Midea V3-B Talking Flash Cards Early Educational Toys Preschool Learning Reading Installation Guide
- June 1, 2024
- Midea
Table of Contents
V3-B Talking Flash Cards Early Educational Toys Preschool Learning
Reading
“`html
Product Specifications
Outdoor Unit: Designed for outdoor
installation
Water Tank: Capacity of XX liters
Specifications: Refer to section 2.3 for
detailed specifications
Product Usage Instructions
1. Safety Precautions
-
DANGER: Indicates an imminently hazardous
situation which if not avoided, will result in death or serious
injury. -
WARNING: Indicates a potentially hazardous
situation which if not avoided, could result in death or serious
injury. -
CAUTION: Indicates a potentially hazardous
situation which if not avoided, may result in minor or moderate
injury. -
NOTE: Indicates situations that could only
result in accidental equipment or property damage.
2. General Introduction
Introduces the outdoor unit and water tank of the product.
3. Before Installation
-
Accessories: Check for all provided
accessories before installation. -
Space for Maintenance: Ensure there is
adequate space for maintenance purposes.
Frequently Asked Questions (FAQ)
Q: How often should the relief valve easing gear be
operated?
A: It is recommended to operate the relief
valve easing gear at least once every six months to prevent
potential issues.
Q: Can the water heater deliver water at high
temperatures?
A: Yes, the water heater may deliver water at
high temperatures. Refer to local regulations and installation
instructions for temperature control requirements.
“`
CONTENTS
1 SAFETY PRECAUTIONS
01
2 GENERAL INTRODUCTION
2.1 Outdoor unit
05
2.2 Water tank
05
2.3 Specifications
06
3 BEFORE INSTALLATION
3.1 Accessories
07
3.2 Space for maintenance
07
4 INSTALLATION PROCEDURE
4.1 Dimension sketch and fixed way
09
4.2 Drain hole position
10
4.3 Pipe connection
11
4.4 Vacuum drying
13
4.5 Refrigerant charge
14
5 ELECTRICAL CONNECTION
5.1 Power supply cords
15
5.2 Water tank temperature sensor installation
16
5.3 ODU & AUX. power connection
16
5.4 Dial code definitions
17
6 CHECK
18
7 OPERATIONS AND PERFORMANCES
19
8 MAINTENANCE
8.1 Confirmation before running
20
8.2 Troubleshooting when abnormal situation happens
20
8.3 After-sale service
20
8.4 Important information for the used refrigerant
20
8.5 Water quality limitations
21
9 ERROR CODE SHOOTING TABLE
22
10 WARRANTY
23
1 SAFETY PRECAUTIONS
The precautions listed here are divided into the following types. They are
mportant, so be sure to follow them carefully. Meanings of DANGER, WARNING,
CAUTION and NOTE symbols.
i INFORMATION
Read these instructions carefully before installation. Keep this manual in a
handy for future reference. Improper installation of equipment or accessories
may result in electric shock, short-circuit, leakage, fire or other damage to
the equipment. Be sure to only use accessories made by the supplier, which are
specifically designed for the equipment and make sure to get installation done
by a professional. All the activities described in this manual must be carried
out by a licensed technician. Be sure to wear adequate personal protection
equipment such as gloves and safety glasses while installing the unit or
carrying out maintenance activities. Contact your dealer for any furth r
assistance.
DANGER
Indicates an imminently hazardous situation which if not avoided, will result
in death or serious injury.
WARNING
Indicates a potentially hazardous situation which if not avoided, could result
in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which if not avoided, may result
in minor or moderate injury. It is also used to alert against unsafe
practices.
NOTE
Indicates situations that could only result in accidental equipment or
property damage.
Explanation of symbols displayed on the unit
CAUTION
This symbol shows that the operation manual should be read carefully.
CAUTION
This symbol shows that a service personnel should be handling this equipment with reference to the installation manual.
CAUTION
This symbol shows that information is available such as the operating manual or installation manual.
WARNING
For continued safety of this appliance it must be installed, operated and
maintained in accordance with the manufacturer’s instructions.
WARNING
This appliance may deliver water at high temperature. Refer to the Plumbing
Code of Australia (PCA), local requirements and installation instructions to
determine if additional delivery temperature control is required.
01
DANGER
The operation of the thermal cut-out indicates a possibly dangerous situation.
Do not reset the thermal cut-out until the water heater has been serviced by a
qualified person.
Failure to operate the relief valve easing gear at least once every six months
may result in the water heater exploding. Continuous leakage of water from the
valve may indicate a problem with the water heater.
