER
| A IN.
(mm)
| B
(small/common base)
**IN. (mm)***
| B
**(large base) IN. (mm) ***
| C IN.
(mm)
| D IN.
(mm)
| E IN.
(mm)
| F IN.
(mm)
| ****
G
IN. (mm)
| ****
H
IN. (mm)
---|---|---|---|---|---|---|---|---|---|---
Small or
Large
| CPRFCURB011B00| 14
(356)
| 10 (254)| ****
14 (356)
| ****
16
(406)
| ****
47.8
(1214)
| 32.4
(822)
| ****
2.7 (69)
| 30.6 (778)| ****
46.1 (1170)
Large| CPRFCURB013B00| 14
(356)
| 14 (356)| 43.9
(1116)
| 42.2 (1072)
Part Number CPRCURB011B00 can be used on both small and large basepan units. The cross supports must be located based on whether the unit is a small basepan or a large basepan.
NOTES
- Roof curb must be set up for unit being installed.
- Seal strip must be applied, as required, to unit being installed.
- Roof curb is made of 16-gauge steel.
- Attach ductwork to curb (flanges of duct rest on curb).
- Insulated panels: 1-in. (25.4 mm) thick fiberglass 1 lb. density.
NOTICE
If the unit gasketing or insulation must be replaced, ensure the material used
is compliant with the two agency requirements listed.
- Insulation and adhesives shall meet NFPA 90.1 requirements for flame spread and smoke generation.
- Cabinet insulation shall meet ASHRAE Standard 62.2.
Receiving and Installation
-
Step 1 – Check Equipment
Identify Unit
The unit model number and serial number are printed on the unit informative plate. Check this information against shipping papers.
Inspect Shipment
Inspect for shipping damage before removing packaging materials. If unit appears to be damaged or is torn loose from its anchorage, have it examined by transportation inspectors before removal. Forward claim papers directly to transportation company. Manufacturer is not responsible for any damage incurred in transit. Check all items against shipping list. Immediately notify the nearest equipment distribution office if any item is missing. To prevent loss or damage, leave all parts in original packages until installation.
If the unit is to be mounted on a curb in a downflow application, review Step 7 to determine which method is to be used to remove the downflow panels before rigging and lifting into place. The panel removal process may require the unit to be on the ground. -
Step 2 – Provide Unit Support
IMPORTANT: The unit must be secured to the curb by installing screws through the bottom of the curb flange and into the unit base rails. When installing large base units onto the common curb, the screws must be installed before allowing the full weight of the unit to rest on the curb. A minimum of six screws are required for large base units. Failure to secure unit properly could result in an unstable unit. See Warning near Rigging/Lifting information and accessory curb instructions for more details.
For hurricane tie downs, contact distributor for details and PE (Professional Engineering) Certificate if required.
Roof Curb
- Install accessory roof curb in accordance with instructions shipped with curb (See Fig. 4). Install insulation, cant strips, roofing, and flashing. Ductwork must be attached to curb.
- IMPORTANT: The gasketing of the unit to the roof curb is critical for a water tight seal. Install gasketing material supplied with the roof curb.
- Improperly applied gasketing also can result in air leaks and poor unit performance.
- Curb should be level to within 1/4 in. (6.35 mm) (See Fig. 4). This is necessary for unit drain to function properly. Refer to accessory roof curb installation instructions for additional information as required.
- Installation on older “G” series roof curbs.
- Two accessory kits are available to aid in installing a new “G” series unit on an old “G” roof curb.
- Accessory kit number CPADCURB001A00, (small chassis) and accessory kit number CPADCURB002A00, (large chassis) includes roof curb adapter and gaskets for the perimeter seal and duct openings. No additional modifications to the curb are required when using this kit.
- An alternative to the adapter curb is to modify the existing curb by removing the outer horizontal flange and use accessory kit number CPGSKTKIT001A00 which includes spacer blocks (for easy alignment to existing curb) and gaskets for the perimeter seal and duct openings. This kit is used when existing curb is modified by removing outer horizontal flange.
CAUTION
UNIT/STRUCTURAL DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Ensure there is sufficient clearance for saw blade when cutting the outer
horizontal flange of the roof curb so there is no damage to the roof or
flashing.
Slab Mount
Place the unit on a solid, level pad that is at least 2 in. (51 mm) above grade. The pad should extend approximately 2 in. (51 mm) beyond the casing on all 4 sides of the unit (See Fig. 7). Do not secure the unit to the pad except when required by local codes.
CAUTION – NOTICE TO RIGGERS PRUDENCE – AVIS AUX MANIPULATEUR
Use top skid as spreader bar. / Utiliser la palette du haut comme barre de répartition
SMALL CABINET | LARGE CABINET | |
---|---|---|
Unit | 24 | 30 |
lb | kg | lb |
lb | kg | lb |
Rigging Weight | 307 | 139 |
198 | 451 | 205 |
N OTE: See dimensional drawing for corner weighs.
Step 3 – Provide Clearances
Fig. 5 – Unit Suggested Rigging
The required minimum service clearances are shown in Fig. 2 and Fig. 3.
Adequate ventilation and outdoor air must be provided. The outdoor fan draws
air through the outdoor coil and discharges it through the top fan grille. Be
sure that the fan discharge does not recirculate to the outdoor coil. Do not
locate the unit in either a corner or under an overhead obstruction. The
minimum clearance under a partial overhang (such as a normal house overhang)
is 48 in. (1219 mm) above the unit top. The maximum horizontal extension of a
partial overhang must not exceed 48 in. (1219 mm)
IMPORTANT: Do not restrict outdoor airflow. An air restriction at either the
outdoor-air inlet or the fan discharge may be detrimental to compressor life.
Do not place the unit where water, ice, or snow from an overhang or roof will
damage or flood the unit. Do not install the unit on carpeting or other
combustible materials. Slab-mounted units should be at least 2 in.(51 mm)
above the highest expected water and runoff levels. Do not use unit if it has
been under water.
Step 4 – Field-Fabricate Ductwork
Secure all ducts to roof curb and building structure on vertical discharge
units. Do not connect ductwork to unit. For horizontal applications, unit is
provided with flanges on the horizontal openings. All ductwork should be
secured to the flanges. Insulate and weatherproof all external ductwork,
joints, and roof openings with counter flashing and mastic in accordance with
applicable codes.
Ducts passing through an unconditioned space must be insulated and covered
with a vapor barrier. If a plenum return is used on a vertical unit, the
return should be ducted through the roof deck to comply with applicable fire
codes. See unit rating plate for any required clearances around ductwork.
Cabinet return-air static shall not exceed -.25 IN. W.C.
Step 5 – Rig and Place Unit
WARNING
PERSONAL INJURY OR PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal injury, death or
property damage.
When installing the unit on a rooftop, be sure the roof will support the
additional weight.
- Rigging and handling of this equipment can be hazardous for many reasons due to the installation location (roofs, elevated structures, etc.).
- Only trained, qualified crane operators and ground support staff should handle and install this equipment.
- When working with this equipment, observe precautions in the literature, on tags, stickers, and labels attached to the equipment, and any other safety precautions that might apply.
- Training for operators of the lifting equipment should include, but not be limited to, the following:
-
Application of the lifter to the load, and adjustment of the lifts to adapt to various sizes or kinds of loads.
Instruction in any special operation or precaution. -
Condition of the load as it relates to operation of the lifting kit, such as balance, temperature, etc.
Follow all applicable safety codes. Wear safety shoes and work gloves.
Inspection
Prior to initial use, and at monthly intervals, all rigging shackles, clevis
pins, and straps should be visually inspected for any damage, evidence of
wear, structural deformation, or cracks. Particular attention should be paid
to excessive wear at hoist hooking points and load support areas. Materials
showing any kind of wear in these areas must not be used and should be
discarded.
WARNING
UNIT FALLING HAZARD
Failure to follow this warning could result in personal injury or death. Never
stand beneath rigged units or lift over people.
WARNING
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal injury.
When straps are taut, the clevis should be a minimum of 36 in. (914 mm) above
the unit top cover.
Rigging/Lifting of Unit (See Fig. 5)
WARNING
UNIT FALLING HAZARD
Failure to follow this warning could result in personal injury or death. Large
base units must be secured to common curb before allowing full weight of unit
to rest on curb. Install screws through curb into unit base rails while
rigging crane is still supporting unit.
Lifting holes are provided in base rails as shown.
- Attach shackles, clevis pins, and straps to the base rails of the unit. Be sure materials are rated to hold the weight of the unit (See Fig. 5).
- Attach a clevis of sufficient strength in the middle of the straps. Adjust the clevis location to ensure unit is lifted level with the ground.
After the unit is placed on the roof curb or mounting pad, remove the top skid.
Step 6 – Connect Condensate Drain
- NOTE: When installing condensate drain connection be sure to comply with local codes and restrictions.
