VORTICE CA WE Tertiary Ventilation Centrifugal Instruction Manual
- June 1, 2024
- VORTICE
Table of Contents
VORTICE CA WE Tertiary Ventilation Centrifugal
Product Specifications
- Model: CA WE
- Manufacturing Date: 31/10/2023
Description and Use
The product is designed for specific applications which are outlined in the
instruction manual. It is important to read and understand the instructions
before using the appliance to ensure safe and proper operation.
Safety
Follow all safety guidelines provided in the manual to prevent any damage to
property or personal injury. Failure to follow safety instructions may result
in hazards.
Installation
Proper installation of the appliance is crucial for its efficient functioning. Refer to the installation section in the manual for detailed steps and guidelines on how to install the product correctly.
Wiring Diagrams
Understanding the wiring diagrams is essential for any electrical connections
related to the product. Make sure to follow the diagrams accurately to avoid
any electrical mishaps.
Maintenance / Cleaning
Regular maintenance and cleaning are necessary to prolong the lifespan of the
appliance. The manual provides instructions on how to maintain and clean the
product correctly.
Caution :
this symbol indicates that care must be taken to avoid damaging the appliance
- Do not rest objects on the device.
- Periodically check device conditions. If imperfections are noted, do not use the unit and immediately contact a Vortice-authorized Technical Assistance Centre.
- Promptly contact a Vortice authorised Assistance Centre in the event of unit malfunction and/or failure and request the use of original Vortice spare parts for any repairs.
- If the unit falls or receives a strong blow, immediately have it inspected at a vortice-authorized Technical Assistance Centre.
- Only connect the device to the main supply/electrical outlet if plant/outlet capacity is suitable for its maximum power. If otherwise, immediately seek assistance from a professionally qualified person.
- Switch off the main switch on the system when: a) a malfunction is detected, b) you decide to perform external cleaning maintenance when you decide not to use the device for prolonged periods.
- It is essential to ensure that sufficient air re-enters the room, in order to guarantee product operation. If a combustion-powered, non-air-tight device is installed in the room (water heater, methane stove, etc.), please ensure that air re-entry also guarantees the perfect combustion of said device.
- The unit cannot be used as an activator for water heaters, stoves, etc. nor should it discharge into hot air ducts.
- The unit must be correctly connected to an effective earthing system as foreseen by current electrical safety regulations. If doubts should arise, request careful inspection by qualified personnel.
- The unit must discharge directly outside.
- The air flow to convey (or fumes) must be clean (or rather free of grease, soot, chemical and corrosive substances or explosive and flammable mixtures).
- Never cover or obstruct the unit delivery grille to ensure optimal air passage.
- The electrical specifications correspond to the ones on the data label A (fig.A).
- An omnipolar switch with a contact opening distance of 3 mm or higher should be provided for installation, enabling complete disconnection under overvoltage category III conditions.
- Products equipped with single-phase wiring (M) engines ALWAYS require connection to 220-240V (or only 230V where required) single-phase lines. Any kind of modification shall be considered as product tampering and shall nullify the relative warranty.
- No specific adjustment is necessary as the devices operate at nominal frequencies without a preliminary setting.
Thermal protection devices
The units are equipped with a manual reset thermal protector If the thermal
protector is triggered, please contact qualified personnel or Vortice
authorised Technical Assistance Centre.
If the problem persists after the reset operation, check the electrical system
to which the unit is connected. In this case, please contact a Vortice
authorised Technical Assistance Centre or professionally qualified personnel.
Installation
See Figures 1-10.
The images shown are purely indicative. Their purpose is to illustrate the
main assembly steps for the entire range.
-
IMPORTANT: See the “Wiring Diagrams” paragraph to check the 3 ventilation speeds.
Fig. 8 CAUTION: use the outer opening of the cover only for the passage of a 16 mm diameter tube coming from the fixed system. -
IMPORTANT: the power cable must be of the H03VV-F type, 2×0.75mm2.
Wiring diagrams
See Figure 11.
Connection with the optional device upon request is foreseen to check
ventilation speeds (device not supplied in packaging):
- 11A) Vortice 3-speed selector Code 12.866-12891
IMPORTANT
Vortice guarantees correct product operation and control only when paired with
the Vortice 3-speed selector (Code 12.866-12891).
Other types of connection
Alternatively, other connection diagrams are available, associated to
different control modes (devices provided by the installer).
Connection alternative for new installation
- 11B) Max;
- 11C) Med;
- 11D) Min;
Machine replacement on existing system
Connection without modifications to the electrical system: the same switches as on the existing system will be used.
Maintenance / Cleaning
Fig 12-14.
Important information concerning the environmentally compatible disposal
This product complies with Directive 2012/19/EU on the management of waste
electrical and electronic equipment (WEEE).
The crossed-out wheeled bin symbol on the appliance indicates that, at the end of its useful life, the product must be taken to a specialised company for transport and treatment. This company will take care of the disposal of the various materials making up the product and their subsequent proper recycling.
Alternatively, the manufacturer of the appliance is obliged to take back the product to be disposed of in exchange for the purchase of an equivalent appliance.
FIGURES
VORTICE S.p.A. reserves the right to make improvements to products at any time and without prior notice.
VORTICE INDUSTRIAL Srl
Via B. Brugnoli, 3
- 37063 – Isola della Scala (VR)
- Tel. +39 045 6631042
- ITALY
- vorticeindustrial.com
- info@vorticeindustrial.com
WARRANTY – OTHER COUNTRIES
The consumer has by law, free of charge, the legal guarantee of conformity with the seller, as described in Directive (EU) 2019/771 in force since January 1, 2022. In EU member countries also refer to local regulations.
References
- Casals Ventilación - Fabricante de Sistemas de Ventilación
- index- Your adventure begins here
- 意大利威特奇集团涡风通风系统(常州)有限公司
- VORTICE LATAM - Aire es Vida
- Vortice ventilation, fans and air conditioners
- Vortice Industrial | Better air for Better life
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>