Midea MSEPB-10CRFN Room Air Conditioner User Manual
- June 1, 2024
- Midea
Table of Contents
- Midea MSEPB-10CRFN Room Air Conditioner
- Specifications
- Product Overview
- FAQs
- SAFETY PRECAUTIONS
- SPECIFICATIONS
- PRODUCTION INSTALLATION
- BEFORE TEST RUN
- DURING TEST RUN
- OPERATION INSTRUCTIONS
- CARE AND MAINTENANCE
- TROUBLESHOOTING
- TRADEMARKS, COPYRIGHTS AND LEGAL STATEMENT
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Midea MSEPB-10CRFN Room Air Conditioner
Specifications
- Model Numbers: MSEPB-10CRFN8, MSEPB-13CRFN8, MSEPB-19CRFN8, MSEPB-25CRFN8, MSEPB-28CRFN8
- Manufacturer: Midea
- Product Type: Room Air Conditioner
- Design and specifications subject to change without notice
Product Overview
The Midea Room Air Conditioner is designed to provide efficient cooling for your space. It comes in multiple models to suit different room sizes. The product features a sleek design and user-friendly controls for easy operation.
Product Installation
Install Your Indoor Unit
Follow the step-by-step instructions provided in the manual to install the indoor unit of the air conditioner. Ensure proper placement and secure mounting for optimal performance.
Install Your Outdoor Unit
Refer to the installation guide to set up the outdoor unit of the air conditioner. Place it in a suitable location with proper ventilation and connections to the indoor unit.
Refrigerant Piping Connection
Connect the refrigerant piping as per the specifications outlined in the manual. Use appropriate tools and techniques to prevent leaks and ensure efficient cooling.
Air Evacuation
Prior to operation, ensure proper air evacuation to remove any trapped air in the system. Follow the guidelines provided to complete this process safely.
Electrical And Gas Leak Checks
Before turning on the unit, conduct checks for electrical connections and gas leaks. Any abnormalities should be addressed by a qualified technician to prevent hazards.
Test Run
Once installation is complete, perform a test run of the air conditioner to ensure all functions are working correctly. Monitor for any unusual noises or issues during this test.
Packing And Unpacking The Unit
If relocating or storing the air conditioner, follow the instructions for proper packing and unpacking to prevent damage to the unit.
Operation Instructions
Indoor Unit Display
Familiarize yourself with the display panel on the indoor unit to understand the different indicators and settings available for controlling the air conditioner.
Remote Control Operation
Use the remote control provided to adjust settings such as temperature, fan speed, and mode of operation. Ensure proper battery installation and clear line of sight between the remote and unit.
Care and Maintenance
Regular maintenance is essential for optimal performance of your air conditioner. Refer to the care instructions in the manual for cleaning filters, checking components, and scheduling professional servicing.
Troubleshooting
If you encounter any issues with your air conditioner, refer to the troubleshooting section of the manual for common problems and solutions. Contact customer support if needed.
FAQs
- Q: What should I do if my air conditioner stops cooling?
- A: Check the filters for dirt buildup, ensure proper airflow around the unit, and verify that all settings are correct. If the issue persists, contact a technician for further inspection.
- Q: How often should I clean the filters?
- A: It is recommended to clean the filters every 2-4 weeks depending on usage. Clogged filters can reduce efficiency and airflow.
- Q: Can I use my air conditioner in a room with high humidity?
- A: The air conditioner is suitable for use in moderately humid environments. Avoid excessively damp areas to prevent condensation issues.
“`
Room Air Conditioner
USER MANUAL
MODEL NUMBER: MSEPB-10CRFN8 MSEPB-13CRFN8 MSEPB-19CRFN8 MSEPB-25CRFN8 MSEPB-
28CRFN8
Warning notices: Before using this product, please read this manual and SAFETY
MANUAL(if any)carefully and keep it for future reference. The design and
specifications are subject to change without prior notice for product
improvement. Consult with your dealer or manufacturer for details. The diagram
above is just for reference. Please take the appearance of the actual product
as the standard.
THANK YOU LETTER
Thank you for choosing Midea! Before using your new Midea product, please read
this manual thoroughly to ensure that you know how to operate the
SAFETY PRECAUTIONS
It’s really important you read Safety Precautions Before Operation and
Installation Incorrect installation due to ignoring instructions can cause
serious damage or injury. The seriousness of potential damage or injuries is
classified as either a WARNING or CAUTION.
Explanation of Symbols
Warning of electrical voltage This symbol indicates that there is a danger to
life and health of persons due to voltage. Warning The signal word indicates a
hazard with a medium level of risk which, if not avoided, may result in death
or serious injury.
Caution The signal word indicates a hazard with a low degree of risk which, if
not avoided, may result in minor or moderate injury.
Attention The signal word indicates important information (e.g. damage to
property), but not danger. Observe instructions This symbol indicates that a
service technician should only operate and maintain this appliance in
accordance with the operating instructions.
Read these operating instructions carefully and attentively before
using/commissioning the unit and keep them in the immediate vicinity of the
installation site or unit for later use!
WARNING
This appliance can be used by children aged from 8 years and above and persons
with reduced physical, sensory or mental capabilities or lack of experience
and knowledge if they have been given supervision or instruction concerning
use of the appliance in a safe way and understand the hazards involved.
Children shall not play with the appliance. Cleaning and user maintenance
shall not be made by children without supervision(European Union countries).
This appliance is not intended for use by persons(including children) with
reduced physical, sensory or mental capabilities, or lack of experience and
knowledge, unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety. Children should
be supervised to ensure that they do not play with the appliance.
02
WARNING FOR PRODUCT USE
If an abnormal situation arises (like a burning smell), immediately turn off
the unit and disconnect the power. Call your dealer for instructions to avoid
electric shock, fire or injury.
Do not insert fingers, rods or other objects into the air inlet or outlet.
This may cause injury, since the fan may be rotating at high speeds.
Do not use flammable sprays such as hair spray, lacquer or paint near the
unit. This may cause fire or combustion.
Do not operate the air conditioner in places near or around combustible gases.
Emitted gas may collect around the unit and cause explosion.
Do not operate your air conditioner in a wet room such as a bathroom or
laundry room. Too much exposure to water can cause electrical components to
short circuit.
Do not expose your body directly to cool air for a prolonged period of time.
Do not allow children to play with the air conditioner. Children must be
supervised
around the unit at all times. If the air conditioner is used together with
burners or other heating devices,
thoroughly ventilate the room to avoid oxygen deficiency. In certain
functional environments, such as kitchens, server rooms, etc., the use of
specially designed air-conditioning units is highly recommended.
ELECTRICAL WARNINGS
Only use the specified power cord. If the power cord is damaged, it must be
replaced by the manufacturer, its service agent or similarly qualified persons
in order to avoid a hazard.
The product must be properly grounded at the time of installation, or
electrical shock may occur.