If the hot water system is not used for two weeks or more, a quantity of
highly flammable hydrogen gas may accumulate in the water heater. To dissipate
this gas safely, it is recommended that a hot tap be turned on for several
minutes or until discharge of gas ceases. Use a sink, basin, or bath outlet,
but not a dishwasher, clothes washer, or other appliance. During this
procedure, there must be no smoking, open flame, or any electrical appliance
operating nearby. If hydrogen is discharged through the tap, it will probably
make an unusual sound as with air escaping.
Before touching electric terminal parts, turn off power switch.
Do not touch the inner parts of the controller. Do not remove the front panel.
Some parts inside are dangerous to touch, otherwise a machine malfunction may
be caused.
When front panels are removed, live parts can be easily touched by accident.
Never leave the unit unattended during installation or servicing when the
front panel is removed.
Do not touch water pipes during and immediately after operation as the pipes
may be hot and could burn your hands. To avoid injury, give the piping time to
return to normal temperature or be sure to wear protective gloves.
Do not touch any switch with wet fingers. Touching a switch with wet fingers
can cause electrical shock.
Before touching electrical parts, turn off all applicable power to the unit.
WARNING
If the water supply pressure exceeds the rated pressure, a pressure reducing valve is to be fitted in the installation.
The water may drip from the discharge pipe of the pressure-relief device and that this pipe must be left open to the atmosphere.
The pressure-relief device is to be operated regularly to remove lime deposits and to verify that it is not blocked.
A discharge pipe connected to the pressure-relief device is to be installed in a continuously downward direction and in a frost-free environment.
For appliances with supplementary heaters, the minimum clearance from the appliance to combustible surfaces will be 3m.
The installation of the appliance shall
to the Plumbing Code of Austral
.
Do not remove, cover or deface any permanent instructions, labels, or the data labels from either the outside of the unit or inside of unit panels.
Require qualified person for relocating, repairing and maintaining the unit
Electric connection work should obey the instructions of local power company, local electric utility and this manual.
Never use the wiring and fuse with wrong rated current, otherwise the unit may break down and cause fire.
Do not insert fingers, rods or other objects into the air inlet or outlet. When the fan is rotating at high speed, it will cause injury.
Never use a flammable spray such as hair spray, lacquer paint near the unit. It may cause a fire.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
Tear apart and throw away plastic packaging bags so that children will not play with them. Children playing with plastic bags face danger of death by suffocation.
Safely dispose of packing materials such as nails and other metal or wood parts that could cause injuries.
Ask your dealer or qualified personnel to perform installation work in accordance with this manual. Do not install the unit yourself. Improper installation could result in water leakage, electric shocks or fire.
Be sure to use only specified accessories and parts for installation work. Failure to use specified parts may result in water leakage, electric shocks, fire, or the unit falling from its mount.
Install the unit on a foundation that can withstand its weight.
and
possible
injury.
may cause the equipment to fall
Perform specified installation work with full consideration of strong wind, hurricanes, or earthquakes. Improper installation work may result in accidents due to equipment falling.
02
Make certain that all electrical work is carried out by qualified personnel according to the local laws and
regulations and this manual
. Insufficient capacity of the power
supply circuit or improper electrical construction may lead to electric shocks or fire.
Be sure to install a ground fault circuit interrupter according to local laws and regulations. Failure to install a ground fault circuit interrupter may cause electric shocks and fire.
Make sure all wiring is secure. Use the specified wires and ensure that terminal connections or wires are protected from water and other adverse external forces. Incomplete connection or affixing may cause a fire.
When wiring the power supply, form the wires so that the front panel can be securely fastened. If the front panel is not in place there could be overheating of the terminals, electric shocks or fire.
After completing the installation work, check to make sure that there is no refrigerant leakage.
Never directly touch any leaking refrigerant as it could cause severe frostbite. Do not touch the refrigerant pipes during and immediately after operation as the refrigerant pipes may be hot or cold, depending on the condition of the refrigerant flowing through the refrigerant piping, compressor and other refrigerant cycle parts. Burns or frostbite are possible if you touch the refrigerant pipes. To avoid injury, give the pipes time to return to normal temperature or, if you must touch them, be sure to wear protective gloves.
Do not touch the internal parts (pump, backup heater, etc.) during and immediately after operation. Touching the internal parts can cause burns. To avoid injury, give the internal parts time to return to normal temperature or, if you must touch them, be sure to wear protective gloves.
Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants.
CAUTION
The earthing pole of socket must be grounded well, make sure that power supply
socket and plug are dry enough and connected tightly.
Before cleaning, be sure to stop the unit and turn the breaker off or pull out
the power plug.
After a long term use, check the unit base and fittings. If damaged, the unit
may sink and result in injury.
Arrange the drain pipe to ensure smooth draining.
Do not turn off the power supply. System will stop or restart heating
automatically. A continuous power supply for water heating is necessary,
except service and maintenance.
Ground the unit.
Grounding resistance should be according to local laws and regulations.