- Unit disposes of condensate water through a 3/4 in. NPT fitting which exits through the base on the evaporator coil access side. See Fig. 2 and Fig. 3 for location.
- Condensate water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground level installations. Install a field-supplied 2-in. (51 mm) condensate trap at end of condensate connection to ensure proper drainage. Make sure that the outlet of the trap is at least 1 in. (25 mm) lower than the drain pan condensate connection to prevent the pan from overflowing (See Fig. 8). When using a gravel apron, make sure it slopes away from the unit.
- Connect a drain tube using a minimum of 3/4 -in. PVC or 3/4 -in. copper pipe (all field-supplied) at the outlet end of the 2-in. (51 mm) trap. Do not undersize the tube. Pitch the drain tube downward at a slope of at least 1-in. (25 mm) for every 10 ft (3.1 m) of horizontal run. Be sure to check the drain tube for leaks. Prime trap at the beginning of the cooling season start-up.
Step 7 – Install Duct Connections
The design and installation of the duct system must be in accordance with the
standards of the NFPA for installation of non-residence type air conditioning
and ventilating systems, NFPA 90A or residence type, NFPA 90B and/or local
codes and ordinances.
Select and size ductwork, supply-air registers, and return air grilles
according to ASHRAE (American Society of Heating, Refrigeration, and Air
Conditioning Engineers) recommendations. The unit has duct flanges on the
supply- and return-air openings on the side of the unit.
When designing and installing ductwork, consider the following:
-
All units should have field-supplied filters or accessory filter rack installed in the return-air side of the unit. Recommended sizes for filters are shown in Table 1.
-
Avoid abrupt duct size increases and reductions. Abrupt change in duct size adversely affects air performance.
50VL-K: Installation Instructions
IMPORTANT: Use flexible connectors between ductwork and unit to prevent transmission of vibration. Use suitable gaskets to ensure a weather-tight and airtight seal. When electric heat is installed, use fireproof canvas (or similar heat resistant material) connector between ductwork and unit discharge connection. If flexible duct is used, insert a sheet metal sleeve inside duct. Heat resistant duct connector (or sheet metal sleeve) must extend 24-in. (610 mm) from electric heater element. -
Size ductwork for cooling air quantity (cfm). The minimum air quantity for proper electric heater operation is listed in Table 2. Heater limit switches may trip at air quantities below those recommended.
-
Seal, insulate, and weatherproof all external ductwork. Seal, insulate and cover with a vapor barrier all ductwork passing through conditioned spaces. Follow latest Sheet Metal and Air Conditioning Contractors National Association (SMACNA) and Air Conditioning Contractors Association (ACCA) minimum installation standards for residential heating and air conditioning systems.
-
Secure all ducts to building structure. Flash, weatherproof, and vibration-isolate duct openings in wall or roof according to good construction practices.
Configuring Units for Downflow (Vertical) Discharge
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before performing service or maintenance operations on the system, turn off
main power to unit and install lockout tag. There may be more than one
disconnect switch.
- Open all electrical disconnects and install lockout tag before starting any service work.
- Remove horizontal (metal) ductcovers to access vertical (downflow) discharge duct knockouts in unit basepan. (See Fig. 9.)
To remove downflow return and supply knockout covers, break front and right
side connecting tabs with a screwdriver and hammer. Push cover down to break
rear and left side tabs.
NOTE: These panels are held in place with tabs similar to an electrical
knockout. Reinstall horizontal duct covers (Fig. 9) shipped on unit from
factory. Insure openings are air and watertight.
NOTE: The design and installation of the duct system must be in accordance
with the standards of the NFPA for installation of nonresidence-type air
conditioning and ventilating systems, NFPA 90A or residence-type, NFPA 90B;
and/or local codes and ordinances.
- Units are shipped for side shot installation.
- Select and size ductwork, supply-air registers, and return-air grilles according to American Society of Heating, Refrigeration and Air Conditioning Engineers (ASHRAE) recommendations.
- Use flexible transition between rigid ductwork and unit to prevent transmission of vibration. The transition may be screwed or bolted to duct flanges. Use suitable gaskets to ensure a weather-tight and airtight seal.
- All units must have field-supplied filters or accessory filter rack installed in the return-air side of the unit. Recommended sizes for filters are shown in Table 1.
- Size all ductwork for maximum required airflow (either heating or cooling) for unit being installed. Avoid abrupt duct size increases or decreases or performance may be affected.
- Adequately insulate and weatherproof all ductwork located outdoors. Insulate ducts passing through unconditioned space, and use vapor barrier in accordance with latest issue of Sheet Metal and Air Conditioning Contractors National Association (SMACNA) and Air Conditioning Contractors of America (ACCA) minimum installation standards for heating and air conditioning systems. Secure all ducts to building structure.
- Flash, weatherproof, and vibration-isolate all openings in building structure in accordance with local codes and good building practices.
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death. The
unit cabinet must have an uninterrupted, unbroken electrical ground to
minimize the possibility of personal injury if an electrical fault should
occur. This ground may consist of an electrical wire connected to the unit
ground screw in the control compartment, or conduit approved for electrical
ground when installed in accordance with NFPA 70 (NEC) (latest edition) (in
Canada, Canadian Electrical Code CSA C22.1) and local electrical codes.
CAUTION
UNIT COMPONENT DAMAGE HAZARD
- Failure to follow this caution may result in damage to the unit being installed.
- Make all electrical connections in accordance with NFPA 70 (NEC) (latest edition) and local electrical codes governing such wiring. In Canada, all electrical connections must be in accordance with CSA standard C22.1 Canadian Electrical Code Part 1 and applicable local codes. Refer to unit wiring diagram. Use only copper conductor for connections between field-supplied electrical disconnect switch and unit. DO NOT USE ALUMINUM WIRE.
- Be sure that high-voltage power to unit is within operating voltage range indicated on unit rating plate. On 3-phase units, ensure phases are balanced within 2 percent. Consult local power company for correction of improper voltage and/or phase imbalance.
- Do not damage internal components when drilling through any panel to mount electrical hardware, conduit, etc.
- Route field power supply(s) away from areas that could be damaged by lawn and garden equipment or other accidental damage.
High-Voltage Connections
The unit must have a separate electrical service with a field-supplied,
waterproof disconnect switch mounted at, or within sight from the unit. Refer
to the unit rating plate, NEC and local codes for maximum fuse/circuit breaker
size and minimum circuit amps (ampacity) for wire sizing.
The field-supplied disconnect may be mounted on the unit over the high-voltage
inlet hole when the standard power and low-voltage entry points are used. See
Fig. 2 and Fig. 3 for acceptable location.
See unit wiring label (Fig. 12 – Fig. 17) and Fig. 10 for reference when
making high voltage connections. Proceed as follows to complete the high-
voltage connections to the unit.
Single phase units:
- Run the high-voltage (L1, L2) and ground lead into the control box.
- Connect ground lead to chassis ground connection.
- Locate the black and yellow wires connected to the line side of the contactor.
- Connect field L1 to black wire on connection 11 of the compressor contactor. Fig. 10 – High- and Control-Voltage Connections
- Connect field wire L2 to yellow wire on connection 23 of the compressor contactor.
Three-phase units
- Run the high-voltage (L1, L2, L3) and ground lead into the control box.
- Connect ground lead to chassis ground connection.
- Locate the black and yellow wires connected to the line side of the contactor.
- Connect field L1 to black wire on connection 11 of the compressor contactor.
- Connect field wire L3 to yellow wire on connection 13 of the compressor contactor.
- Connect field wire L2 to blue wire from compressor.
Special Procedures for 208-V Operation
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing system, always turn off main power to system
and install lockout tag. With disconnect switch open, move black wire from
transformer (3/16 in.)(4.8 mm) terminal marked 230 to terminal marked 208.
This retaps transformer to primary voltage of 208 vac.
Control Voltage Connections
NOTE: Do not use any type of power-stealing thermostat. Unit control problems
may result.
Use no. 18 American Wire Gage (AWG) color-coded, insulated (35°C minimum)
wires to make the control voltage connections between the thermostat and the
unit. If the thermostat is located more than 100 ft (30.5 m) from the unit (as
measured along the control voltage wires), use no. 16 AWG color-coded,
insulated (35° C minimum) wires.
Standard Connection
Locate the seven (eight for 3-phase) low voltage thermostat leads in 24 volt
splice box. A gray wire is standard on 3-phase units for connection to an
economizer. See Fig. 10 for connection diagram. Run the low-voltage leads from
the thermostat, through the control wiring inlet hole grommet (Fig. 2 and Fig.
3), and into the low-voltage splice box.
Provide a drip loop before running wires through panel. Secure and strain
relief all wires so that they do not interfere with operation of unit.
If an accessory electric heater is installed, low voltage leads from heater
must be connected to factory supplied control leads from Indoor Fan Board P4
connector.