For all electrical work, follow all local and national wiring standards,
regulations, and the Installation Manual. Connect cables tightly, and clamp
them securely to prevent external forces from damaging the terminal. Improper
electrical connections can overheat and cause fire, and may also cause shock.
All electrical connections must be made according to the Electrical Connection
Diagram located on the panels of the indoor and outdoor units.
All wiring must be properly arranged to ensure that the control board cover
can close properly. If the control board cover is not closed properly, it can
lead to corrosion and cause the connection points on the terminal to heat up,
catch fire, or cause electrical shock.
Disconnection must be incorporated in the fixed wiring in accordance with the
wiring rules.
Do not pull power cord to unplug unit. Hold the plug firmly and pull it from
the outlet. Pulling directly on the cord can damage it, which can lead to fire
or electric shock.
Do not modify the length of the power supply cord or use an extension cord to
power the unit.
Do not share the electrical outlet with other appliances. Improper or
insufficient power supply can cause fire or electrical shock.
Keep power plug clean. Remove any dust or grime that accumulates on or around
the plug. Dirty plugs can cause fire or electric shock.
If connecting power to fixed wiring, an all-pole disconnection device which
has at least 3mm clearances in all poles, and have a leakage current that may
exceed 10mA, the residual current device(RCD) having a rated residual
operating current not exceeding 30mA, and disconnection must be incorporated
in the fixed wiring ` in accordance with the wiring rules.
03
TAKE NOTE OF FUSE SPECIFICATIONS
The air conditioner’s circuit board (PCB) is designed with a fuse to provide
overcurrent protection. The specifications of the fuse are printed on the
circuit board , such as : T3.15AL/250VAC, T5AL/250VAC, T3.15A/250VAC,
T5A/250VAC, T20A/250VAC, T30A/250VAC,etc. NOTE: For the units with R32
refrigerant , only the blast-proof ceramic fuse can be used.
UV-C lamp(Applicable to the unit contains an UV-C lamp only)
This appliance contains a UV-C lamp. Read the maintenance instructions before
opening the appliance. Do not operate UV-C lamps outside of the appliance.
Appliances that are obviously damaged must not be operated. Unintended use of
the appliance or damage to the housing may result in the
escape of dangerous UV-C radiation. UV-C radiation may, even in small doses,
cause harm to the eyes and skin. Before opening doors and access panels
bearing the ULTRAVIOLET RADIATION hazard symbol for the conducting USER
MAINTENANCE, it is recommended to disconnect the power. The UV-C lamp can not
be cleaned, repaired and replaced. UV-C BARRIERS bearing the ULTRAVIOLET
RADIATION hazard symbol should not be removed.
WARNING
This appliance contains an UV emitter. Do not stare at the light source.
WARNINGS FOR PRODUCT INSTALLATION
Installation must be performed by an authorized dealer or specialist.
Defective installation can cause water leakage, electrical shock, or fire.
Installation must be performed according to the installation instructions. (In
North America, installation must be performed in accordance with the
requirement of NEC and CEC by authorized personnel only). Improper
installation can cause water leakage, electrical shock, or fire.
Contact an authorized service technician for repair or maintenance of this
unit. This appliance shall be installed in accordance with national wiring
regulations.
Only use the included accessories, parts, and specified parts for
installation. Using non-standard parts can cause water leakage, electrical
shock, fire, and can cause the unit to fail.
Install the unit in a firm location that can support the unit’s weight. If the
chosen location cannot support the unit’s weight, or the installation is not
done properly, the unit may drop and cause serious injury and damage.
Install drainage piping according to the instructions in this manual. Improper
drainage may cause water damage to your home and property.
For units that have an auxiliary electric heater, do not install the unit
within 1 meter (3 feet) of any combustible materials.
Do not install the unit in a location that may be exposed to combustible gas
leaks. If combustible gas accumulates around the unit, it may cause fire.
Do not turn on the power until all work has been completed. When moving or
relocating the air conditioner, consult experienced service
technicians for disconnection and reinstallation of the unit. How to install
the appliance to its support, please read the information for details
in “indoor unit installation” and “outdoor unit installation” sections .
04
CAUTION
Turn off the air conditioner and disconnect the power if you are not going to
use it for a long time.
Turn off and unplug the unit during storms. Make sure that water condensation
can drain unhindered from the unit. Do not operate the air conditioner with
wet hands. This may cause electric shock. Do not use device for any other
purpose than its intended use. Do not climb onto or place objects on top of
the outdoor unit. Do not allow the air conditioner to operate for long periods
of time with doors or
windows open, or if the humidity is very high.
CLEANING AND MAINTENANCE WARNINGS
Turn off the device and disconnect the power before cleaning. Failure to do so
can cause electrical shock.
Do not clean the air conditioner with excessive amounts of water. Do not clean
the air conditioner with combustible cleaning agents. Combustible
cleaning agents can cause fire or deformation.
Note about Fluorinated Gasses(Not applicable to the unit using R290
Refrigerant)
This air-conditioning unit contains fluorinated greenhouse gasses. For
specific information on the type of gas and the amount, please refer to the
relevant label on the unit itself or the “Owner’s Manual – Product Fiche ” in
the packaging of the outdoor unit. (European Union products only).
Installation, service, maintenance and repair of this unit must be performed
by a certified technician.
Product uninstallation and recycling must be performed by a certified
technician. For equipment that contains fluorinated greenhouse gases in
quantities of 5 tonnes
of CO2 equivalent or more, but of less than 50 tonnes of CO2 equivalent, If
the system has a leak-detection system installed, it must be checked for leaks
at least every 24 months. When the unit is checked for leaks, proper record-
keeping of all checks is strongly recommended.
WARNING FOR USING R32/R290 REFRIGERANT
When flammable refrigerant are employed, appliance shall be stored in a well
ventilated area where the room size corresponds to the room area as specifiec
for operation. For R32 frigerant models:
Appliance shall be installed, operated and stored in a room with a floor area
larger than 4m 2.
For R290 refrigerant models, appliance shall be installed, operated and stored
in a room with a floor area larger than:
<=2.6kW units: 17.33m 2 >2.6kW and <=3.5kW units: 25.4m 2 >3.5kW and <=5.2kW
units: 34.67m 2 >5.3kW and <=7.1kW units: 47.33m 2 Reusable mechanical
connectors and flared joints are not allowed indoors.
05
SPECIFICATIONS
Product Model Power source
MSEPB-10CRFN8 MSEPB-13CRFN8 MSEPB-19CRFN8 MSEPB-25CRFN8 MSEPB-28CRFN8 220-240V~50Hz,1Ph
Cooling capacity 9,500(3,000-10,000)Btu/h 12,500(3,500-13,100)Btu/h 19,000(3,500-21,000)Btu/h 24,000(9,550-26,500)Btu/h 28,000(11,100-29,200)Btu/h
Heating capacity
–
–
–
–
–
Rated current
10.0A
11.0A
12.0A
17.5A
17.5A
Rated power input
1,800W
2,000W
2,500W
4,050W
4,050W
Outdoor unit resistance class
IPX4
IP24
06
PRODUCT OVERVIEW
NOTE ON ILLUSTRATIONS:
Illustrations in this manual are for explanatory purposes. The actual shape of
your indoor unit may be slightly different. The actual shape shall prevail.