Do not connect the ground wire to gas or water pipes, lightning conductors or
telephone ground wires. Incomplete grounding may cause electric shocks.
– Gas pipes Fire or an explosion might occur if the gas leaks.
– Water pipes Hard vinyl tubes are not effective grounds.
– Lightning conductors or telephone ground wires Electrical threshold may rise
abnormally if struck by a lightning bolt.
Do not wash the unit. This may cause electric shocks or fire. The appliance
must be installed in accordance with national wiring regulations. If the
supply cord is damaged, it must be replaced by the manufacturer, its service
agent or similarly qualified persons in order to avoid a hazard.
Do not install the unit in the following places:
– Where there is mist of mineral oil, oil spray (eg: kitchen) or vapors.
Plastic parts may deteriorate, and cause them to come loose or water to leak.
– Where corrosive gases (such as sulphurous acid gas) are produced. Where
corrosion of copper pipes or soldered parts may cause refrigerant to leak.
– Where there is machinery which emits electromagnetic waves. Electromagnetic
waves can disturb the control system and cause equipment malfunction.
– Where flammable gases may leak, where carbon fiber or ignitable dust is
suspended in the air or where volatile flammables such as paint thinner or
gasoline are handled. These types of gases might cause a fire.
– In vehicles or vessels.
– Where acidic or alkaline vapors are present.
– Other special environments.
03
This appliance can be used by children 8 years old and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they are supervised or given instruction on using the unit in a safe manner and understand the hazards involved. Children should not play with the unit. Cleaning and user maintenance should not be done by children without supervision.
Children should be supervised to ensure that they do not play with the appliance.
If the supply cord is damaged, it must be replaced by the person.
or its service agent or a similarly qualified
DISPOSAL: Do not dispose this product as unsorted municipal waste. Collection of such waste
for special
treatment is necessary. Do not dispose of electrical appliances as municipal waste, use
collection facilities.
Contact your local
for information regarding the collection systems available. If electrical appliances are
disposed of in landfills or dumps, hazardous substance can leak into the
and get into the food chain,
damaging your health and well-being.
The wiring must be performed by professional technicians in accordance with national wiring regulation and this circuit
diagram. An all-pole disconnection device which has at least 3mm
distance in all pole and a
device(RCD) with the rating not exceeding 30mA shall be incorporated in the fixed wiring according to the national rule.
Confirm the safety of the ins gas.
hout hidden dangers such as water, electricity, and
Before installation, check whether the user’s power supply meets the electrical installation requirements of unit (including reliable grounding, leakage, and ire diameter electrical load, etc.). If the electrical installation requirements of the product are not met, the installation of the product is prohibited until the product is rectified.
When installing multiple air conditioners in a centrali ed manner, please confirm the load balance of the three-phase power supply, and multiple units are prevented from being assembled into the same phase of the three-phase power supply.
Product installation should be fixed firmly. Take reinforcement measures, when necessary.
NOTE
The appliance is intended to be permanently connected to the water mains and
not connected by a hose-set. When using the off-peak function, the product can
only work under the off-peak power supply all the time. About Fluorinated
Gasses This air-conditioning unit contains fluorinated gasses. For specific
information on the type of gas and the amount, please refer to the relevant
label on the unit itself. Compliance with national gas regulations shall be
observed. – Installation, service, maintenance and repair of this unit must be
performed by a certified technician. – Product un installation and recycling
must be performed by a certified technician.
Generally, the ambient air temperature of the unit must be above -15°C and below 43°C.
Install safety valve to water inlet, the largest torque of safety valve shouldn’t be more than 80N.m.
Please make sure water tank is
upright. Install in the place that can prevent unit toppling and falling (e.g.
balcony or corner). If install unit in an open space, to avoid being blown down by strong wind (
in are
with strong wind), please fix water tank according to operation manual.
All the diagrams in this manual is for reference only, its appearance and function may different from heater ctual model shall prevail.
water
04
2 GENERAL INTRODUCTION
2.1 Outdoor unit
5
5
4
2.2 Water tank
3 1 2
5 4 12
UP
300L With Aux.*
6 7
8 9 12 10
11
Fig. 2-2
Table 2-1
No.
Name
Power cord enter Refrigerant gas valve
Refrigerant liquid valve Air outlet
5 Air inlet
1
2 3
Fig. 2-1
Table 2-2
No.
Name
1 Magnesium rod insertion port 2 Foam filling port 3 Reserved port 4 Water
outlet
5 Temperature pressure safety valve 6 Water tank temperature sensor 7 Handle 8
Refrigerant gas pipe 9 Re5frigerant liquid pipe 10 Water inlet
11 Drain outlet 12 Electric auxiliary heater
05
- Electric auxiliary heater is shortened to Aux.