NOTE: If the unit 24V wires do not have a matching receptacle, cut the 24V
wires from the electric heater plug, strip the ends, and wire nut together to
match the schematic connections. If the electric heater 24V wires do not have
a matching plug, cut the 24V wires from the unit receptacle, strip the ends,
and wire nut together to match the schematic connections.
Factory wires are provided for electric heat staging W1 and W2 (W2 and W3 on
IFB). If room thermostat has only one stage of supplemental heat, connect
white and violet wires shown in Fig. 10 to second stage heat field wire.
Some electric heaters have four control wires (plus common wire). Consult unit
wiring diagram and electric heater wiring diagram for additional details.
Ttransformer Protection
The transformer is of the energy-limiting type, however a direct short will
likely blow a secondary fuse. If an overload or short is present, correct
overload condition and check for blower fuse on Indoor Fan Board. Replace fuse
as required with correct size and rating.
Table 1 – Physical Data-Unit
UNIT SIZE | 24 | 30 | 36 | 42 | 48 | 60 |
---|---|---|---|---|---|---|
NOMINAL CAPACITY (ton) | 2 | 2-1/2 | 3 | 3-1/2 | 4 | 5 |
SHIPPING WEIGHT lb. SHIPPING WEIGHT (kg) | 307 |
139
| 316
143
| 354
161
| 388
176
| 437
198
| 451
205
COMPRESSORS
Quantity
| Scroll
1
REFRIGERANT (R-410A)
Quantity lb Quantity (kg)
| ****
6.4
2.9
| ****
6.0
2.7
| ****
5.75
2.6
| ****
6.0
2.7
| ****
9.0
4.1
| ****
10.75
4.9
REFRIGERANT METERING DEVICE| Orifice| TXV
ORIFICE ID in./mm| .059 / 1.5| .063 / 1.60| .070 / 1.78| .073 / 1.85| .080 /
2.03| N/A
OUTDOOR COIL
Rows…Fins/in. Face Area (sq ft)
| ****
1…21
11.9
| ****
1…21
13.6
| ****
1…21
13.6
| ****
1…21
13.6
| ****
1…21
23.3
| ****
2…21
17.5
OUTDOOR FAN
Nominal Cfm Diameter in. Diameter (mm) Motor Hp (Rpm)
| ****
2500
24
609.6
1/12 (810)
| ****
3200
24
609.6
1/5 (810)
| ****
3500
26
660.4
1/5 (810)
| ****
3500
26
660.4
1/5 (810)
| ****
3500
26
660.4
1/5 (810)
| ****
3500
26
660.4
1/5 (810)
INDOOR COIL
Rows…Fins/in. Face Area (sq ft)
| ****
3…17
3.7
| ****
3…17
3.7
| ****
2…17
5.6
| ****
3…17
4.7
| ****
3…17
5.6
| ****
3…17
5.6
INDOOR BLOWER
Nominal Cooling Airflow (Cfm) Size in.
Size (mm.)
Motor HP (RPM)
| ****
750
10×10
254×254
1/2 (1050)
| ****
950
10×10
254×254
1/2 (1050)
| ****
1150
11×10
279.4×254
1/2(1000)
| ****
1350
11×10
279.4×254
3/4 (1075)
| ****
1600
11×10
279.4×254
1.0 (1075)
| ****
1750
11×10
279.4×254
1.0 (1040)
HIGH-PRESSURE SWITCH
(psig) Cut-out Reset (Auto)
| 650 +/- 15
420 +/- 25
LOSS-OF-CHARGE / LOW-PRESSURE
SWITCH (psig) cut-out Reset (auto)
| N/A
RETURN-AIR FILTERS* †
Throwaway Size in. Throwaway Size (mm)
| ****
2 each 20x12x1 (508x305x25)
| 1 each 24x18x1 (610x457x25) 24x16x1
(610x406x25)
| 1 each 24×14 x1 (610x356x25) 24x16x1
(610x406x25)
| 1 each 24x18x1 (610x457x25) 24x16x1
(610x406x25)
- Required filter sizes shown are based on the larger of the AHRI (Air Conditioning Heating and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 to 350 ft/minute for throwaway type or 450 ft/minute for high-capacity type. Air filter pressure drop for non-standard filters must not exceed 0.08 in. W.C.
- If using accessory filter rack refer to the filter rack installation instructions for correct filter sizes and quantity.
Table 2 – Minimum Airflow for Safe Electric Heater Operation (CFM)
SIZE | 24 | 30 | 36 | 42 | 48 | 60 |
---|---|---|---|---|---|---|
Cfm | 800 | 1000 | 1200 | 1400 | 1600 | 1750 |
Pre-Start-up
WARNING
ENVIRONMENTAL, FIRE, EXPLOSION, ELECTRICAL
SHOCK HAZARD
Failure to follow this warning could result in personal injury or death and/or
property damage.
- Follow recognized safety practices and wear protective goggles when checking or servicing refrigerant system.
- Relieve and recover all refrigerant from system before touching or disturbing compressor plug if refrigerant leak is suspected around compressor terminals.
- Never attempt to repair soldered connection while refrigerant system is under pressure.
- Do not use torch to remove any component. System contains oil and refrigerant under pressure.
- To remove a component, wear protective goggles and proceed as follows:
- Shut off electrical power to unit and install lockout tag.
- Relieve and reclaim all refrigerant from system using both highand low-pressure ports.
- ut component connecting tubing with tubing cutter and remove component from unit.
- Carefully unsweat remaining tubing stubs when necessary. Oil can ignite when exposed to torch flame. Proceed as follows to inspect and prepare the unit for initial start-up:
-
Remove all access panels (see Fig. 20).
-
Read and follow instructions on all DANGER, WARNING,
CAUTION, and INFORMATION labels attached to, or shipped with unit. -
Make the following inspections:
- Inspect for shipping and handling damages, such as broken lines, loose parts, disconnected wires, etc.
- Inspect all field- and factory-wiring connections. Be sure that connections are completed and tight.
- Ensure wires do not touch refrigerant tubing or sharp sheet metal edges.
- Inspect coil fins. If damaged during shipping and handling, carefully straighten fins with a fin comb.
-
Verify the following conditions:
-
Make sure that condensate drain pan and trap are filled with water to ensure proper drainage.
-
Make sure that all tools and miscellaneous loose parts have been removed.
Start-up
Step 1 – Check for Refrigerant Leaks
WARNING
EXPLOSION HAZARD
Failure to follow this warning could result in death, serious personal injury,
and/or property damage.
Never use air or gases containing oxygen for leak testing or operating
refrigerant compressors. Pressurized mixtures of air or gases containing
oxygen can lead to an explosion.
Proceed as follows to locate and repair a refrigerant leak and to charge the unit:
-
Locate leak and make sure that refrigerant system pressure has been relieved and reclaimed from both high- and low-pressure ports.
-
Repair leak following accepted practices.
NOTE: Install a filter drier whenever the system has been opened for repair. -
Add a small charge of Puron (R-410A) refrigerant vapor to system and leak-test unit.
-
Recover refrigerant from system and evacuate to 500 microns if no additional leaks are found.
-
Charge unit with Puron (R-410A) refrigerant, using an accurate scale. Refer to unit rating plate for required charge.
Step 2 – Start-Up Cooling Section And Make Adjustments
Complete the required procedures given in the Pre-Start-Up section before starting the unit. Do not jumper any safety devices when operating the unit. Do not operate the unit when the outdoor temperature is below 40°F (4°C) (unless accessory low-ambient kit is installed). Do not rapid cycle the compressor. Allow 5 minutes between “on” cycles to prevent compressor damage.
Checking Cooling Control Operation
Start and check the unit for proper cooling control operation as follows:
- Place room thermostat SYSTEM switch in OFF position. Observe that blower motor starts when FAN switch is placed in ON position and shuts down when FAN switch is placed in AUTO position.
- Place SYSTEM switch in COOL position and FAN switch in AUTO position. Set cooling control below room temperature. Observe that compressor, condenser fan, and evaporator blower motors start. Observe that compressor and outdoor fan shut down when control setting is satisfied and that indoor blower shuts down after 90 second fan time delay expires.
IMPORTANT: Three-phase, scroll compressors are direction oriented.
Unit must be checked to ensure proper compressor 3-phase power lead
orientation. If not corrected within 5 minutes, the internal protector will
shut off the compressor. The 3-phase power leads to the unit must be reversed
to correct rotation. When turning backwards, the difference between compressor
suction and discharge pressures may be minimal.
Checking and Adjusting Refrigerant Charge
The refrigerant system is fully charged with Puron (R-410A) refrigerant and is
tested and factory sealed.
WARNING
EXPLOSION HAZARD
Failure to follow this warning could result in death, serious personal injury,
and/or property damage.
Never use air or gases containing oxygen for leak testing or operating
refrigerant compressors. Pressurized mixtures of air or gases containing
oxygen can lead to an explosion.