1
1
2
3
Air-break
2
switch
4
3 4
6
5
7
9
8
10 5
6 7
8
11
(1)
1 Wall Mounting Plate
5 Air Filter(Pull it upwards)
2 Front Panel
6 Drainage Pipe
3 Power Cable(some units)
7 Signal Cable
4 Louver
8 Refrigerant Piping
It would be perfect you had these tools
11
(2)
9 Remote Controller
10
Remote controller Holder (not supplied)
11 Outdoor Unit Power Cable (some units)
Gloves
Screwdriver & wrench
Hammer drill
Core drill
07
Goggles & masks
Vinyl tape
PRODUCTION INSTALLATION
ACCESSORIES
The air conditioning system comes with the following accessories. Use all of
the installation parts and accessories to install the air conditioner.
Improper installation may result in water leakage, electrical shock and fire,
or cause the equipment to fail. The items are not included with the air
conditioner must be purchased separately.
Name of Accessories Q’ty(pc)
Shape
Name of Accessories Q’ty(pc)
Shape
Manual
2-3
Remote controller
1
Drain joint
(for cooling &
1
heating models)
Seal
(for cooling &
1
heating models)
Mounting plate
1
Anchor
Mounting plate fixing screw
5~8 (depending on models)
5~8 (depending on models)
Transfer connector
(19( 3/4in) transfer
to 16( 5/8in). Packed
with the indoor unit,
1
the North America
market 33K hyper heat
unit only. )
FROM EDGE TO HOLE CENTER:50mm
50 2
100 4
mm inch 150 6 RECOMMAND
BUBBLE LEVEL
100 mm 50
4 inch 2 LIQUID
50
100
2
4
GAS
FROM EDGE TO HOLE CENTER:100mm
Battery
2
Remote controller
holder(purchase separately)
1
Fixing screw for
remote controller
holder(purchase
2
separately)
Small Filter
(Need to be installed on the back of main air filter by the authorized
technician while installing the machine)
1~2 (depending on models)
NOTE: In North America market, when 33K hyper heat indoor unit matches with multi-zone condensers, you must purchase pipe with liquid side 9.52( 3/8in) and gas side 16( 5/8in).The transfer connector need to be installed on the indoor unit gas side to meet the pipe size.
Name
Connecting pipe assembly
Magnetic ring and belt (if supplied ,please refer to the wiring diagram to
install it on the connective cable. )
Liquid side Gas side
1 2 3
Shape 6.35( 1/4in) 9.52( 3/8in) 9.52( 3/8in) 12.7( 1/2in) 16( 5/8in) 19( 3/4in)
Quantity(PC)
Parts you must purc hase separately. Consult the dealer about the proper pipe
size of the unit you purchased.
Pass the belt through the hole of the Magnetic ring to fix it on the cable
Varies by model
08
INSTALLATION SUMMARY – INDOOR UNIT
1
Distance from ceiling is determinded
2
by the installation method.
12cm
(4-3/4″)
2.3m (7/8″)
12cm
(4-3/4″)
3
50 2
100 4
mm inch 150 6 RECOMMAND
BUBBLE LEVEL
100 mm 50
4 inch 2 LIQUID
50
100
2
4
GAS
FROM EDGE TO HOLE CENTER:100mm
FROM EDGE TO HOLE CENTER:50mm
Select Installation Location
4
Attach Mounting Plate
5
Determine Wall Hole Position
6
Drill Wall Hole
7
Connect Piping
8
Connect Wiring
(Not applicable for some locations in North America )
Prepare Drain Hose
9
Wrap Piping and Cable
(Not applicable for some locations in North America )
Mount Indoor Unit 09
Install You Indoor Unit
1 Select installation location
NOTE : Prior to installation
Before installing the indoor unit, refer to the label on the product box to
make sure that the model number of the indoor unit matches the model number of
the outdoor unit. The following are standards that will help you choose an
appropriate location for the unit. Proper installation locations meet the
following standards:
Good air circulation
Convenient drainage Noise from the unit will A location at least one
not disturb other people. meter from all other
Distance from ceiling is determinded by the installation method.
electrical devices (e.g., TV, radio, computer)
Firm and solid–the
location will not vibrate
Strong enough to support
the weight of the unit
If no need the back holder to prop up the unit: Finishing the pipe and cable connections before mount the indoor unit on the wall. If the instllation height is limited, 5cm from the ceiling is allowable, but this can lower product performance. To ensure enough space to install and remove the top air filter, keep at least 10cm or more from the ceiling.
Need the back holder to prop up the unit: If connecting pipe and cable with front panel open, the minimum distance from ceiling is 22cm or more, if connecting pipe and cable without front panel(remove it) , the minimum distance from ceiling is 11cm or more.
DO NOT install unit in the following locations:
Near any source of heat, steam, or combustible gas
Near flammable items such as curtains or clothing
Near any obstacle that might block air circulation
Near the doorway
In a location subject to direct sunlight
NOTE: FOR PRODUCT INSTALLATION
If there is no fixed refrigerant piping: While choosing a location, be aware
that you should leave ample room for a wall hole (see Drill wall hole for
connective piping step) for the signal cable and refrigerant piping that
connect the indoor and outdoor units. The default position for all piping is
the right side of the indoor unit (while facing the unit). However, the unit
can accommodate piping to both the left and right.
10
2
Drill wall hole for connective piping
Determine wall hole location
NOTE : The wall hole size
The size of the wall hole is determined by the connective pipes. When the size
of the gas side
connective pipe is 16mm(5/8″) or more, the wall hole should be 90mm(3-9/16″).
For the size of connective pipe is less than 16mm(5/8″), the wall hole should
be 65mm(2-1/2″).
Step 1 Remove the screw that attaches the mounting plate to the back of the
indoor unit.
Screw
Unit: mm(inch)
Horizontal direction ruler
100 mm 50
4 inch 2 LIQUID
50
100
2
4
GAS
BUBBLE LEVEL
50 2 100 4
Vertical direction ruler mm inch
150 6 RECOMMAND
425(16.7)
51(2.0)
Step 2
Secure the mounting plate to the wall with the screws provided. Make sure that
mounting plate is flat against the wall.
pipe hole 65(2.5)
50(1.9)
pipe hole 65(2.5)
120(4.7)
40(1.6)
Indoor unit dimensions(WxH): 795mm(31in)x295mm(11.6in)
490(19.3)
40(1.5)
40(1.6)
pipe hole 65(2.5)
50(1.9)
pipe hole 65(2.5)
95(3.7)
Correct orientation of Mounting Plate
Step 3 Confirm the mounting plate you own. Determine the location of the wall
hole based on the position of the mounting plate. The dotted rectangular box
on the right figure shows the size of your product.