2.3 Specifications
odel
odel
Ambient temperature
Leaving water temperature
Heating
Capacity1 Input
General Hot water yield
W W m3/h
Liquid side
mm/inch
Refrigerant Gas side
piping
Max. height difference
mm/inch m
Max. refrigerant pipe length m
Design pressure
MPa
Outdoor unit power supply
V/N/Hz
Max. current
A
Compressor Type Fan
Type
Type
Air side heat exchanger
Outdoor unit
Throttle Outdoor sound pressure level
Unit dimension(LWH)
Type Type dB(A) mm
Dimension Packing dimension(LWH) mm
Net weight
kg
Gross weight
kg
Refrigerant
Type
Charged volume
g
Tank volume
L
Water Tank
Electric heater
Dimension
Capacity Power supply Unit dimension(WDH) Packing dimension(WDH) Net weight Gross weight
kW V/N/Hz
mm mm kg kg
Notes:
MT-200R26E20 MT-200R26E20
-15~46 20~60 2600 1000 0.04411/ 0.05622
Table 2-3 MT-300R26E20 MT-300R26E20
10 20 3 220-240/1/50
Rotary
AC
Hydraulic aluminum fin + Inner grooved copper tube
Electric expansion valve
54
804327555
845390630
29
32
R134a
900
200
300
1
220-240/1/50
220-240/1/50
5055051665
5805801735
1775635590
1835690670
73
96
83
108
1. Ambient temperature 19/15 (DB/WB), Initial water temperature 9 , Terminative water temp. 60 . 2. Ambient temperature 19/15 (DB/WB), Initial water temperature 15 , Terminative water temp. 55 .
Unit:
Table 2-4
Ambient Leaving water temperature temperature
-15~-10
50
60
-10~43
60
55 50
43~46
55
Fig. 2-3
Leaving water temperature
20 -15 -10
Ambient temperature
06
43 46
3 BEFORE INSTALLATION 3.1 Accessories
Accessory Name
Qty. Shape Purpose
Table 3-1
Installation manual
1
Manual of wired controller
1
Need by master unit Wired controller instructions
Wired controller components 1
Control unit and display unit status
Outdoor unit Water drainage connection
1
Water drainage pipe
1
Plastic expansion tube
4
Screw
4
Fixing box of HMI
1
Wiring for HMI
1
Water tank fixing strip
1
PTR valve
1
Safety valve
1
Water tank
Safety valve connector
2
Water drainage pipe for water tank(with hose clamp)
1
For condensate water draining Condensate water drainage of unit bottom plate To fix mounting box To fix mounting box Install the wired controller Connect the unit and HMI Fixed water tank Pressure relief Prevents backflow of water Connect the safety valve and the water tank Drain water from tank when necessary
3.2 Space for maintenance NOTE
During installing, it is necessary to reserve enough installation space and
maintenance space according to the following figures.
3.2.1 Outdoor unit installation and maintenance space, see Fig 3-1 and Fig 3-2
. (Unit: mm)
Use bolt to fix
Fig 3-1
07
Air outlet 3.2.2 Water tank installation and maintenance space, see Fig 3-3 and Fig 3-4 . (Unit: mm)
Fig 3-2
NOTE
hen the water tank is installed outdoors, the distance between the water tank
and the fence is not less than 200mm.
hen the water tank is installed indoors, the distance between the water tank
and the wall is not less than 600mm.
Fig 3-3
Fig 3-4
08
4 INSTALLATION PROCEDURE
NOTE
Ask your dealer or speciali ed person for moving, repair and maintenance.
The
horizontal, and its structure
endure the weight of the unit.
Please firmly install the unit, otherwise it may cause abnormal noise and vibration.
Remove obstacles nearby, a narrow circulation space may influence performance of the unit.
Install in the place that closes to water tank as possible, under the condition that the installation requirements could be satisfied.
When installing in the place that near to the sea and high place where strong wind blows, install the unit against a wall or use a baffle when necessary to ensure the unit could run normally, see Fig 4-1. Especially in the place with strong wind, pay attention not to let strong wind blow back to the unit.
If install the unit in a basement, inside the room or other confined space, please pay attention to air discharge and air supply circulation around the unit and outside. Circulation air volume should not less than 1250m3/h.
Strong wind
4.1
Dimension
4.1.1 Outdoor unit, see Fig. 4-2, Fig. 4-3 and Table 4-1 (Unit: mm)
×
Fig. 4-1
A
D
E
Dimension
Table 4-1
A
B
C
D
E
804 555 302 452 137
Fig. 4-2
Please fix the four bases of the outdoor unit on the flat ground with bolts.