-
NOTE: Adjustment of the refrigerant charge is not required unless the unit is suspected of not having the proper Puron (R-410A) charge.
-
NOTE: Some units have fixed orifice refrigerant metering devices. There is a different charging procedure for both expansion devices. Refer to the correct procedure for your unit.
-
The charging label and the tables shown refer to system temperatures and pressures in cooling mode only. A refrigerant charging label attached to the inside of the compressor access panel. (See Fig. 18 Subcool chart for units with TXV and superheat chart for units with fixed orifice.) The chart includes the required liquid line temperature at given discharge line pressures and outdoor ambient temperatures.
-
A superheat chart is attached to the inside of the compressor access panel for the unit with fixed metering device. Refer to the charging procedure on the label.
An accurate thermocouple- or thermistor-type thermometer, and a gauge manifold are required when using the subcooling charging method for evaluating the unit charge. Do not use mercury or small dial-type thermometers because they are not adequate for this type of measurement. -
NOTE: Allow system to operate for a minimum of 15 minutes before checking or adjusting refrigerant charge.
-
IMPORTANT: When evaluating the refrigerant charge, an indicated adjustment to the specified factory charge must always be very minimal. If a substantial adjustment is indicated, an abnormal condition exists somewhere in the cooling system, such as insufficient airflow across either coil or both coils.
Proceed as follows
- Remove caps from low- and high-pressure service fittings.
- Using hoses with valve core depressors, attach low- and high-pressure gauge hoses to low- and high-pressure service fittings, respectively.
- Start unit and let run until system pressures stabilize.
- Measure and record the following:
- Outdoor ambient-air temperature (°F [°C] db).
- iquid line temperature (°F [°C]) at TXV.
- Discharge (high-side) pressure (psig).
- Suction (low-side) pressure (psig) (for reference only).
- Using Cooling Charging Charts compare outdoor-air temperature (°F [°C] db) with the discharge line pressure (psig) to determine desired system operating liquid line temperature (See Fig. 18).
- Compare actual liquid line temperature with desired liquid line temperature. Using a tolerance of ±2°F (±1.1°C), add refrigerant if actual temperature is more than 2°F (1.1°C) higher than proper liquid line temperature, or remove refrigerant if actual temperature is more than 2°F (1.1°C) lower than required liquid line temperature.
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in unit damage.
For cooling operation, the recommended airflow is 350 to 450 cfm for each
12,000 Btuh of rated cooling capacity. For heating operation, the airflow must
produce a temperature rise that falls within the range stamped on the unit
rating plate.
NOTE: Be sure that all supply-and return-air grilles are open, free from obstructions, and adjusted properly.
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect electrical power to the unit and install lockout tag before
changing blower speed.
This unit is factory-set up for use with a single cooling fan speed. In addition, this unit has the field-selectable capability to run two different cooling fan speeds: The rated cooling fan speed (350~400 CFM/Ton) and an enhanced dehumidification fan speed (As low as 320 CFM/Ton) for use with either a dehumidistat or a thermostat that supports dehumidification.
The cooling speed is marked “LOW” on the interface fan board (IFB)(See Fig.
11). The factory-shipped settings are noted in Table 4. There are 4 additional
speed tap wires available for use in either electric heating or cooling (For
color coding on the indoor fan motor leads, see Table 3). The additional 4
speed tap wires are shipped loose with vinyl caps and are located in the
control box, near the interface fan board (IFB) (See Fig. 11).
Single Cooling Fan Speed Set-up (Dehumidification feature not used)
To change cooling speed:
- Remove the vinyl cap off of the desired speed tap wire (Refer to Table 3 for color coding). Add the wet coil pressure drop in Table 5 to the system static to determine the correct cooling airflow speed in Table that will deliver the nominal cooling airflow as listed in Table for each size.
- Remove the current speed tap wire from the “LOW” terminal on the interface fan board (IFB) (See Fig. 11) and place vinyl cap over the connector on the wire.
- Connect the desired speed tap wire to the “LOW” terminal on the interface fan board (IFB).
NOTE: If accessory electric heat is installed, and the electric heat fan speed
is chosen to be the same as the normal cooling fan speed, the dry airflow must
meet or exceed the minimum airflow speed specified in Table 2 for the specific
size unit.
Two Cooling Fan Speeds Set-up (Dehumidification feature used)
IMPORTANT: Dehumidification control must open control circuit on humidity rise
above set point.
Use of the dehumidification cooling fan speed requires use of either a 24 VAC dehumidistat or a thermostat which includes control of a 24 VAC dehumidistat connection. In either case, the dehumidification control must open the control circuit on humidity rise above the dehumidification set point.
-
Using Fig. 11, move the two pin DEHUM jumper from the “STD” position to the “DEHUM” position.
-
Remove fan speed tap wire from the “LOW” terminal on the interface fan board (IFB) (See Fig. 11).
-
Determine correct normal cooling fan speed for unit and application. Add the wet coil pressure drop in Table 5 to the system static to determine the correct cooling airflow speed in Table 4 that will deliver the nominal cooling airflow as listed in Table 1 for each size.
NOTE: If accessory electric heat is installed, the dry airflow must meet or exceed the minimum airflow speed specified in Table 2 for the specific size unit. The electric heat fan speed will be the same as the normal cooling fan speed. -
Remove the vinyl cap off of the desired speed tap wire (Refer to Table 3 for color coding) for the normal cooling fan speed and place desired speed tap wire on “HIGH” on the interface board.
-
Refer to airflow table (Table 4) to determine allowable speeds for the dehumidification cooling fan speed. In Table 4, speeds that are not allowed for dehumidification cooling are shaded.
-
Remove the vinyl cap off of the desired speed tap wire (Refer to Table 3 for color coding) for the dehumidification cooling fan speed and place desired speed tap wire on the “LOW” connection on the interface board (IFB). Verify that static pressure is in the acceptable range for the speed tap to be used for dehumidification cooling.
-
Use any spare vinyl plugs to cap any unused speed tap wires.
Fig. 11 – Interface Fan Board (IFB)
Single Speed Cooling with Higher Electric Heat Speed
This unit can also be configured to operate with single speed cooling and a higher speed for an accessory electric heater.
- Using Fig. 11, move the two pin DEHUM jumper from the “STD” position to the “DEHUM” position.
- See Table 2 for minimum airflow for electric heat operation. Add electric heater and filter pressure drop to duct system static pressure to determine total external static pressure.
- Select speed tap from Table 4 that will achieve required airflow from Table 2.
- Remove the vinyl cap off of the desired speed tap wire (Refer to Table 3 for color coding).
- Connect the desired speed tap wire to the “HIGH” terminal on the interface fan board (IFB).
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in unit component damage or improper
operation.
To use this mode, a speed connection must be made on the “HIGH” terminal that
meets or exceeds the minimum airflow found in Table 2.
Table 3 – Color Coding for Indoor Fan Motor Leads
Black = High Speed
Orange = Med-High Speed
Red = Med Speed
Pink = Med-Low Speed
Blue = Low Speed
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect electrical power to the unit and install lockout tag before
changing blower speed.
Continuous Fan Operation
When the DEHUM feature is not used, the continuous fan speed will be the same as cooling fan speed. When the DEHUM feature is used, the continuous fan will operate on IFB “LOW” speed when the DH control lead is not energized, or IFB “HIGH” speed when the DH lead is energized (see Fig. 11).
Cooling Sequence of Operation
- With the room thermostat SYSTEM switch in the COOL position and the FAN switch in the AUTO position, the cooling sequence of operation is as follows:
- When the room temperature rises to a point that is slightly above the cooling control setting of the thermostat, the thermostat completes the circuit between thermostat terminal R to terminals Y and G. These completed circuits through the thermostat connect contactor coil (C)(through unit wire Y) and time delay relay (TDR) (through unit wire G) across the 24-V secondary of transformer (TRAN).
- The normally open contacts of energized contactor (C) close and complete the circuit through compressor motor (COMP) to condenser (outdoor) fan motor (OFM). Both motors start instantly.
- A set of normally open contacts on the interface fan board (IFB) are closed which energizes a circuit to the indoor fan motor (IFB).
- NOTE: Once the compressor has started and then has stopped, it should not be started again until 5 minutes have elapsed.
- The cooling cycle remains on until the room temperature drops to a point that is slightly below the cooling control setting of the room thermostat. At this point, the thermostat breaks the circuit between thermostat terminal R to terminals Y and G. These open circuits deenergize contactor coil C and IFB. The condenser and compressor motors stop. After a 90-second delay, the blower motor stops. The unit is in a standby condition, waiting for the next call for cooling from the room thermostat.
*Table 4 – Dry Coil Air Delivery – Horizontal and Downflow Discharge Sizes 24-60**
Unit Size
| ****
Motor Speed
| ****
Tap
| ESP (in. W.C.)
