Danfoss FA11 iC7-Automation In Back Out Back Cooling Kit Installation Guide Product Information
- June 1, 2024
- Danfoss
Table of Contents
FA11 iC7-Automation In Back Out Back Cooling Kit
Product Information
Specifications
-
Product Name: In-back/Out-back Cooling Kit for FA11-FA12 iC7
Series Frequency Converters -
Compatible with: FA11 and FA12 frequency converters mounted in
Rittal TS8 cabinets with widths of 600 mm (24 in) or 800 mm (32
in) -
Kit Numbers: 176F4057 (for FA11) and 176F4058 (for FA12)
Product Usage Instructions
Installation
Safety Information
NOTICE: Only qualified, Danfoss authorized
personnel are allowed to install the parts described in these
installation instructions.
-
Disassembly and reassembly of the frequency converter must be
done in accordance with the service guide. -
Use the standard fastener torque values from the service guide,
unless the torque value is specified in these instructions.
WARNING: Discharge Time (40 Minutes)
-
Stop the motor.
-
Disconnect AC mains and remote DC-link power supplies,
including battery back-ups, UPS, and DC-link connections to other
frequency converters. -
Wait 40 minutes for the DC-link capacitors to discharge
fully. -
Before performing any service or repair work, measure the
voltage level to verify that the capacitors are fully
discharged.
WARNING: Electrical Shock Hazard
-
Only use qualified electricians for the installation.
-
Disconnect the frequency converter from all power sources
before installation or service. -
Treat the frequency converter as live whenever the mains
voltage is connected. -
Follow the guidelines in these instructions and local
electrical safety codes.
Items Supplied
The following parts are contained in the kit:
Item | Description |
---|---|
Top cover | Cover for the top of the frequency converter |
Top gasket | Gasket for sealing the top cover |
Bottom cover | Cover for the bottom of the frequency converter |
FAQ
Q: Can I install this cooling kit myself?
A: No, only qualified, Danfoss authorized personnel are allowed
to install the parts described in these installation
instructions.
Q: How long should I wait for the capacitors to discharge
fully?
A: Wait 40 minutes after power has been removed before
performing any service or repair work to ensure the capacitors are
fully discharged.
Installation Guide
In-back/Out-back Cooling Kit for FA11-FA12
iC7 Series Frequency Converters
1 Overview
1.1 Description
The in-back/out-back cooling kit fits FA11 and FA12 frequency converters
mounted in Rittal TS8 cabinets with widths of 600 mm (24 in) or 800 mm (32
in). When the kit is installed, air flows into the lower back duct and out
through the upper back duct of the frequency converter. See Illustration 1.
1
e30bf963.10
4
2
3
Illustration 1: Direction of Airflow with Kit Installed
1
Top cover
2
Cabinet
3
Pedestal
5 6
4
Cooling back channel
5
Air flow direction
6
Bottom cover
1.2 Kit Numbers
Use these instructions with the following kits.
Table 1: In-back/Out-back Cooling Kits
Number
Kit description
176F4057 176F4058
In-back/out-back cooling kit for FA11 frequency converter In-back/out-back cooling kit for FA12 frequency converter
Danfoss A/S © 2022.03
AN361428862578en-000101 / 136R0249 | 1
In-back/Out-back Cooling Kit for FA11-FA12 Installation Guide
1.3 Items Supplied
The following parts are contained in the kit. Table 2: Items Supplied in In-
back/Out-back Cooling Kits
Item Top cover Top gasket Bottom cover Bottom gasket Back duct 6-hole gasket
8-hole gasket Clip-on nut M5x14 screw M5x18 screw M6x12 screw
Quantity 1 1 1 1 2 4 4 16 810 16 12
Overview
2 | Danfoss A/S © 2022.03
AN361428862578en-000101 / 136R0249
In-back/Out-back Cooling Kit for FA11-FA12 Installation Guide
Installation
2 Installation
2.1 Safety Information
NOTICE
QUALIFIED PERSONNEL Only qualified, Danfoss authorized personnel are allowed
to install the parts described in these installation instructions.
– Disassembly and reassembly of the frequency converter must be done in
accordance with the service guide. – Use the standard fastener torque values
from the service guide, unless the torque value is specified in these
instructions.
WARNING
DISCHARGE TIME (40 MINUTES) The frequency converter contains DC-link
capacitors, which can remain charged even when the frequency converter is not
powered. High voltage can be present even when the warning LED indicator
lights are off. Failure to wait 40 minutes after power has been removed before
performing service or repair work can result in death or serious injury.
– Stop the motor. – Disconnect AC mains and remote DC-link power supplies,
including battery back-ups, UPS, and DC-link connections to other
frequency converters.