Fig. 4-3
09
4.1.2 Water tank, see Fig. 4-4, Fig. 4-5 and Table 4-2 (Unit: mm)
Table 4-2
Dimension
A
H
Model
200L
505
1665
300L
580
1735
H
A
4.2 Drain hole position
Water outlet connection pipe/ Gasket
Fig. 4-4
. Fig. 4-5
Please use the Allen wrench to open the drain valve to drain the water. If no water flows out, it means that the draining is completed.
Fig 4-6
Drain outlet Fig 4-7
10
4.3 Pipe connection
4.3.1 Unit connection Unit connection
, please refer to Fig.4-8.
Hot water outlet
9.52 6.35
Cold water inlet
Outdoor unit
Water tank
Fig. 4-8
Icons and meanings
Name
Water end user
Stop valve
Table 4-3
Water mixing
valve
(
)
Icon
NOTE
The water tank temperature can be set from 20 t o 60 .
The minimum water inlet pressure is not less than Pa, and the maximum is not more than Pa. If the
inlet water pressure is less than Pa, a pump should be installed at the water inlet.
To guarantee the safety usage of tank, a the water pressure exceeds Pa.
valve should be installed in the water inlet pipe, if
It is strongly recommended to use thread seal tape for sealing when connecting water pipes and valves.
11
4.3.2 PTR valve
The valve body unloading pressure is 850kPa, unloading temperature is 99 , and
the valve body opening energy value is 46kW, more details refer to certificate
No:WMK26608.
PT valve is tightened with a 68N.m torque wrench. Apply sealant to the first 3
turns of screw thread before installation; After installation, the outlet of
the drain pipe shall be installed face down, and the thread turns that are not
screwed into the PT valve shall be less than 3 turns.
Before filling the water tank the PTR valve must be installed properly.
The PTR valve should be checked every half year to make sure that there is no
restriction of the valve. Please beware of hot water from the valve. The
drainage pipe should be well insulated in order to prevent water inside pipe
from freezing in cold weather.
Handle
Drainage pipe
4.3.3 Stop valve instruction In general, the shape of stop valve and names of
each part are shown in Fig.4-10. Effect of stop valve: – Stop the system when
the unit is working. – When water tank connects with the outdoor unit, vacuumi
e and add refrigerant through it. – Stop the system and then recycle
refrigerant to outdoor unit when maintaining. Open and close the stop valve: –
Open: dismantle the bonnet by wrench and insert an *Allen key to spool, open
the stop block anticlockwise and then tighten the bonnet. – Close: use a
wrench to dismantle the bonnet and insert an Allen key to spool, close the
stop block clockwise and then tighten the bonnet.
Fig.4-9 *Allen key
Spool Valve spool
Bonnet Connection nut Ball-shape cushion
Connection pipe
Fig.4-10
CAUTION
Before water heater runs, please make sure every stop valve has been opened.
4.3.4 Connection length of outdoor unit and water tank pipe and height difference requirements: Table 4-4
Max.length (m)
20
Max. height difference (m)
10
12
NOTE
Do not let air, dust, or other impurities fall in the pipe system during
installation. The connecting pipe should not be installed until the indoor and
outdoor units have been fixed already. Keep the connecting pipe dry, and do
not let moisture in during installation. When connecting copper pipe, please
wrap it with thermal insulation material.
4.4 Vacuum Drying
4.4.1 Purpose Vacuum drying should be performed in order to remove moisture
and non-condensable gases from the system. Removing moisture prevents ice
formation and oxidization of copper piping or other internal components. The
presence of ice particles in the system would cause abnormal operation, whilst
particles of oxidized copper can cause compressor damage. The presence of non-
condensable gases in the system would lead to pressure fluctuations and poor
heat exchange performance. 4.4.2 Procedure
Pressure gauge Vacuum pump
Outdoor unit
1
2
Service port
1 Gas pipe stop valve 2 Liquid pipe stop valve
Fig.4-11
13
Item
Description
Connect the (low pressure side) 1 hose of a pressure gauge to the
outdoor unit gas pipe stop valve.
2
Connect the hose to the vacuum pump.
3
Connect the outdoor unit gas pipe stop valve to water tank gas pipe
4
Connect the outdoor unit liquid pipe stop valve to water tank liquid pipe
Start the vacuum pump and then open 5 the pressure gauge valves to start
vacuum the system.
Image
Notice
Table 4-5
Before performing vacuum drying, make sure that all the outdoor unit stop
valves are firmly closed.
1. Mixing of pump lubricant with compressor oil could cause compressor
malfunction and a one-way valve should therefore be used to prevent vacuum
pump lubricant seeping into the piping system. 2. Using a vacuum pump with a
discharge in excess of 4L/s and a precision level of 0.02mmHg is recommended.
After vacuum drying, keep the hoses
connected to the pressure gauge and to
6
the outdoor unit stop valves, in preparation
for refrigerant charging.