---|---|---|---
| 0.1| 0.2| 0.3| 0.4| 0.5| 0.6| 0.7|
0.8| 0.9| 1
24
| ****
Low
| ****
Blue
| CFM| 640| 553| 454| 310| —| —| —| —| —| —
BHP| 0.07| 0.08| 0.08| 0.09| —| —| —| —| —| —
Med-Low
| ****
Pink
| CFM| 830| 758| 688| 607| 514| 393| 254| —| —| —
BHP| 0.12| 0.13| 0.13| 0.13| 0.14| 0.14| 0.15| —| —| —
Medium**
| ****
Red
| CFM| 1080| 1025| 969| 910| 852| 787| 718| 638| 541| 457
BHP| 0.21| 0.22| 0.23| 0.23| 0.24| 0.24| 0.25| 0.25| 0.26| 0.27
Med-High
| ****
Orange
| CFM| 1101| 1046| 993| 936| 878| 816| 749| 676| 599| 498
BHP| 0.22| 0.23| 0.24| 0.24| 0.25| 0.26| 0.26| 0.27| 0.27| 0.28
High
| ****
Black
| CFM| 1222| 1173| 1123| 1072| 1021| 967| 912| 853| 787| 712
BHP| 0.29| 0.29| 0.30| 0.31| 0.31| 0.32| 0.33| 0.34| 0.34| 0.34
30
| ****
Low
| ****
Blue
| CFM| 643| 552| 455| 348| 225| —| —| —| —| —
BHP| 0.09| 0.10| 0.11| 0.11| 0.11| —| —| —| —| —
Med-Low
| ****
Pink
| CFM| 817| 744| 673| 597| 516| 431| 325| 190| —| —
BHP| 0.14| 0.15| 0.15| 0.16| 0.17| 0.17| 0.18| 0.18| —| —
Medium
| ****
Red
| CFM| 1159| 1104| 1045| 990| 937| 878| 821| 759| 693| 618
BHP| 0.31| 0.32| 0.33| 0.33| 0.34| 0.35| 0.36| 0.37| 0.37| 0.38
Med-High**
| ****
Orange
| CFM| 1201| 1147| 1095| 1037| 987| 934| 877| 818| 755| 671
BHP| 0.34| 0.35| 0.36| 0.37| 0.37| 0.38| 0.39| 0.40| 0.41| 0.40
High
| ****
Black
| CFM| 1291| 1236| 1181| 1131| 1080| 1033| 978| 909| 792| 661
BHP| 0.41| 0.42| 0.43| 0.43| 0.44| 0.45| 0.46| 0.45| 0.43| 0.40
36
| ****
Low
| ****
Blue
| CFM| 1096| 1044| 994| 945| 892| 837| 780| 717| 664| 612
BHP| 0.14| 0.15| 0.16| 0.18| 0.19| 0.19| 0.20| 0.21| 0.22| 0.23
Med-Low
| ****
Pink
| CFM| 1151| 1103| 1056| 1002| 953| 897| 845| 788| 729| 678
BHP| 0.16| 0.17| 0.18| 0.19| 0.20| 0.21| 0.22| 0.23| 0.24| 0.25
Medium
| ****
Red
| CFM| 1299| 1252| 1204| 1155| 1106| 1059| 1007| 959| 905| 844
BHP| 0.22| 0.23| 0.24| 0.25| 0.26| 0.27| 0.28| 0.29| 0.30| 0.31
Med-High**
| ****
Orange
| CFM| 1382| 1335| 1292| 1246| 1202| 1152| 1106| 1058| 1007| 957
BHP| 0.26| 0.27| 0.28| 0.29| 0.30| 0.31| 0.32| 0.33| 0.34| 0.35
High
| ****
Black
| CFM| 1530| 1485| 1442| 1398| 1354| 1309| 1263| 1217| 1169| 1120
BHP| 0.33| 0.35| 0.36| 0.37| 0.38| 0.39| 0.40| 0.41| 0.42| 0.43
Unit Size
| ****
Motor Speed
| ****
Tap
| ESP (in. W.C.)
---|---|---|---
| 0.1| 0.2| 0.3| 0.4| 0.5| 0.6| 0.7|
0.8| 0.9| 1
42
| ****
Low
| ****
Blue
| CFM| 956| 899| 843| 786| 729| 676| 621| 558| 504| 435
BHP| 0.13| 0.13| 0.14| 0.15| 0.16| 0.16| 0.17| 0.18| 0.18| 0.19
Med-Low
| ****
Pink
| CFM| 1201| 1153| 1107| 1060| 1012| 965| 917| 871| 828| 782
BHP| 0.21| 0.22| 0.22| 0.23| 0.24| 0.25| 0.26| 0.27| 0.28| 0.29
Medium
| ****
Red
| CFM| 1443| 1402| 1361| 1322| 1284| 1243| 1204| 1164| 1124| 1084
BHP| 0.32| 0.33| 0.34| 0.35| 0.36| 0.37| 0.38| 0.39| 0.40| 0.42
Med-High**
| ****
Orange
| CFM| 1529| 1491| 1451| 1411| 1376| 1338| 1300| 1261| 1223| 1185
BHP| 0.37| 0.39| 0.40| 0.41| 0.42| 0.43| 0.44| 0.45| 0.46| 0.47
High
| ****
Black
| CFM| 1604| 1565| 1529| 1490| 1455| 1421| 1385| 1348| 1310| 1274
BHP| 0.42| 0.44| 0.45| 0.46| 0.47| 0.48| 0.49| 0.50| 0.51| 0.52
48
| ****
Low
| Blue| CFM| 641| 551| 462| 385| 289| 216| 163| 115| —| —
| BHP| 0.05| 0.06| 0.06| 0.07| 0.07| 0.08| 0.08| 0.09| —| —
Med-Low
| ****
Pink
| CFM| 1437| 1395| 1351| 1307| 1265| 1221| 1176| 1132| 1084| 1039
BHP| 0.29| 0.30| 0.31| 0.32| 0.33| 0.34| 0.35| 0.36| 0.37| 0.38
Medium**
| ****
Red
| CFM| 1771| 1735| 1699| 1664| 1627| 1592| 1557| 1522| 1486| 1450
BHP| 0.51| 0.52| 0.53| 0.55| 0.56| 0.57| 0.58| 0.59| 0.61| 0.62
Med-High
| ****
Orange
| CFM| 1928| 1897| 1862| 1830| 1796| 1764| 1732| 1698| 1620| 1512
BHP| 0.64| 0.65| 0.67| 0.68| 0.69| 0.71| 0.72| 0.73| 0.71| 0.66
High
| ****
Black
| CFM| 2212| 2167| 2124| 2061| 1976| 1892| 1794| 1699| 1567| 1438
BHP| 0.97| 0.99| 1.00| 0.97| 0.95| 0.91| 0.86| 0.82| 0.77| 0.71
60
| ****
Low
| ****
Blue
| CFM| 641| 551| 462| 385| 289| 216| 163| 115| —| —
BHP| 0.05| 0.06| 0.06| 0.07| 0.07| 0.08| 0.08| 0.09| —| —
Med-Low
| ****
Pink
| CFM| 1437| 1395| 1351| 1307| 1265| 1221| 1176| 1132| 1084| 1039
BHP| 0.29| 0.30| 0.31| 0.32| 0.33| 0.34| 0.35| 0.36| 0.37| 0.38
Medium**
| ****
Red
| CFM| 1914| 1881| 1848| 1814| 1780| 1748| 1716| 1681| 1619| 1512
BHP| 0.62| 0.64| 0.65| 0.67| 0.68| 0.69| 0.71| 0.72| 0.71| 0.66
Med-High
| ****
Orange
| CFM| 1928| 1897| 1862| 1830| 1796| 1764| 1732| 1698| 1620| 1512
BHP| 0.64| 0.65| 0.67| 0.68| 0.69| 0.71| 0.72| 0.73| 0.71| 0.66
High
| ****
Black
| CFM| 2212| 2167| 2124| 2061| 1976| 1892| 1794| 1699| 1567| 1438
BHP| 0.97| 0.99| 1.00| 0.97| 0.95| 0.91| 0.86| 0.82| 0.77| 0.71
| Shaded areas indicate speed/static combinations that are not permitted for
dehumidification speed.
Shaded areas indicate speed/static combinations that are not permitted for dehumidification speed.
- Air delivery values are without air filter and are for dry coil (See Wet Coil Pressure Drop Table).
- Factory-shipped cooling speed
- “High Static Cooling” = Only to be used for cooling function (not allowed for heating function)
NOTE: Deduct field-supplied air filter pressure drop and wet coil pressure drop to obtain static pressure available for ducting.
Table 5 – Wet Coil Pressure Drop (IN. W.C.)