– Disconnect or lock the motor. – Disconnect any brake option. – Disconnect
any DC connector option. – Wait 40 minutes for the DC-link capacitors to
discharge fully. – Before performing any service or repair work, measure the
voltage level to verify that the capacitors are fully discharged.
WARNING
ELECTRICAL SHOCK HAZARD The frequency converter contains dangerous voltages
when connected to mains voltage. Improper installation, and installing or
servicing with power connected, can cause death, serious injury, or equipment
failure.
– Only use qualified electricians for the installation. – Disconnect the
frequency converter from all power sources before installation or service. –
Treat the frequency converter as live whenever the mains voltage is connected.
– Follow the guidelines in these instructions and local electrical safety
codes.
NOTICE
ELECTROSTATIC DISCHARGE Electrostatic discharge can damage components.
– Ensure electrostatic discharge before touching internal frequency converter
components, for example by touching a groun-
ded, conductive surface or by wearing a grounded armband.
Danfoss A/S © 2022.03
AN361428862578en-000101 / 136R0249 | 3
In-back/Out-back Cooling Kit for FA11-FA12 Installation Guide
2.2 Installation Overview
NOTICE
APPLYING GASKETS This kit contains self-adhesive gaskets to ensure a proper
seal between metal parts.
– Before affixing a gasket, check that the part matches the gasket and that no
holes are covered.
1
Installation
5 6
7 8 9
e30bg242.10
10 2 3 4
11 12
Illustration 2: Overview of In-back/Out-back Cooling Kit 4 | Danfoss A/S © 2022.03
AN361428862578en-000101 / 136R0249
In-back/Out-back Cooling Kit for FA11-FA12 Installation Guide
Installation
1
Cabinet
2
Bottom gasket
3
Bottom cover
4
M5x14 screw
5
Top cover
6
Top gasket
7
Clip-on nut
8
Back duct
9
M5x18 screw
10
6-hole gasket
11
8-hole gasket
12
M6x12 screw
2.3 Creating Vent Openings in the Mounting Plate
To create upper and lower vent openings in the mounting plate, use the
following steps. Use the dimensions in Illustration 3 for 600 mm (24 in)
cabinets, and Illustration 4 for 800 mm (32 in) cabinets. Procedure
1. Drill 6 mounting holes in the back of the frequency converter using the
dimensions in the template. 2. Insert 6 M10 pem self-clinching nuts (not
supplied) in the mounting holes. 3. Cut out the upper and lower vent openings
in the mounting plate using the dimensions in the template.
The openings must match the frequency converter vent openings.
4. Drill 6 screw holes around each vent opening using the dimensions in the
template.
The holes must match the holes in the frequency converter and the inner flange
of the back ducts.
Danfoss A/S © 2022.03
AN361428862578en-000101 / 136R0249 | 5
2X 246 (9.7) 230 (9.1) 206 (8.1) 2X 201 (7.9)
0.0 2X 201 (7.9) 206 (8.1) 230 (9.1) 2X 246 (9.7)
e30bg240.10
In-back/Out-back Cooling Kit for FA11-FA12 Installation Guide
499 (19.7)
6X S-M10-2Z1 7 (0.3)
3 (0.1)
0.0
100 (3.9) 137 (5.3) 158 (6.2) 169 (6.7)
314 (12.3) 332467 ((1123..87))
23 (0.9)
1335 (52.6) 1357 (53.4) 1368 (53.9)
1513 (59.6) 1524 (60.0) 1545 (60.8)
1645 (64.7)
Installation
2X 230 (9.1) 215 (8.5) 0.0 215 (8.5) 2X 230 (9.1)
Illustration 3: Vent Dimensions for Mounting Plate in 600 mm (24 in) Cabinet
6 | Danfoss A/S © 2022.03
AN361428862578en-000101 / 136R0249
In-back/Out-back Cooling Kit for FA11-FA12 Installation Guide
699 (27.5)
6X S-M10-2Z1 7 (0.3)
3 (0.1)
2X 246 (9.7) 230 (9.1) 206 (8.1) E3h 254 (10.0) E4h 2X 201 (7.9) 0.0 2X 201
(7.9) 206 (8.1) E3h 254 (10.0) E4h 230 (9.1) 2X 246 (9.7)
e30bg244.10
Installation
0.0
100 (3.9) 137 (5.3) 158 (6.2) 169 (6.7)
314 (12.3) 326 (12.8) 347 (13.7)
23 (0.9)
1335 (52.6) 1357 (53.4) 1368 (53.9)
1513 (59.6) 1524 (60.0) 1545 (60.8)
1645 (64.7)
2X 230 (9.1) 215 (8.5) E3h 263 (10.4) E4h 0.0 215 (8.5) E3h 263 (10.4) E4h 2X 230 (9.1)
Illustration 4: Vent Dimensions for Mounting Plate in 800 mm (32 in) Cabinet
2.4 Creating Vent Openings in the Backplate
To create upper and lower vent openings in the cabinet backplate, use the
following steps. Use the dimensions in Illustration 5 for 600 mm (24 in)
cabinets, and Illustration 6 for 800 mm (32 in) cabinets. Procedure
1. Cut out the vent openings in the cabinet backplate using the dimensions in
the template.