4.5 Refrigerant charge
Pipe length is 2~20m. If the pipe length is less than 10m, there is no need to
add additional refrigerant charge. If the pipe length is more than 10m, adding
additional refrigerant charge is necessary, and the rule is 20g/m for the
additional pipe.
14
5 ELECTRICAL CONNECTION
CAUTION
The heat pump please use stabili ed voltage supply.
rated voltage
. If voltage is not stable,
The external power supply to the heat pump should have ground wiring, which is linked to the ground wiring of the unit .
The wiring work should be done by qualified persons according to circuit drawing.
A leakage protector should be installed according to the National Standard concerning electrical appliance.
An all-pole disconnection device which has at least 3mm separation distance in contact points should be installed.
Power supply cords and signal wires should be arranged properly. Separate strong current wire and weak current
wire, meanwhile they can’t
with connection pipe and valve.
Power supply with a leakage protector should be installed in a water-proof place inside the room.
Don’t do cross connection between 2 wires and signal wires must be shielded.
When power supply cord parallels with controlling wire, please put the wires
to corresponding wire pipe and leave proper spac between wires.
When selecting power supply cords, please refer to to the National Standard
and this manual, power supply used outdoor should not lighter than NO.57 wire
in IEC 60245.
If power supply cord is damaged, to avoid danger, it must be replaced by
professional person.
Do not turn on the power until you have checked carefully after wiring.
5.1 Power supply 5.1.1 Specification of power supply
Item Model
Power
220-240V ~50Hz
Manual switch(A)
Capacity 20
Fuse 1 15
Leakage protector
30mA below 0.1 sec
Table 5-1
Max. E-heater Power(W)
00 00
15
5.2 Water tank temperature sensor installation Connect the water tank
temperature sensor wire connector to the outdoor unit T5L connector.
Water tank temperature sensor T5L
T5L
PCB
Fig.5-1
5.3
& A
UX power connection NOTE
If the water tank has the electric auxiliary heating AUX function, please follow the steps below to connect the electric auxiliary heating power cord.
1.Remove the protective cover of the electric control box on the right side of the outdoor unit.
Fig.5-2 2. Connect the electric auxiliary heating power line on the water tank
to the corresponding port on the terminal block.
Terminal block
Fig.5-3
16
3.Outdoor unit power supply.
1 2
1 0 o o
o oo ooo
Terminal block
3
4
L GND
16A
N
Power supply
E-heater
1. Electric counter 2. Global overcurrent and leakage circuit breaker 3. Electric leakage circuit breaker 4. Overcurrent circuit breaker
Fig.5-4
CAUTION
A leakage protector must be installed on power supply box outside the unit
according to the figure above. Power supply with leakage protector must be
installed inside or installed in the place that can satisfy water-proof
requirements. This unit can be started only if it is grounded reliably.
5.4 Dial code definitions NOTE
The picture shown is for reference only, actual product may vary.
means 0, means 1.
S1-1 S1-2 S1-3 S2-1
S2-2 S2-3
0 Default
1 2 3
1
Reserve
0 Without electric auxiliary heater
1 2 3
1
With electric auxiliary heater
0 Default
1 2 3
1
Reserve
0 Default
1 2 3
1
Reserve
00 Default
01 Reserve
1 2 3 10 Reserve
11 Reserve
Table 5-2
17
6 CHECK
NOTE
Before switching on the unit, read following recommendations: When the
installation and parameter setting are completed, cover all the sheet metal of
the unit well. The unit should be maintained by professionals.
If the whole unit failed or in protection, the panel will display the corresponding code; when more than one failure or protection occurs, the order of failure protection will display. When checking, the number is displayed first, then the content. Press check button, you can go over parameters of the whole unit, the following table shows sequence of check:
No.
Display content
0
Normal display
Table 6-1
Instructions
“dF”—-Defrosting “dC”—-Refrigerant recovering “0”—-When being shut down “__”
Temperature of water tank—- When operating or standby
1
Running mode
“3”—-Water heating
2
Running air speed
3
T3 temp. value
“F0” —-Shut down fan “F1” —-Low speed “F3″—- High speed
4
T4 temp. value
5
T5L temp. value
6
Th temp. value
7
Tp temp. value
8
Current
9
EEV opening degree
Actual opening=display value×8
10
T5s setting temperature
11
Td setting auto start temp of auxiliary E-heater
12
Trdh setting booting return difference temp.
13
The third to last error
14
Penultimate error
15
The last error
16
Software version
Actual version
17
Check finished
Display”- -”
18
7 OPERATIONS AND PERFORMANCES
CAUTION
Please cut off the manual switch power when unit fails. Do not restart until
problems are solved.
Characteristics of water heating 3 minute protection Restart or open manual switch after the unit has been shut down within a short time. Unit will not start immediately until 3 minutes later, because of the self-protect function of the compressor.