Unit
Size
| Standard CFM (SCFM)
---|---
600| 700| 800| 900| 1000| 1100| 1200|
1300| 1400| 1500| 1600| 1700| 1800| 1900|
2000| 2100| 2200
24| 0.03| 0.04| 0.04| 0.05| 0.06| | | | | | | | | | | |
30| | | | 0.05| 0.06| 0.07| 0.08| 0.11| | | | | | | | |
36| | | | 0.06| 0.06| 0.09| 0.10| 0.11| 0.14| | | | | | | |
42| | | | | 0.05| 0.05| 0.06| 0.07| 0.08| 0.08| 0.09| 0.09| 0.11| | | |
48| | | | | | | 0.04| 0.06| 0.09| 0.10| 0.10| 0.11| 0.12| 0.13| 0.14| |
60| | | | | | | | | | 0.06| 0.07| 0.01| 0.08| 0.09| 0.10| 0.12| 0.13
Table 6 – Economizer with 1-in. Filter Pressure Drop (IN. W.C.)
Filter Size in. (mm)| Cooling
Tons
| Standard CFM (SCFM)
---|---|---
600| 700| 800| 900| 1000| 1100| 1200|
1300| 1400| 1500| 1600| 1700| 1800| 1900|
2000| 2100| 2200
600-1400CFM
12x20x1+12x20x1 (305x508x25+305x508x25)
| 2.0,
2.5
| ****
–
| ****
–
| ****
0.09
| ****
0.14
| ****
0.16
| ****
0.18
| ****
0.25
| ****
0.28
| ****
0.3
| ****
–
| ****
–
| ****
–
| ****
–
| ****
–
| ****
–
| ****
–
| ****
–
1200-1800 CFM
16x24x1+14x24x1 (406x610x25+356x610x25)
| ****
3.5
| ****
–
| ****
–
| ****
–
| ****
–
| ****
–
| ****
–
| ****
0.10
| ****
0.11
| ****
0.12
| ****
0.13
| ****
0.14
| ****
0.16
| ****
0.16
| ****
–
| ****
–
| ****
–
| ****
–
1500-2200 CFM
16x24x1+18x24x1 (406x610x25+457x610x25)
| 3.0,
4.0,
5.0
| ****
–
| ****
–
| ****
–
| ****
–
| ****
–
| ****
.08
| ****
.10
| ****
.11
| ****
.13
| ****
0.15
| ****
0.17
| ****
0.18
| ****
0.20
| ****
0.21
| ****
0.22
| ****
0.23
| ****
0.23
Table 7 – Filter Pressure Drop Table (IN. W.C.)
Filter Size in. (mm)| Cooling
Tons
| Standard CFM (SCFM)
---|---|---
600| 700| 800| 900| 1000| 1100| 1200|
1300| 1400| 1500| 1600| 1700| 1800| 1900|
2000| 2100| 2200
600-1400CFM
12x20x1+12x20x1 (305x508x25+305x508x25
| 2.0,
2.5
| ****
0.03
| ****
0.05
| ****
0.06
| ****
0.08
| ****
0.10
| ****
0.11
| ****
0.13
| ****
0.14
| ****
0.16
| ****
–
| ****
–
| ****
–
| ****
–
| ****
–
| ****
–
| ****
–
| ****
–
1200-1800 CFM
16x24x1+14x24x1 (406x610x25+356x610x25)
| ****
3.5
| ****
–
| ****
–
| ****
–
| ****
–
| ****
–
| ****
–
| ****
0.07
| ****
0.08
| ****
0.09
| ****
0.09
| ****
0.10
| ****
0.11
| ****
0.12
| ****
–
| ****
–
| ****
–
| ****
–
1100-2200 CFM
16x24x1+18x24x1 (406x610x25+457x610x25)
| 3.0
4.0
5.0
| ****
–
| ****
–
| ****
–
| ****
–
| ****
–
| ****
0.02
| ****
0.02
| ****
0.03
| ****
0.03
| ****
0.04
| ****
0.06
| ****
0.08
| ****
0.10
| ****
0.11
| ****
0.13
| ****
0.14
| ****
0.15
Table 8 – Electric Heat Pressure Drop Table (IN. W.C.) Small Cabinet: 24-36
STATIC | STANDARD CFM (SCFM) |
---|---|
500 | 600 |
1200 | 1300 |
5 kW | 0.00 |
10 kW | 0.00 |
15 kW | 0.00 |
20 kW | 0.00 |
Table 9 – Electric Heat Pressure Drop Table (IN. W.C) Large Cabinet: 42-60
STATIC | STANDARD CFM (SCFM) |
---|---|
1100 | 1200 |
1800 | 1900 |
2500
5 kW| 0.00| 0.00| 0.00| 0.01| 0.02| 0.03| 0.04| 0.05| 0.06| 0.07| 0.08| 0.09|
0.10| 0.11| 0.12
10 kW| 0.00| 0.00| 0.01| 0.02| 0.03| 0.04| 0.05| 0.06| 0.07| 0.08| 0.09| 0.10|
0.11| 0.12| 0.13
15 kW| 0.00| 0.02| 0.03| 0.04| 0.05| 0.06| 0.07| 0.08| 0.09| 0.10| 0.11| 0.12|
0.13| 0.14| 0.15
20 kW| 0.02| 0.03| 0.04| 0.05| 0.06| 0.07| 0.08| 0.09| 0.10| 0.11| 0.12| 0.13|
0.14| 0.15| 0.16
CONNECTION WIRING DIAGRAM DANGER: ELECTRICAL SHOCK HAZARD DISCONNECT
POWER BEFORE SERVICING
Fig. 12 – Connection Wiring Diagram 208/230-1-60
LADDER WIRING DIAGRAM DANGEP. ELECTRICAI SHOCK HAZARD DISCONNECT POWER REFORE SERVICING
CONNECTION WIRING DIAGRAM DANGER: ELECTRICAL SHOCK HAZARD DISCONNECT POWER BEFORE SERVICING
NOTES:
- IF ANY OF THE ORIGINAL WIRES FURNISHED ARE REPLACED
- IT MUST BE REPLACED WITH THE SAME OR IT’S EQUIVALENT.
- SEE PRE SALE LITERATURE FOR THERMOSTATS. USE 75 DEGREES C COPPER CONDUCTORS FOR FIELD
- INSTALLATION. REFER TO INSTALLATION INSTRUCTIONS FOR CORRECT SPEED SELECTION FOR IFM.
- RELOCATION OF SPEED TAPS MAY BE REQUIRED WHEN USING FIELD INSTALLED ELECTRIC HEATERS.
- CONSULT INSTALLATION INSTRUCTIONS TO DETERMINE CORRECT SPEED TAP SETTING
- “DO NOT DISCONNECT PLUG UNDER LOAD”. THIS FUSE IS MANUFACTURED
- BY LITTLE FUSE, P/N 287003. N.E.C. CLASS 2, 24V
- DEHUM FEATURE CANNOT BE USED WHEN ECONOMIZER IS INSTALLED. UNIT FACTORY – SHIPPED IN STD MODE.
- CCH NOT USED ON ALL UNITS.
Fig. 14 – Connection Wiring Diagram 208/230-3-60
LADDER WIRING DIAGRAM DANGER: ELECTRICAL SHOCK HAZARD DISCONNECT POWER BEFORE SERVICING
Fig. 15 – Ladder Wiring Diagram 208/230-3-60
CONNECTION WIRING DIAGRAM DANGER: ELECTRICAL SHOCK HAZARD DISCONNECT POWER BEFORE SERVICING
Fig. 16 – Connection Wiring Diagram 460-3-60
CONNECTION WIRING DIAGRAM DANGER: ELECTRICAL SHOCK HAZARD DISCONNECT POWER BEFORE SERVICING
Fig. 17 – Ladder Wiring Diagram 460-3-60
Superheat charging table is derived from optimum performance point. (95_F [35_C] outdoor ambient and (80_F [27_C] dry bulb; 67_F [19_C] wet bulb indoor condition.) Where a dash(–) appears do not attempt to check charge or charge unit under these conditions using the superheat method. (Weigh in method should be used.)
Fig. 18 – Cooling Charging Chart
Maintenance
To ensure continuing high performance, and to minimize the possibility of
premature equipment failure, periodic maintenance must be performed on this
equipment. This cooling unit should be inspected at least once each year by a
qualified service person. To troubleshoot unit, refer to Table 10,
Troubleshooting Chart.
NOTE TO EQUIPMENT OWNER: Consult your local dealer about the availability of a
maintenance contract.
WARNING
PERSONAL INJURY AND UNIT DAMAGE HAZARD Failure to follow this warning could
result in personal injury or death and possible unit component damage.
The ability to properly perform maintenance on this equipment requires certain
expertise, mechanical skills, tools and equipment. If you do not possess
these, do not attempt to perform any maintenance on this equipment, other than
those procedures recommended in the Owner’s Manual.
WARNINGELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow these warnings could result in personal injury or death
- Turn off electrical power to the unit and install lockout tag before performing any maintenance or service on this unit.