CAUTION: For the convenience of installation, there are bubble level, carved
dimensions on the mounting plate.The Bubble level on the mounting plate can’t
be removed. If it is broken, make sure to clean up the leaking liquid.
Indoor unit dimensions(WxH): 965mm(38in)x322mm(12.7in)
570.7(22.5)
60(2.4)
50(1.9)
70(2.8)
50(1.9)
pipe hole 90(3.54)
Indoor unit dimensions(WxH): 1140mm(44.8in)x370mm(14.6in)
pipe hole 90(3.54)
11
CAUTION
When drilling the wall hole, make sure to avoid wires, plumbing, and other
sensitive components.
Drill wall hole
65mm (2-1/2″)
90mm (3-9/16″)
Using a 65mm (2-1/2″) or 90mm(3-9/16″) core drill(depending on models )
Wall
Indoor
Outdoor
Step 1
Using a 65mm (2.5″) or 90mm(3.54″) core drill(depending on models ), drill a
hole in the wall. Make sure that the hole is drilled at a slight downward
angle, so that the outdoor end of the hole is lower than the indoor end by
about 5mm to 7mm (3/16-5/16″). This will ensure proper water drainage.
5-7mm (3/16-5/16″)
Drill the wall hole
wall hole.
the protective wall cuff
Place the protective wall cuff in the hole.
Step 2
Place the protective wall cuff in the hole. This protects the edges of the
hole and will help seal it when you finish the installation process.
NOTE : FOR CONCRETE OR BRICK WALLS
If the wall is made of brick, concrete, or similar material, drill 5mm-
diameter (0.2in-diameter) holes in the wall and insert the sleeve anchors
provided. Then secure the mounting plate to the wall by tightening the screws
directly into the clip anchors.
12
3 Install refrigerant pipe & drain hose
NOTE
The refrigerant piping is inside an insulating sleeve attached to the back of
the unit. You must prepare the piping before passing it through the hole in
the wall.
Prepare refrigerant piping
Left-hand side
Right-hand side
Knock-out Panel on the left & right side
needle nose pliers
Knock-out Panel(cut depending on the actual size needed)
Left rear
Right rear
Four angles to exit the piping
Step 1
Based on the position of the wall hole relative to the mounting plate, choose
the side from which the piping will exit the unit. You have four options for
the exit direction of the piping.
NOTE ON PIPING CONNECTING In some locations of US, a conduit tube must be used
to connect the cable. To ensure an enough space for the pipes running and the
machine is against the wall after installation, It is recommended to attach
the drain hose to the right-hand side (when you’re facing the back of the
unit). When choose Left-hand side or Right-hand side piping, please make sure
that the pipes come out horizontally so as not to affect the lower panel
installation.
If need to cut the big size plastic panel, cut as shown above.
Step 2
If the wall hole is behind the unit, keep the knock-out panel in place. If the
wall hole is to the side of the indoor unit, remove the plastic knock-out
panel from that side of the unit.Use needle nose pliers if the plastic panel
is too difficult to remove by hand.
Step 3 Use the holder at the back of the unit to prop up the unit, giving you
enough room to connect the refrigerant piping, signal cable, and drain hose.
Step 4
connect the indoor unit’s refrigerant piping to the connective piping that
will join the indoor and outdoor units. Refer to the Refrigerant Piping
Connection section of this manual for detailed instructions.
CAUTION
Be extremely careful not to dent or damage the piping while bending them away
from the unit. Any dents in the piping will affect the unit’s performance.
13
If refrigerant piping is already embedded in the wall, do the following:
30-50mm 1-3/16~2in
30-50mm 1-3/16~2in
Move to left or right
Open the cover and unscrew the screw
Model A
Open the cover and unscrew the screws
Unscrew the screws
Model B
NOTE : UNIT IS ADJUSTABLE
Keep in mind that the hooks on the mounting plate are smaller than the holes
on the back of the unit. If you find that you don’t have ample room to connect
embedded pipes to the indoor unit, the unit can be adjusted left or right by
about 30-50mm (1.18-1.96in), depending on the model.
Open and fix the position of the panel, then, open the covers of the two lock
blocks, unscrew the screw showed in the picture (Model A & Model B), then hold
both sides of the lower panel in the place marked “PULL”, pull it upwards to
release the buckles, then take the lower panel down.
Use the holder at the back of the unit to prop up the unit, giving you enough
room to connect the refrigerant piping, signal cable, and drain hose.
Connect drain hose and refrigerant piping (refer to Refrigerant Piping
Connection section of this manual for instructions).
Keep pipe connection point exposed to perform the leak test (refer to
Electrical Checks and Leak Checks section of this manual).
After the leak test, wrap the connection point with insulation tape.
Release the holder that is propping up the unit.
Using even pressure, push down on the bottom half of the unit. Keep pushing
down until the unit snaps onto the hooks along the bottom of the mounting
plate.
Use the holder at the back of the unit against on the mounting plate to prop
up the unit
14
Connect drain hose
Drain hose
vinyl tape
Connecting cable
Drain hose
Gas side piping
Liquid side piping
Make sure the drain hose is at the bottom
Drain pipe
Vinyl tape(narrow)
Drain pipe extension
Step 1
The drain hose can be attached to the left or right side. To ensure proper
drainage, attach the drain hose on the same side that your refrigerant piping
exits the unit. Attach drain hose extension (purchased separately) to the end
of drain hose.
Wrap the connection point firmly with Teflon tape to ensure a good seal and to
prevent leaks.
For the portion of the drain hose that will remain indoors, wrap it with foam
pipe insulation to prevent condensation.
Remove the air filter and pour a small amount of water into the drain pan to
make sure that water flows from the unit smoothly.
NOTE ON DRAIN HOSE PLACEMENT
Make sure to arrange the drain hose according to the following figures.
CORRECT
Make sure there are no kinks or dent in drain hose to ensure proper drainage.
NOT CORRECT
Kinks in the drain hose will create water traps.
NOT CORRECT
Kinks in the drain hose will create water traps.
NOT CORRECT
Do not place the end of the drain hose in water or in containers that collect
water. This will prevent proper drainage.
CAUTION
PLUG THE UNUSED DRAIN HOLE
To prevent unwanted leaks you must plug the unused drain hole with the rubber
plug provided.
15
4 Electrical work preparation
WARNING
BEFORE PERFORMING ANY ELECTRICAL WORK, READ THESE REGULATIONS BEFORE
PERFORMING ANY ELECTRLCAL OR WIRING WORK, TURN OFF
THE MAIN POWER TO THE SYSTEM.
1. All wiring must comply with local and national electrical codes,
regulations and must be installed by a licensed electrician.
2. All electrical connections must be made according to the Electrical
Connection Diagram located on the panels of the indoor and outdoor units.
3. If there is a serious safety issue with the power supply, stop work
immediately. Explain your reasoning to the client, and refuse to install the
unit until the safety issue is properly resolved.