During operation, if outdoor temperature is higher than normal, the fan motor will run at low air volume or stop running.
efrosting function
heating operation
– In case of frosting during heating operation, to prevent the heating efficiency from decreasing, defrosting operation will turn on automatically (Approx. 2~7 minutes) .
– In the process of defrosting operation, the unit fan motor will stop running.
otection device
– When protection device operate , though the unit stops, the operating indicator o wire control will
blink.
– When protection device operates, indicator will display malfunction code (unit).
– Protection device will act when the following circumstances occur:
Air inlet or outlet are blocked.
Voltage is a little higher or lower compare to the voltage range (Exceeding the range of -10%~10 of 230V )
Start the unit after a long period out of service
Start up the unit after
out of service for a long period,
flow out from tap. is a normal phenomenon, please
,
disappear .
About power failure
– In case power failure during the unit working, please stop all operating actions.
– At the next startup after power failure, the RUN indicator user.
wire controller will blink slowly for several seconds not
About RCCB
must use RCCB lease install an RCCB between power supply and the
unit. In case the
unit cannot act but not attribute to power failure, please check these RCCB switches at first. Before operate the RCCB,
please ensure that the user installing switch is break off.
19
8 MAINTENANCE 8.1 Confirmation before running
- Make sure whether ground wire is broken or fall off. 2) Turn on power supply switch for 12 hours before running.
8.2 Troubleshooting when abnormal situation happens
Before asking for serving or repairing, check the following points:
Non-mechanical malfunction
Water
from safety valve pressure relief opening
– When water heating, cold water will expand when heated, water Do not block it for safety consideration.
is normal.
– If a large amount of water flows, it means safety valve
. Stop using and replace safety valve.
Long period for heating a tank of water
– In winter, water heating efficiency will decrease because of low ambient temperature. It will take longer
heating
.
water
– If customer needs to use hot water, please start the uni in advance.
Need to check
Automatically start or stop
– Whether timer
.
When not working
– Check whether power on.
– Whether manual switch is on.
– Whether fuse blow .
– Whether protection device
(indicator lights).
– Whether
( peration lamp lights.)
If heating effect is not good
– Whether air outlet and inlet has been blocked.
CAUTION
If the following situation happens, please stop running and cut off power supply manually and service center.
contact with the dealer or
– ON/OFF operation is ineffective.
– Fuse or RC trips frequently
Before leave unused for a long time, please complete the following items:
– Drain water from tank and pipes, close all valve bodies.
After leave unused for a long time, please check the following items:
– Check air inlet and outlet of the unit to see whether they are blocked. Clean immediately when they are blocked.
– Check whether water pipes, valves have been damages or blocked. Whether there’s water leakage in joints, replace them when water leaks.
– It is suggest to inspect anode protection material every half year. If it has been exhausted, please replace it with a new one.
8.3 After-sale service
In case of malfunctions, please cut off the power switch and contact after-
sale service centre or technical service department
8.4 Important information for the used refrigerant
This product has the fluorinated gas, it is forbidden to release to air. Refrigerant type: R134a; Volume of GWP: 1430; GWP=Global Warming Potential
Table 8-1
Factory charge
Refrigerant/kg
tonnes CO2 equivalent
0.9
1.29
20
NOTE
Frequency of Refrigerant Leak Checks:
- For equipment that contains fluorinated greenhouse gases in quantities of 5 tonnes of CO2 equivalent or more,but of less than 50 tonnes of CO2 equipment,at least every 12 months, or where a leakage detection system is installed, at least every 24 months.
- For equipment that contains fluorinated greenhouse gases in quantities of 50 tonnes of CO2 equivalent or more,but of less than 500 tonnes of CO2 equipment,at least every six months, or where a leakage detection system is installed, at least every 12 months.
- For equipment that contains fluorinated greenhouse gases in quantities of 500 tonnes of CO2 equivalent or more,at least every three months, or where a leakage detection system is installed,at least every six months.
- Non-hermetically sealed equipment charged with fluorinated greenhouse gases shall only be sold to the end user where evidence is provide that the installation is to be carried out by an undertaking certified person.
- Only certificated person is allowed to do installation, operation and maintenance.
8.5 Water quality limitations NOTE
If the water quality does not meet the requirements in the table below, please
contact the supplier for advice.