- Use extreme caution when removing panels and parts.
- Never place anything combustible either on or in contact with the unit.
CAUTIONUNIT
OPERATION HAZARD
Failure to follow this caution may result in equipment damage or improper
operation.
Errors made when reconnecting wires may cause improper and dangerous
operation. Label all wires prior to disconnecting when servicing.
The minimum maintenance requirements for this equipment are as follows:1.
Inspect air filter(s) each month. Clean or replace when necessary.
2. Inspect indoor coil, drain pan, and condensate drain each cooling season
for cleanliness. Clean when necessary.
3. Inspect blower motor and wheel for cleanliness each cooling season. Clean
when necessary.
4. Check electrical connections for tightness and controls for proper
operation each cooling season. Service when necessary.
5. Ensure electric wires are not in contact with refrigerant tubing or sharp
metal edges.
Air Filter
IMPORTANT: Never operate the unit without a suitable air filter in the return-
air duct system. Always replace the filter with the same dimensional size and
type as originally installed. See Table 1 for recommended filter sizes.
Inspect air filter(s) at least once each month and replace (throwaway-type) or
clean (cleanable-type) at least twice during each cooling season and twice
during the heating season, or whenever the filter becomes clogged with dust
and lint.
Indoor Blower and Motor
NOTE: All motors are pre-lubricated. Do not attempt to lubricate these motors.
For longer life, operating economy, and continuing efficiency, clean
accumulated dirt and grease from the blower wheel and motor annually.
WARNING ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect and tag electrical power to the unit before cleaning the blower
motor and wheel.To clean the blower motor and wheel:1. Remove and disassemble
blower assembly as follows:
- Remove blower access panel (see Fig. 20).
- Disconnect 5 pin plug and 4 pin plug from indoor blower motor. Remove capacitor if required.
- On all units remove blower assembly from unit. Remove screws securing blower to blower partition and slide assembly out. Be careful not to tear insulation in blower compartment.
- Ensure proper reassembly by marking blower wheel and motor in relation to blower housing before disassembly.
- Loosen setscrew(s) that secures wheel to motor shaft, remove screws that secure motor mount brackets to housing, and slide motor and motor mount out of housing.
- Remove and clean blower wheel as follows:
- Ensure proper reassembly by marking wheel orientation.
- Lift wheel from housing. When handling and/or cleaning blower wheel, be sure not to disturb balance weights (clips) on blower wheel vanes.
- . Remove caked-on dirt from wheel and housing with a brush. Remove lint and/or dirt accumulations from wheel and housing with vacuum cleaner, using soft brush attachment. Remove grease and oil with mild solvent.
- Reassemble wheel into housing.
- Reassemble motor into housing. Be sure setscrews are tightened on motor shaft flats and not on round part of shaft. Reinstall blower into unit.
- Connect 5 pin plug and 4 pin plug to indoor blower motor. Reinstall capacitor if required.
- Reinstall blower access panel (see Fig. 20).
- Restore electrical power to unit. Start unit and check for proper blower rotation and motor speeds during cooling cycles.
MAX DISTANCE BETWEEN TOP OF FAN GRILLE AND BOTTOM OF FAN BLADE
Size| “A” IN.
mm
---|---
|
24| 9.0| 228
30| 8.0| 203
36| 7.6| 193
42| 7.6| 193
48| 7.6| 193
60| 7.6| 193
Fig. 19 – Fan Blade Position
Outdoor Coil, Indoor Coil, and Condensate Drain Pan
Inspect the condenser coil, evaporator coil, and condensate drain pan at least
once each year.
The coils are easily cleaned when dry; therefore, inspect and clean the coils
either before or after each cooling season. Remove all obstructions, including
weeds and shrubs, that interfere with the airflow through the condenser coil.
Straighten bent fins with a fin comb. If coated with dirt or lint, clean the
coils with a vacuum cleaner, using the soft brush attachment. Be careful not
to bend the fins. If coated with oil or grease, clean the coils with a mild
detergent and water solution. Rinse coils with clear water, using a garden
hose. Be careful not to splash water on motors, insulation, wiring, or air
filter(s). For best results, spray condenser coil fins from inside to outside
the unit. On units with an outer and inner condenser coil, be sure to clean
between the coils. Be sure to flush all dirt and debris from the unit base.
Inspect the drain pan and condensate drain line when inspecting the coils.
Clean the drain pan and condensate drain by removing all foreign matter from
the pan. Flush the pan and drain trough with clear water. Do not splash water
on the insulation, motor, wiring, or air filter(s). If the drain trough is
restricted, clear it with a “plumbers snake” or similar probe device.
Outdoor Fan
CAUTIONUNIT OPERATION HAZARD
Failure to follow this caution may result in damage to unit components. Keep
the condenser fan free from all obstructions to ensure proper cooling
operation. Never place articles on top of the unit.
-
Remove 6 screws holding condenser grille and motor to top cover.
Turn motor/grille assembly upside down on top cover to expose the fan blade. -
Inspect the fan blades for cracks or bends.
-
If fan needs to be removed, loosen the setscrew and slide the fan off the motor shaft.
-
When replacing fan blade, position blade as shown in Fig. 19.
-
Ensure that setscrew engages the flat area on the motor shaft when tightening
-
Replace grille.
Electrical Controls and Wiring
Inspect and check the electrical controls and wiring annually. Be sure to turn
off the electrical power to the unit.
Remove access panels (see Fig. 20) to locate all the electrical controls and
wiring. Check all electrical connections for tightness. Tighten all screw
connections. If any smoky or burned connections are noticed, disassemble the
connection, clean all the parts, restripe the wire end and reassemble the
connection properly and securely.
After inspecting the electrical controls and wiring, replace the access panels
(see Fig. 20). Start the unit, and observe at least one complete heating cycle
and one complete cooling cycle to ensure proper operation. If discrepancies
are observed in either or both operating cycles, or if a suspected malfunction
has occurred, check each electrical component with the proper electrical
instrumentation. Refer to the unit wiring label when making these checkouts.
NOTE: Refer to the heating and/or cooling sequence of operation in this
publication as an aid in determining proper control operation
Refrigerant Circuit
Inspect all refrigerant tubing connections.
WARNING
EXPLOSION, SAFETY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could result in personal injury, death or equipment damage.
This system uses Puron (R-410A) refrigerant which has higher operating pressures than R-22 and other refrigerants. No other refrigerant may be used in this system. Gauge set, hoses, and recovery system must be designed to handle Puron (R-410A). If you are unsure, consult the equipment manufacturer.
If low cooling performance is suspected, leak-test all refrigerant tubing
using an electronic leak-detector or liquid-soap solution. If a refrigerant
leak is detected, refer to the Check for Refrigerant Leaks section.
If no refrigerant leaks are found and low cooling performance is suspected,
refer to the Checking and Adjusting Refrigerant Charge section.
Evaporator Airflow
The heating and/or cooling air-flow does not require checking unless improper
performance is suspected. If a problem exists, be sure that all supply- and
return-air grilles are open and free from obstructions, and that the air
filter is clean. When necessary, refer to Indoor Airflow and Airflow
Adjustments section to check the system airflow.
Puron (R-410A) Items
The indoor metering device is either a TXV or orifice type device depending on
size.
Pressure Switches
Pressure switches are protective devices wired into the control circuit (low
voltage). They shut off compressor if abnormally high or low pressures are
present in the refrigeration circuit. These pressure switches are specifically
designed to operate with Puron (R-410A) systems. R-22 pressure switches must
not be used as replacements for the Puron (R-410A) air conditioner.
Low Pressure Switch (if used)
This switch is located on the suction line and protects against low suction
pressures caused by such events as loss of charge, low airflow across indoor
coil, dirty filters, etc. It opens at 50 psig (957 Pa). If system pressure is
above this, switch should be closed.
To check switch:
- Turn off all power to unit.
- 2. Disconnect leads on switch.
- Apply ohmmeter leads across switch. You should have continuity on a closed switch.
NOTE: Because these switches are attached to refrigeration system under pressure, it is not advisable to remove this device for troubleshooting unless you are reasonably certain that a problem exists. If switch must be removed, remove and recover all system charge so that pressure gauges read 0 psi (0 Pa). Never open system without breaking vacuum with dry nitrogen.
High-Pressure Switch
The high-pressure switch is located in the discharge line and protects against
excessive condenser coil pressure. It opens at 650 psig (31.1 kPa). High
pressure may be caused by a dirty condenser coil, failed fan motor, or
condenser air recirculation.
To check switch:
- Turn off all power to unit.
- Disconnect leads on switch.
- Apply ohmmeter leads across switch. You should have continuity on a good switch.
Compressor (Puron (R-410A) Refrigerant)
The compressor used in this product is specifically designed to operate with
Puron (R-410A) refrigerant and cannot be interchanged.