The openings must match the frequency converter and mounting plate vent
openings. 2. Drill 8 screw holes (6 mm) around each vent opening using the
dimensions in the template.
The holes must match the holes in the frequency converter and in the outer
flange of the back duct.
Danfoss A/S © 2022.03
AN361428862578en-000101 / 136R0249 | 7
244 (9.6) 2X 232 (9.1) 225 (8.9) 2X 218 (8.6) 2X 82 (3.2) 75 (3.0) 2X 68 (2.7)
0.0 2X 68 (2.7) 75 (3.0) 2X 82 (3.2) 2X 218 (8.6) 225 (8.9) 2X 232 (9.1) 244
(9.6)
e30bg241.10
In-back/Out-back Cooling Kit for FA11-FA12 Installation Guide
592 (23.3)
16X Ø 6 (0.2)
18 (0.7)
0.0
185 (7.3) 4X 196 (7.7) 198 (7.8)
392 (15.4) 4X 394 (15.5) 405 (15.9)
1383 (54.4) 1394 (54.9) 1396 (55.0)
1590 (62.6) 1592 (62.7) 1603 (63.1)
Installation
Illustration 5: Vent Dimensions for Backplate in 600 mm (24 in) Cabinet
8 | Danfoss A/S © 2022.03
AN361428862578en-000101 / 136R0249
In-back/Out-back Cooling Kit for FA11-FA12 Installation Guide
792 (31.2)
16X Ø 6 (0.2)
244 (9.6) 2X 232 (9.1) 225 (8.9) 2X 218 (8.6) 2X 82 (3.2) 75 (3.0) 2X 68 (2.7)
0.0 2X 68 (2.7) 75 (3.0) 2X 82 (3.2) 2X 218 (8.6) 225 (8.9) 2X 232 (9.1) 244
(9.6)
e30bg245.10
18 (0.7) 0.0
Installation
185 (7.3) 4X 196 (7.7) 198 (7.8)
392 (15.4) 4X 394 (15.5) 405 (15.9)
1383 (54.4) 1394 (54.9) 1396 (55.0)
1590 (62.6) 1592 (62.7) 1603 (63.1)
Illustration 6: Vent Dimensions for Backplate in 800 mm (32 in) Cabinet
2.5 Installing the Top Cover
To install the top cover, use the following steps. See Illustration 7.
Procedure
1. Remove paper backing from the top gasket to expose the adhesive. 2. Adhere
the top gasket to the underside of the top cover. 3. Remove the M5x14 screws
(T25) surrounding the sides and back of the vent in the top of the frequency
converter.
Retain the screws. FA11 converters have 6 screws; FA12 converters have 7
screws. 4. Loosen 3 M5x12 screws (T25) at the front of the vent in the top
surface of the frequency converter. 5. Slide the edge of the top cover plate
under the 3 loosened screws, positioning the plate over the vent in the top of
the
frequency converter. 6. Secure the top cover plate with the M5x14 screws (T25)
removed previously in step 3.
Torque all screws to 2.3 Nm (20 in-lb).
Danfoss A/S © 2022.03
AN361428862578en-000101 / 136R0249 | 9
In-back/Out-back Cooling Kit for FA11-FA12 Installation Guide
1
2 3 4 5 6
Installation
e30bg162.10
Illustration 7: Installation of the Top Cover
1
M5x14 screw
2
Top cover
3
Top gasket
4
Top vent
5
M5x12 screws (loosened, not removed)
6
Top of frequency converter
2.6 Installing the Bottom Cover
NOTICE
DRAIN OPENING The bottom cover features a drain opening in the middle of the
plate.
– To drain moisture in wet or humid environments, attach nylon tubing with
interior diameter of 8 mm (0.3 in). – To seal the drain in dry environments,
fasten a screw in the drain hole.
To install the bottom cover at the lower end of the cooling back channel, use
the following steps. See Illustration 8. Procedure
1. Remove the paper backing from the bottom gasket. 2. Adhere the gasket to
the upper side of the bottom cover. 3. Position the bottom cover and gasket
over the opening at the lower end of the cooling channel.