4. If connecting power to fixed wiring, a switch or circuit breaker that
disconnects all poles and has a contact separation of at least 1/8in (3mm)
must be incorporated in the fixed wiring. The qualified technician must use an
approved circuit breaker or switch.
5. Only connect the unit to an individual branch circuit outlet. Do not
connect another appliance to that outlet.
6. Make sure to properly ground the air conditioner.
7. Every wire must be firmly connected. Loose wiring can cause the terminal
to overheat, resulting in product malfunction and possible fire.
8. Do not let wires touch or rest against refrigerant tubing, the compressor,
or any moving parts within the unit.
9. To avoid getting an electric shock, never touch the electrical components
soon after the power supply has been turned off. After turning off the power,
always wait 10 minutes or more before you touch the electrical components.
10. Power voltage should be within 90-110% of rated voltage. Insufficient
power supply can cause malfunction, electrical shock, or fire.
WARNING
All wiring must be performed strictly in accordance with the wiring diagram
located on the back of the Indoor Unit’s front panel.
Connect signal and power cables
The signal cable enables communication between the indoor and outdoor units.
You must first choose the right cable size before preparing it for connection.
Cable Types(Not applicable for North America) · Indoor Power Cable (if
applicable):
H05VV-F or H05V2V2-F · Outdoor Power Cable: H07RN-F or H05RN-F
· Signal Cable: H07RN-F
Minimum Cross-Sectional Area of
Power and Signal Cables (For reference)
Rated Current of Appliance (A)
3 and 6 > 6 and 10 > 10 and 16 > 16 and 25 > 25 and 32 > 32 and 40
Nominal Cross-Sectional Area (mm )
0.75 1
1.5 2.5
4 6
CHOOSE THE RIGHT CABLE SIZE
The size of the power supply cable, signal cable, fuse, and switch needed is
determined by the maximum current of the unit. The maximum current is
indicated on the nameplate located on the side panel of the unit. Refer to
this nameplate to choose the right cable, fuse, or switch.
DO NOT MIX UP LIVE AND NULL WIRES This is dangerous, and can cause the air conditioning unit to malfunction.
16
1. Open and fix the position of the panel, then, open the covers of the two
lock blocks, remove the screw , then hold both sides of the lower panel in the
place marked “PULL”, pull it upwards to release the buckles, then take the
lower panel down(please refer to Page 14).
2. Open the wire box cover on the right side of the unit. This will reveal
the terminal block.
3. Unscrew the cable clamp below the terminal block and place it to the side.
4. Facing the back of the unit, remove the plastic panel on the bottom left-
hand side.
5. Feed the signal wire through this slot, from the back of the unit to the
front.
6. Facing the front of the unit, connect the wire according to the indoor
unit’s wiring diagram, connect the u-lug and firmly screw each wire to its
corresponding terminal.
7. After checking to make sure every connection is secure, use the cable
clamp to fasten the signal cable to the unit. Screw the cable clamp down
tightly.
8. Replace the wire cover on the front of the unit, and the plastic panel on
the back.
In North America
NOTE: Choose the cable type according to the local electrical codes and
regulations. Please choose the right cable size according to the Minimum
Circuit Ampacity indicated on the nameplate of the unit.
First open the front panel, then remove the lower panel.
open the Wire cover
Terminal block Cable clamp
Rat baffle(some units) Knock-out panel
NOTE: If the size of the cable is too big, remove the middle small plastic
knock-out panel to create a slot through which the cable can exit. If you want
to remove the chassis or drain hose, please remove the rat baffle first.
NOTE: For North America products, first remove the knok-out panel to create a
slot through which the conduit tube can install. Then make the cable through
the conduit tube and connect to the indoor unit.
17
5 Wrap piping & Cables
NOTE
Before passing the piping, and drain hose and the signal cable through the
wall hole, you must bundle them together to save space, protect them, and
insulate them.
Indoor Unit
Signal wire
Drain hose
Vinyl tape Pipe (narrow)
Wrap with insulation tape
Space behind unit
Step 1
Bundle the drain hose, refrigerant pipes, and signal cable as shown in the
figure(Not applicable for some locations in North America ).
Refrigerant piping Insulation tape
Step 2
Using adhesive vinyl tape, attach the drain hose to the underside of the refrigerant pipes.
Step 3
Using insulation tape, wrap the refrigerant pipes, signal wire and drain hose tightly together. Double-check that all items are bundled.
Drain hose
Do not intertwine signal calbe with other wires
While bundling these items together,do not intertwine or cross the signal
cable with any other wiring.
DRAIN HOSE MUST BE ON BOTTOM
Make sure that the drain hose is at the bottom of the bundle. Putting the
drain hose at the top of the bundle can cause the drain pan to overflow, which
can lead to fire or water damage.
DO NOT WRAP ENDS OF PIPING
When wrapping the bundle, keep the ends of the piping unwrapped. You need to
access them to test for leaks at the end of the installation process (refer to
Electrical Checks and Leak Checks section of this manual).
18
6 Mount indoor unit
Hook it
Connecting cable
Drain hose
Put pipes in wall hole
Hook it and press down lightly to secure
Check that the unit is firmly mounted
If you installed new connective piping to the outdoor unit, do the following:
If you have already passed the refrigerant piping through the hole in the
wall, proceed to Step 4. Otherwise, double-check that the ends of the
refrigerant pipes are sealed to prevent dirt or foreign
materials from entering the pipes. Slowly pass the wrapped bundle of
refrigerant pipes, drain hose, and signal wire through the hole
in the wall. Hook the top of the indoor unit on the upper hook of the mounting
plate. Check that unit is hooked firmly on mounting by applying slight
pressure to the left and right-hand
sides of the unit. The unit should not jiggle or shift. Using even pressure,
push down on the bottom half of the unit. Keep pushing down until the unit
snaps onto the hooks along the bottom of the mounting plate. Again, check that
the unit is firmly mounted by applying slight pressure to the left and the
right-hand
sides of the unit.
CAUTION
For the units adopt the following pipe connectors, please strictly perform the
piping work in accordance with the following instructions.
Connector A
Connector B
Cross-shape part
Red point protruding
Before performing the refrigerant piping connection, always wear work gloves
and goggles, and remember that the connectors A and B are not allowed to face
people directly.
Keep pressing the cross-shape part of connector B with a tool for about 5~10
seconds until the red protuding point of connector A retracts completely.
Remove connectors A and B, then perform the refrigerant piping connection
between indoor unit and outdoor unit.
19
Install Your Outdoor Unit
1
Select installation location
NOTE : PRIOR TO INSTALLATION
Before installing the outdoor unit, you must choose an appropriate location.
The following are standards that will help you choose an appropriate location
for the unit.
Proper installation locations meet the following standards:
60cm24″ above
30cm12″ on left
30cm12″ from back wall
Good air circulation Firm and solid–the
Noise from the unit
and ventilation.
location can support the will not disturb other
unit and will not vibrate. people.