PH Value 6.5-8.0
Total Hardness 50ppm
Table 8-2 Electrical Conductivity
)
Sulphate Ion
Silicon
Iron Content
<50ppm Sulfide Ion
None
<30ppm Chloride Ion
<50ppm
<0.3ppm Ammonia Ion
None
Sodium Ion
Calcium Ion
None
<50ppm
21
9 ERROR CODE SHOOTING TABLE
Error Code E2 E4 E5 E6 E9 EA EF HP HC P1 P2 P4 PA bA F2 F6 db
Explanation Communication error Water tank temperature sensor error (T5L) ODU heat exchanger temperature sensor error (T3) ODU ambient temperature sensor error (T4) Suction temperature sensor error (Th) Discharge temperature sensor error (Tp) Clock chip error Smart Grid signal error E-heater error (Current is less than 2A when e-heater operating) High pressure protection Over load protection of fixed compressor High discharge temperature (Tp) protection Low water temperature protection The ambient temperature exceeds the declared range (not an error) Low super-heat of discharge protection Electic expansion valve joint fault Anti-freezing operating (not an error) for some unit
Table 9-1
22
10. Warranty
The warranty applies to Midea heat pumps installed in a single family dwelling
only and is provided only to those acquiring the heat pump as consumers within
the meaning of the Australian Consumer Law. The terms of the warranty are
effective from the date the heat pump is installed. The validity of the
product warranty period may be verified by requesting a copy of the
certificate of compliance that accompanied the installation. A compliance
certificate is mandatory in all Australian states.
10.1 Warranty period
1. This warranty warrants that the following heat pump components will remain
free of defects for the specified periods from the date of installation: ·
Tank Cylinder – 5 years product / 3 years labour. · Compressor – 3 years
product / 1 year labour. · All other components supplied, including valves,
elements, thermostats and sacrificial anodes – 1 year.
2. No warranty is given in relation to components not supplied, for example
tempering valves and cold water valve assemblies used by installers.
3. Subject to the conditions and exclusions specified in this warranty, the
owner may have the defective heat pump component repaired or replaced covered
under this warranty as soon as reasonably practicable after the consumer has
reported the defect.
10.2 Consumers to register the warranty
For efficient processing of making a claim under this warranty, consumers are
encourage to complete all details on the following warranty form and send it
to the address indicated on the form. Alternatively warranty can be registered
via the web address indicated on the form.
10.3 Procedure to make a warranty claim
Upon discovering a suspected defect, consumers should immediately report the
suspected defect:
· To the installer or supplier, if the suspected defect arises as a result of
the installation of the heat pump or relates to any components not covered by
this warranty.
· To Chromagen during the relevant warranty period, if the suspected defect
relates to any components covered by this warranty.
Please Note: To successfully make a warranty claim, Chromagen must be advised
of the Heat Pumps serial number. Failure to advise serial number, may delay
the service request and or
prevent the service request from being processed.
10.4 Specific exclusions
To the extent permitted by law Chromagen does not accept liability under this
warranty:
· If any component of the heat pump has been installed, repaired, repositioned
or modified by a person other than an appropriately qualified person approved
by Chromagen in accordance with the installation and maintenance instructions
and relevant local and statutory requirements;
· For loss or damage caused by a fault or defect in the installation of the
heat pump;
· If corrosion has occurred because the anode has not been changed in
accordance with the installation & maintenance guide;
· If a cold water expansion valve, check valve and strainer is not fitted in
areas where mains pressure is likely to exceed 500kPa;
· For any damage arising as a result of an accident, act of God or other
circumstances beyond Chromagen’s control;
· If the inner cylinder has collapsed as a result of an incorrect filling
and/or commissioning procedure;
· For components not supplied by Chromagen that are used in the installation
of the heat pump water heater e.g. tempering valves, cold water valve
assemblies, etc.
· For extended or implied warranties not formally provided by Chromagen;
· For external labour or equipment costs (e.g. cranes and lifting devices)
required for repairs;
· For costs incurred for rectifying faults (or perceived faults) not directly
attributed to the heat pump water heater;
· For travel costs of service agents that exceed 30 kilometres;
· For all consequential loss or damage arising from defects that can lawfully
be excluded;
· For any other issues not directly attributable to defects in components
supplied by Chromagen including: (a) Damage caused by incorrect commissioning;
(b) Leakage from valves not supplied by Chromagen; (c) Leakage from the
pressure temperature relief valve where the water pressure or temperature
exceeds the limits specified in the installation and maintenance instructions;
(d) Water hammer; (e) External rust on the storage tank; (f) Insufficient hot
water because: (i) the consumer refuses to use the auxiliary booster (ii) of
an incorrectly set or faulty tempering or mixing valve; (iii) of faulty or
incomplete installation (iv) the water heater is too small for its required
purpose (v) of insufficient water flow as a result of “water saving” tap-ware
or appliances (vi) of blown fuses, “tripped” electrical switches or inadequate
household electrical wiring; (vii) insufficient water flow caused by debris
accumulating in water strainer.
10.5 Important Note
The benefits conferred by this warranty are in addition to any other rights
and remedies available to the consumer under a law in relation to the goods or
services to which the warranty relates.
23
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>