10 | Danfoss A/S © 2022.03
AN361428862578en-000101 / 136R0249
In-back/Out-back Cooling Kit for FA11-FA12 Installation Guide
Installation
4. Secure the bottom cover using the M5x14 screws (T25). Torque screws to 2.3
Nm (20 in-lb). FA11 frequency converters require 8 screws, and FA12 frequency
converters require 10 screws.
1 2
e30bg243.10
7
3
8
4
5
6
Illustration 8: Installation of the Bottom Cover
1
Frequency converter
2
Cooling back channel
3
Bottom gasket
4
Bottom cover
5
M5x14 screws
6
Drain hole
7
Mounting plate
8
Cabinet rails
2.7 Mounting the Frequency Converter
To install the mounting plate and frequency converter in the cabinet, use the
following steps. Refer to Illustration 9. Procedure
1. Remove the paper backing from both 6-hole gaskets, exposing the adhesive.
2. Adhere 1 gasket around the vent opening on each side of the mounting plate.
3. Position the mounting plate in the Rittal cabinet, aligning the top
mounting plate hole with the 5th hole from the top of the
cabinet rails.
Check that the pem nuts face the back of the cabinet.
4. Fasten the mounting plate to the cabinet rails with 14 M5x10 thread-
forming screws. 5. Loosely fasten 3 M10 screws (not supplied) into the pem
nuts at the lower end of the mounting plate.
Check that the screws are secure. The base of the frequency converter rests on
the screws.
6. Slightly lean the top of the frequency converter forward and set the
cutouts in the base onto the 3 screws. 7. Slowly push the top of the frequency
converter back against the mounting plate until the top 3 pem nuts line up
with the
holes in the frequency converter. 8. Secure the top of the frequency converter
using 3 M10 screws.
Torque the 6 M10 screws to 19 Nm (170 in-lb).
Danfoss A/S © 2022.03
AN361428862578en-000101 / 136R0249 | 11
In-back/Out-back Cooling Kit for FA11-FA12 Installation Guide
Installation
1 2
e30bg209.10
3 4 5 6
7 8
9 10
Illustration 9: Installation in Cabinet
1
Frequency converter
2
Rittal cabinet
3
Mounting plate
4
Backplate
5
M5 clip-on nut
6
Back duct
7
M6x12 screw
8
M5x18 screw
9
8-hole gaskets
10
6-hole gaskets
2.8 Installing the Backplate and Back Ducts
To attach the cabinet backplate and the upper and lower back ducts, use the
following steps. Procedure
1. Position the cabinet backplate on the rear rails of the cabinet behind the
mounting plate. 2. Secure the backplate to the rails using the existing
fasteners. 3. Slide 8 M5 clip-on nuts over the screw holes surrounding the
upper duct opening in the backplate.
Repeat for the lower duct opening.
4. Remove the paper backing from 1 pair of 8-hole gaskets, exposing the
adhesive. 5. Adhere 1 gasket to the back and 1 to the front of the upper back
duct outer flange.
Repeat for the lower duct.
6. Position each back duct in the hole created for it in the mounting plate
and cabinet backplate.
12 | Danfoss A/S © 2022.03
AN361428862578en-000101 / 136R0249
In-back/Out-back Cooling Kit for FA11-FA12 Installation Guide
7. Fasten the inner flanges of the back ducts with 12 M6x12 screws (T30), 6
screws in each duct. Torque screws to 3.9 Nm (35 in-lb).
8. Fasten the outer flanges of the back ducts with 16 M5x18 screws (T25), 8
screws in each duct. Torque screws to 2.3 Nm (20 in-lb).
Installation
Danfoss A/S © 2022.03
AN361428862578en-000101 / 136R0249 | 13
In-back/Out-back Cooling Kit for FA11-FA12 Installation Guide
Installation
Danfoss A/S Ulsnaes 1 DK-6300 Graasten danfossdrives.com
Any information, including, but not limited to information on selection of
product, its application or use, product design, weight, dimensions, capacity
or any other technical data in product manuals, catalogues descriptions,
advertisements, etc. and whether made available in writing, orally,
electronically, online or via download, shall be considered informative, and
is only binding if and to the extent, explicit reference is made in a
quotation or order confirmation. Danfoss cannot accept any responsibility for
possible errors in catalogues, brochures, videos and other material. Danfoss
reserves the right to alter its products without notice. This also applies to
products ordered but not delivered provided that such alterations can be made
without changes to form, fit or function of the product. All trademarks in
this material are property of Danfoss A/S or Danfoss group companies. Danfoss
and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.
136R0249
14 | Danfoss A/S © 2022.03
M00278
AN361428862578en-000101 / 136R0249