200cm79″ in front
60cm24″ on right
Long-term
Meets all spatial requirements shown in Installation Protected from prolonged periods Where snowfall is anticipated, take
Space Requirements above.
of direct sunlight or rain.
appropriate measures to prevent
ice buildup and coil damage.
NOTE
Install the unit by following local codes and regulations , there may be differ slightly between different regions.
CAUTION:
SPECIAL CONSIDERATIONS FOR EXTREME WEATHER
If the unit is exposed to heavy wind:
Install unit so that air outlet fan is at a 90° angle to the direction of the wind. If needed, build a barrier
in front of the unit to protect it from extremely heavy winds. See Figures below.
If the unit is frequently exposed to heavy rain or snow:
Build a shelter above the unit to protect it from the rain or snow. Be careful not to obstruct air flow
around the unit.
If the unit is frequently exposed to salty air(seaside):
Use outdoor unit that is specially designed to resist corrosion.
Strong wind
Wind Baffle
Shelter
Strong wind
90° angle to the direction of the wind
Strong wind
Build a wind Baffle to protect the unit
Build a shelter to protect the unit
DO NOT install unit in the following locations:
Near an obstacle that will block air inlets and outlets.
Near a public street, crowded areas, or where noise from the unit will disturb
others.
Near animals or plants that will be harmed by hot air discharge.
Near any source of combustible gas.
In a location that is exposed to large amounts of dust
In a location exposed to a excessive amounts of salty air.
20
2 Install drain joint(Heat pump unit only)
NOTE : PRIOR TO INSTALLATION
Before bolting the outdoor unit in place, you must install the drain joint at
the bottom of the unit. For the units with base pan built-in with multiple
holes for proper draining during defrost, the drain joint is no need to be
installed.
Step 1 Find out the base pan hole of outdoor unit.
Seal
Base pan hole of outdoor unit
Step 2 Fit the rubber seal on the end of the drain joint that will connect to
the
outdoor unit. Insert the drain joint into the hole in the base pan of the
unit. The drain joint
will click in place. Connect a drain hose extension (not included) to the
drain joint to redirect
water from the unit during heating mode.
NOTE : IN COLD CLIMATES
In cold climates, make sure that the drain hose is as vertical as possible to
ensure swift water drainage. If water drains too slowly, it can freeze in the
hose and flood the unit.
21
3 Anchor Outdoor Unit
WARNING
WHEN DRILLING INTO CONCRETE, EYE PROTECTION IS RECOMMENDED AT ALL TIME.
The outdoor unit can be anchored to the ground or to a wall-mounted bracket
with bolt(M10). Prepare the installation base of the unit according to the
dimensions below.
The following is a list of different outdoor unit sizes and the distance
between their mounting feet. Prepare the installation base of the unit
according to the dimensions below.
A
Air inlet
Air inlet
H
D B
Air outlet
Top view
W
Front view
Outdoor Unit Dimensions (mm) W x H x D
668x469x252 (26.3″x 18.5″x 9.9″) 680x542x248 (26.8″x 21.3″x 9.8″) 700x550x275
(27.5″x 21.6″x 10.8″) 720x495x270 (28.3″x 19.5″x 10.6″) 765x555x303 (30.1″x
21.8″x 11.9″) 770x555x300 (30.3″x21.8″x11.8″) 800x554x333 (31.5″x21.8″x13.1″)
805x554x330 (31.7″x 21.8″x 12.9″) 845x702x363 (33.3″x 27.6″x 14.3″)
890x673x342 (35.0″x 26.5″x 13.5″) 946x810x420 (37.2″x 31.9″x 16.5″)
946x810x410 (37.2″x 31.9″x 16.1″)
Mounting Dimensions
Distance A (mm)
430 (16.9″) 452 (17.8″) 450 (17.7″) 452 (17.8″) 452 (17.8″) 487 (19.2″) 514
(20.2″) 511 (20.1″) 540 (21.3″) 663 (26.1″) 673 (26.5″) 673 (26.5″)
Distance B (mm)
231 (9.1″) 230 (9.1″) 260 (10.2″) 255 (10.0″) 286(11.3″) 298 (11.7″) 340
(13.4″) 317 (12.5″) 350 (13.8″) 354 (13.9″) 403 (15.9″) 403 (15.9″)
If you will install the unit on the
ground or on a concrete mounting platform, do the following
Mark the positions for four expansion bolts based on dimensions chart.
Pre-drill holes for expansion bolts. Place a nut on the end of each expansion
bolt. Hammer expansion bolts into the pre-drilled
holes. Remove the nuts from expansion bolts, and
place outdoor unit on bolts. Put washer on each expansion bolt, the
replace the nuts. Using a wrench, tighten each nut until snug.
If you will install the unit on a wall-mounted
bracket , do the following:
Mark the position of bracket holes based on dimensions chart.
Pre-drill the holes for the expansion bolts. Place a washer and nut on the end
of each expansion bolt. Thread expansion bolts through holes in mounting
brackets, put mounting brackets in position, and hammer expansion bolts into
the wall. Check that the mounting brackets are level. Carefully lift unit and
place its mounting feet on brackets. Bolt the unit firmly to the brackets. If
allowed, install the unit with rubber gaskets to reduce vibrations and noise.
CAUTION
Make sure that the wall is made of solid brick, concrete, or of similarly
strong material. The wall must be able to support at least four times the
weight of the unit.
22
4 Connect signal and power cables
WARNING – Before the Operation
ALL WIRING WORK MUST BE PERFORMED STRICTLY IN ACCORDANCE WITH THE WIRING
DIAGRAM LOCATED INSIDE OF WIRE COVER OF THE OUTDOOR UNIT.
BEFORE PERFORMING ANY ELECTRICAL OR WIRING WORK,TURN OFF THE MAIN POWER TO THE
SYSTEM.
Prepare the cable for connection
Please choose the right cable according to the “Cable types” in page 15. Using
wire strippers, strip the rubber jacket from both ends of cable to reveal
about 40mm (1.57in) of the wires inside. Strip the insulation from the ends of
the wires. Using a wire crimper, crimp u-lugs on the ends of the wires.
Choose the right cable size
The size of the power supply cable, signal cable, fuse, and switch needed is
determined by the maximum current of the unit. The maximum current is
indicated on the nameplate located on the side panel of the unit.
Pay attention to live wire
While crimping wires, make sure you clearly distinguish the Live (“L”) Wire
from other wires.
The outside unit’s terminal block is protected by an electrical wiring cover
on the side of the unit. A comprehensive wiring diagram is sticked on the
inside of the wiring cover. Unscrew the electrical wiring cover and remove
it. Unscrew the cable clamp below the terminal
block and place it to the side. Connect the wire according to the wiring
diagram, and firmly screw the u-lug of each wire to its corresponding
terminal. After checking to make sure every connection is secure, loop the
wires around to prevent rain water from flowing into the terminal. Using the
cable clamp, fasten the cable to the unit. Screw the cable clamp down tightly.