The compressor is an electrical (as well as mechanical) device. Exercise
extreme caution when working near compressors. Power should be shut off, if
possible, for most troubleshooting techniques. Refrigerants present additional
safety hazards.
FIRE/EXPLOSION HAZARD
Failure to follow this warning could result in personal injury or death and/or
property damage.
Wear safety glasses and gloves when handling refrigerants. Keep torches and
other ignition sources away from refrigerants and oils.
For models that have a scroll compressor, the compressor pumps refrigerant
throughout the system by the interaction of a stationary and an orbiting
scroll. The scroll compressor has no dynamic suction or discharge valves, and
it is more tolerant of stresses caused by debris, liquid slugging, and flooded
starts. The compressor is equipped with a noise reducing shutdown device and
an internal pressure relief port. The pressure relief port is a safety device,
designed to protect against extreme high pressure. The relief port has an
operating range between 550 (26.3 kPa) and 625 (29.9 kPa) psig differential
pressure.
Refrigerant
WARNING
EXPLOSION, ENVIRONMENTAL HAZARD
Failure to follow this warning could result in personal injury, death or
equipment damage.
This system uses Puron (R-410A) refrigerant which has higher operating
pressures than R-22 and other refrigerants. No other refrigerant may be used
in this system. Gauge set, hoses, and recovery system must be designed to
handle Puron (R-410A). If you are unsure, consult the equipment manufacturer.
This system uses Puron (R-410A) refrigerant which has higher operating pressures than R-22 and other refrigerants. No other refrigerant may be used in this system. Gage set, hoses, and recovery system must be designed to handle Puron (R-410A). If you are unsure, consult the equipment manufacturer. Failure to use Puron (R-410A) compatible servicing equipment or replacement components may result in property damage or injury.
Compressor Oil
The Copeland scroll compressor uses 3MAF POE oil. If additional oil is needed,
use Uniqema RL32-3MAF. If this oil is not available, use Copeland Ultra 32 CC
or Mobil Arctic EAL22 CC. This oil is extremely hygroscopic, meaning it
absorbs water readily. POE oils can absorb 15 times as much water as other
oils designed for HCFC and CFC refrigerants. Take all necessary precautions to
avoid exposure of the oil to the atmosphere.
Servicing Systems on Roofs with Synthetic Materials
POE (polyolester) compressor lubricants are known to cause long term damage to
some synthetic roofing materials. Exposure, even if immediately cleaned up,
may cause embrittlement (leading to cracking) to occur in one year or more.
When performing any service that may risk exposure of compressor oil to the
roof, take appropriate precautions to protect roofing. Procedures which risk
oil leakage include, but are not limited to, compressor replacement, repairing
refrigerant leaks, replacing refrigerant components such as filter drier,
pressure switch, metering device, coil, accumulator, or reversing valve.
Synthetic Roof Precautionary Procedure
- 1. Cover extended roof working area with an impermeable polyethylene (plastic) drip cloth or tarp. Cover an approximate 10 x 10 ft (3 x 3 m) area.
- Cover area in front of the unit service panel with a terry cloth shop towel to absorb lubricant spills, prevent run-offs, and protect drop cloth from tears caused by tools or components.
- Place terry cloth shop towel inside unit immediately under component(s) to be serviced and prevent lubricant run-offs through the louvered openings in the unit base.
- Perform required service.
- Remove and dispose of any oil contaminated material per local codes.
Liquid Line Filter Drier
The filter drier is specifically designed to operate with Puron (R-410A). Use only factory-authorized components. Filter drier must be replaced whenever the refrigerant system is opened. When removing a filter drier, use a tubing cutter to cut the drier from the system. Do not unsweat a filter drier from the system. Heat from unsweating will release moisture and contaminants from drier into system.
Puron (R-410A) Refrigerant Charging
Refer to unit information plate and charging chart. Some R-410A refrigerant
cylinders contain a dip tube to allow liquid refrigerant to flow from cylinder
in upright position. For cylinders equipped with a dip tube, charge Puron
(R-410A) units with cylinder in upright position and a commercial metering
device in manifold hose. Charge refrigerant into suction-line.
troubleshooting
Refer to the Troubleshooting Chart (Table 10) for troubleshooting information.
Start-up Checklist
Use the Start-Up Checklist at the back of this manual.
My Learing Cener is your central location for professional residential HVAC
training resources that help strengthen careers and businesses. We believe in
providing high quality learning experiences both online and in the classroom.
Access My Learning Center with your HVACpartners credentials at
www.MLCtraining.com. Please contact us at
mylearning@carrier.com with questions.
Table 10 – Troubleshooting Chart
SYMPTOM | CAUSE | REMEDY |
---|---|---|
Compressor and outdoor fan will not start | Power failure | Call power company |
Fuse blown or circuit breaker tripped | Replace fuse or reset circuit breaker |
Defective contactor, transformer, control relay, or high-pressure, loss-of-
charge or low-pressure switch| Replace component
Insufficient line voltage| Determine cause and correct
Incorrect or faulty wiring| Check wiring diagram and rewire correctly
Thermostat setting too low/too high| Reset thermostat setting
Compressor will not start but condenser fan runs
| Faulty wiring or circuit Loose connections in compressor| Check wiring and
repair or replace
Compressor motor burned out, seized, or| Determine cause
internal overload open| Replace compressor
Defective run capacitor, overload, or PTC (positive temperature coefficient)
thermistor| Determine cause and replace
One leg of 3-phase power dead| Replace fuse or reset circuit breaker Determine
cause
Low input voltage| Determine cause and correct
Three-phase scroll compressor (size 36- 60 unit) has a low pressure
differential| Scroll compressor is rotating in the wrong direction| Correct
the direction of rotation by reversing the 3-phase power leads to the unit
Compressor cycles (other than normally satisfying) cooling/heating calls
| Refrigerant overcharge or undercharge| Recover refrigerant, evacuate system,
and recharge to capacities shown on rating plate
Defective compressor| Replace and determine cause
Insufficient line voltage| Determine cause and correct
Blocked outdoor coil| Determine cause and correct
Defective run/start capacitor, overload or start relay| Determine cause and
replace
Faulty outdoor fan motor or capacitor| Replace
Restriction in refrigerant system| Locate restriction and remove
Compressor operates continuously
| Dirty air filter| Replace filter
Unit undersized for load| Decrease load or increase unit size
Thermostat temperature set too low| Reset thermostat setting
Low refrigerant charge| Locate leak, repair, and recharge
Air in system| Recover refrigerant, evacuate system, and recharge
Outdoor coil dirty or restricted| Clean coil or remove restriction
Excessive head pressure
| Dirty air filter| Replace filter
Dirty indoor or outdoor coil| Clean coil
Refrigerant overcharged| Recover excess refrigerant
Air in system| Recover refrigerant, evacuate system, and recharge
Indoor or outdoor air restricted or air short-cycling| Determine cause and
correct
Head pressure too low| Low refrigerant charge| Check for leaks, repair and
recharge
Restriction in liquid tube| Remove restriction
Excessive suction pressure| Refrigerant overcharged| Recover excess
refrigerant
Suction pressure too low| Dirty air filter| Replace filter
Low refrigerant charge| Check for leaks, repair and recharge
Metering device or low side restricted| Remove source of restriction
Insufficient coil airflow| Check filter–replace if necessary
Temperature too low in conditioned area| Reset thermostat setting
Outdoor ambient below 55±F (13±C)| Install low-ambient kit
Filter drier restricted| Replace
Start-Up Checklist
(Remove and Store in Job Files)
- I.PRELIMINARY INFORMATION
- MODEL NO.: ____
- SERIAL NO.: ____
- DATE: __
- TECHNICIAN:___
PRESTART-UP (Insert check mark in box as each item is completed)
- VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT
- REMOVE ALL SHIPPING HOLD DOWN BOLTS AND BRACKETS PER INSTALLATION INSTRUCTIONS
- CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS
- CHECK THAT INDOOR (EVAPORATOR) AIR FILTER IS CLEAN AND IN PLACE
- VERIFY THAT UNIT INSTALLATION IS LEVEL
- CHECK FAN WHEEL, AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS ( ) INSPECT TUBING
START-UP
ELECTRICAL
- SUPPLY VOLTAGE ___
- COMPRESSOR AMPS ____
- NDOOR (EVAPORATOR) FAN AMPS ___
- TEMPERATURES
- OUTDOOR (CONDENSER) AIR TEMPERATURE __ DB
- RETURN-AIR TEMPERATURE__ DB ___ WB
- COOLING SUPPLY AIR ____ DB ___ WB
PRESSURES
-
REFRIGERANT SUCTION____
-
PSIG,SUCTION LINE TEMP*_____
-
-
REFRIGERANT DISCHARGE ____
PSIG, LIQUID TEMP†___ -
- VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS
-
- Measured at suction inlet to compressor
-
{Measured at liquid line leaving condenser.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 3
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>