Insulate unused wires with PVC electrical tape. Arrange them so that they do
not touch any electrical or metal parts. Replace the wire cover on the side of
the unit, and screw it in place.
NOTE: The unit you purchased may be slightly different.The illustrations are
for explanatory purposes. The actual shape shall prevail.
Remove four screws Cover
Cover
Screw
NOTE: If the cable clamp looks like the following, please select the
appropriate through-hole according to the diameter of the wire.
Buckle
Three size hole: Small, Large, Medium
When the calbe is not fasten enough, use the buckle to prop it up , so it can
be clamped tightly.
23
In North America
The outside unit’s terminal block is protected by an electrical wiring cover
on the side of the unit. A comprehensive wiring diagram is sticked on the
inside of the wiring cover. Remove the wire cover from the unit by
loosening the 3 screws. Dismount caps on the conduit panel. Temperarily mount
the conduit tubes(not
included) on the conduit panel. Properly connect both the power supply and
low voltage lines to the corresponding terminals on the terminal block. Ground
the unit in accordance with local codes. Be sure to size each wire allowing
several inches longer than the required length for wiring. Use lock nuts to
secure the conduit tubes.
NOTE: Please choose the right cable size according to the Minimum Circuit
Ampacity indicated on the nameplate of the unit.
Terminal block
(O40vmerm1-)9/16″
G
Wire Cover
Connecting cable Power supply cord
Conduit panel
Please select the appropriate through-hole according to the diameter of the wire.
How to properly connect the wire lines.
Strip 25mm(15/16″) Strip 10mm(3/8″)
Loop
Insulation Solid wire
Round terminal
Strand wire
Wire
Screw with special washer Round terminal Terminal plate
Wire
Screw with special washer Round terminal
Step 1 The treatment about the end of the wire.
Wall receptacle or Air break switch(North America)
(purchased seperately)
Outdoor unit power wires
Indoor & Outdoor connective wires (purchased seperately)
Step 2
connecting the line to the corresponding terminals on the terminal block.
Indoor unit power wires
Wall receptacle or Air break switch (North America) (purchased seperately)
Outdoor unit
Indoor unit
(A)
Outdoor unit
Indoor unit
Indoor & Outdoor connective wires (purchased seperately)
(B)
24
Refrigerant Piping Connection
1
Piping Connection Precautions
WARNING
WHEN CONNECTING REFRIGERANT PIPING, DO NOT LET SUBSTANCES OR GASES OTHER THAN
THE SPECIFIED REFRIGERANT ENTER THE UNIT. THE PRESENCE OF OTHER GASES OR
SUBSTANCES WILL LOWER THE UNIT’S CAPACITY, AND CAN CAUSE ABNORMALLY HIGH
PRESSURE IN THE REFRIGERATION CYCLE. THIS CAN CAUSE EXPLOSION AND INJURY.
Note on Pipe Length
The length of refrigerant piping will affect the performance and energy efficiency of the unit. Nominal efficiency is tested on units with a pipe length of 5 meters (16.5ft). ( In North America, the standard pipe length is 7.5m (25′). For the R290 refrigerant models, no refrigerant can be added and the maximum length of refrigerant pipe should not exceed 5 meters(16.5ft).A minimum pipe run of 3 metres is required to minimise vibration & excessive noise. Connection Instructions Refrigerant Piping.
Maximum Length and Drop Height of Refrigerant Piping per Unit Model
Model R410A,R32 Inverter Split Air Conditioner
R22 Fixed-speed Split Air Conditioner
R410A, R32 Fixed-speed Split Air Conditioner
Capacity (BTU/h)
< 15,000
15,000 and < 24,000 24,000 and < 36,000 36,000 and < 60,000
< 18,000
18,000 and < 21,000 21,000 and < 35,000 35,000 and < 41,000
< 18,000
18,000 and < 36,000 36,000 and < 60,000
Max. Length (m)
25 (82ft) 30 (98.5ft) 50 (164ft) 65 (213ft) 10 (33ft) 15 (49ft) 20 (66ft) 25
(82ft) 20 (66ft) 25 (82ft) 30 (98.5ft)
Max. Drop Height (m)
10 (33ft) 20 (66ft) 25 (82ft) 30 (98.5ft) 5 (16ft) 8(26ft) 10(33ft) 10 (33ft)
8(26ft) 10(33ft) 15 (49ft)
Connection Instructions Refrigerant Piping
Step 1: Cut pipes
When preparing refrigerant pipes, take extra care to cut and flare them
properly. This will ensure efficient operation and minimize the need for
future maintenance.
Measure the distance between the indoor and outdoor units.
Using a pipe cutter, cut the pipe a little longer than the measured distance.
Make sure that the pipe is cut at a perfect 90° angle.
90°
Oblique Rough Warped
DO NOT DEFORM PIPE WHILE CUTTING
Be extra careful not to damage, dent, or deform the pipe while cutting. This
will drastically reduce the heating efficiency of the unit.
25
CAUTION
MUST BE CHECK OVER THE END OF THE PIPE FOR CRACKS AND EVEN FLARING. ENSURE THE
PIPE IS SEALED.
Step 2: Remove burrs
Burrs can affect the air-tight seal of refrigerant piping connection. They
must be completely removed. Hold the pipe at a downward angle to prevent
burrs from falling into the pipe. Using a reamer or deburring tool, remove all
burrs from the cut section of the pipe.
Pipe Reamer
Point down
Remove PVC tape from ends of pipe when ready to perform flaring work.
Clamp flare form on the end of the pipe. The end of the pipe must extend
beyond the edge of the flare form in accordance with the dimensions shown in
the table below.
Handle
Bar Yoke
Cone
Clamp handle
Red arrow mark
Step 3: Flare pipe ends
Proper flaring is essential to achieve an airtight seal. After removing burrs
from cut pipe, seal
the ends with PVC tape to prevent foreign materials from entering the pipe.
Sheath the pipe with insulating material. Place flare nuts on both ends of
pipe. Make sure they are facing in the right direction, because you can’t put
them on or change their direction after flaring.
Flare nut
Copper pipe
PIPING EXTENSION BEYOND FLARE FORM
Outer Diameter of Pipe (mm)
Ø 6.35 (Ø 1/4″) Ø 9.52 ( Ø 3/8″) Ø12.7 ( Ø 1/2″) Ø 16 ( Ø 5/8″) Ø 19 ( Ø 3/4″)
A (mm)
Min.
MMaaxx..
0.7 (0.0275″) 1.3 (0.05″)
1.0 (0.04″)
1.6 (0.063″)
1.0 (0.04″)
1.8 (0.07″)
2.0 (0.078″)
2.2 (0.086″)
2.0 (0.078″)
2.4 (0.094″)
Flare form
A
Pipe
Place flaring tool onto the form. Turn the handle of the flaring tool
clockwise
until the pipe is fully flared. Remove the flaring tool and flare form, then
inspect the end of the pipe for cracks and even flaring.
26
2 Refer to Torque Requirement to connect pipes
CAUTION
WHEN CONNECTING REFRIGERANT PIPES, BE CAREFUL NOT TO USE EXCESSIVE TORQUE OR
TO DEFORM THE PIPING IN ANY WAY. YOU SHOULD FIRST CONNECT THE LOW-PRESSURE
PIPE, THEN THE HIGH-PRESSURE PIPE.
MINIMUM BEND RADIUS
When bending connective refrigerant piping, the minimum bending radius is
10cm.
Radius
10cm (4″)
Instructions for Connecting Piping to Indoor Unit
Step 1
Align the center of the two pipes that you will connect.
Step 2
Tighten the flare nut as tightly as possible by hand. Using a spanner, grip
the nut on the unit tubing. While firmly gripping the nut on the unit tubing,
use a
torque wrench to tighten the flare nut according to the torque values in the
Torque Requirements table below. Loosen the flaring nut slightly, then tighten
again.
Indoor unit tubing
Flare nut Pipe
Torque wrench
Indoor unit tubing
Spanner (fixed) Flare nut
Connection pipe
TORQUE REQUIREMENTS
Outer Diameter of Pipe(mm) Tightening Torque(N·m) Flare dimension(B)(mm)
Ø 6.35 (Ø 1/4″) Ø 9.52 (Ø 3/8″) Ø 12.7 ( Ø 1/2″)
18~20(180~200kgf.cm) 32~39(320~390kgf.cm) 49~59(490~590kgf.cm)
8.4~8.7 (0.33~0.34″) 13.2~13.5 (0.52~0.53″) 16.2~16.5 (0.64~0.65″)
Ø 16 ( Ø 5/8″) Ø 19 (Ø 3/4″)
57~71(570~710kgf.cm) 67~101(670~1010kgf.cm)
19.2~19.7 (0.76~0.78″) 23.2~23.7 (0.91~0.93″)
Flare shape
90°+_ 4 45 °+_2
B R0.4~0. 8
DO NOT USE EXCESSIVE TORQUE
Excessive force can break the nut or damage the refrigerant piping. You must
not exceed torque requirements shown in the table above.
27
3 Connecting Piping to Outdoor Unit
NOTE
This section still needs to be operated according to the TORQUE REQUIREMENTS
chart on the previous page.
Unscrew the cover Valve cover
Outdoor unit
Liquid side piping (Smaller diameter)
(Bigger
Torque wrench
Step 1 Unscrew the cover from the packed
valve on the side of the outdoor unit.
Step 2 Remove protective caps from ends of
valves. Align flared pipe end with each valve,
and tighten the flare nut as tightly as possible by hand. Using a spanner,
grip the body of the valve. Do not grip the nut that seals the service valve.
USE SPANNER TO GRIP MAIN BODY OF VALVE Torque from tightening the flare nut
can snap off other parts of valve.
Connect all pipes
Step 3
While firmly gripping the body of the valve, use a torque wrench to tighten
the flare nut according to the correct torque values.
Loosen the flaring nut slightly, then tighten again.
Repeat Steps 1 to 3 for the remaining pipe.
28
Air Evacuation
NOTE : PREPARATIONS AND PRECAUTIONS
Air and foreign matter in the refrigerant circuit can cause abnormal rises in
pressure, which can damage the air conditioner, reduce its efficiency, and
cause injury. Use a vacuum pump and manifold gauge to evacuate the refrigerant
circuit, removing any non-condensable gas and moisture from the system.
Evacuation should be performed upon initial installation and when unit is
relocated.
BEFORE PERFORMING EVACUATION Make sure the connective pipes between the indoor
and outdoor units are connected properly. Check to make sure all wiring is
connected properly.
Evacuation Instructions
Indoor unit
Outdoor unit
Manifold valve
-76cmHg
Compound gauge
Pressure gauge
Low pressure
valve Pressure hose
or Charge hose
High pressure valve Charge hose
Low pressure valve
Step 1
Connect the charge hose of the manifold gauge to service port on the outdoor
unit’s low pressure valve.
Connect another charge hose from the manifold gauge to the vacuum pump.
Open the Low Pressure side of the manifold gauge. Keep the High Pressure side
closed.
Turn on the vacuum pump to evacuate the system.
Run the vacuum for at least 15 minutes, or until the Compound Meter reads
-76cmHG (-10 Pa).
Close the Low Pressure side of the manifold gauge, and turn off the vacuum
pump.
Wait for 5 minutes, then check that there has been no change in system
pressure.
Vacuum pump
29
Flare nut
valve body
valve stem
Step 2
If there is a change in system pressure, refer to Gas Leak
Check section for information on how to check for leaks.
If there is no change in system pressure, unscrew the cap
from the packed valve (high pressure valve).
Insert hexagonal wrench into the packed valve(high
pressure valve) and open the valve by turning the wrench
in a 1/4 counterclockwise turn. Listen for gas to exit the
system, then close the valve after 5 seconds.
Watch the Pressure Gauge for one minute to make sure
Cap
that there is no change in pressure. The Pressure Gauge
should read slightly higher than atmospheric pressure.
Remove the charge hose from the service port.
Using hexagonal wrench, fully open both the high
pressure and low pressure valves.
Tighten valve caps on all three valves (service port, high
pressure, low pressure) by hand. You may tighten it
further using a torque wrench if needed.
OPEN VALVE STEMS GENTLY
When opening valve stems, turn the hexagonal wrench until it hits against the
stopper. Do not try to force the valve to open further.
NOTE ON ADDING REFRIGERANT
Some systems require additional charging depending on pipe lengths. The
standard pipe length varies according to local regulations. For example, in
North America, the standard pipe length is 7.5m (25′). In other areas, the
standard pipe length is 5m (16`). The refrigerant should be charged from the
service port on the outdoor unit’s low pressure valve. For the R290
refrigerant models, no refrigerant can be added. The additional refrigerant to
be charged can be calculated using the following formula:
ADDITIONAL REFRIGERANT PER PIPE LENGTH
Connective Pipe Air Purging
Length (m)
Method
< Standard pipe length Vacuum Pump
Additional Refrigerant
N/A
Standard pipe length
Vacuum Pump
Liquid Side: Ø 6.35 (1/4″)
Liquid Side: Ø 9.52 (3/8″)
R410A: (Pipe length standard length) x 15g/m
R410A: (Pipe length standard length) x 30g/m
(Pipe length standard length) x 0.16oZ/ft (Pipe length standard length) x 0.32oZ/ft
R32: (Pipe length standard length) x 12g/m
R32: (Pipe length standard length) x 24g/m
(Pipe length standard length) x 0.13oZ/ft (Pipe length standard length) x 0.26oZ/ft
R22: (Pipe length standard length) x 20g/m
R22: (Pipe length standard length) x 40g/m
(Pipe length standard length) x 0.21oZ/ft (Pipe length standard length) x 0.42oZ/ft
DO NOT MIX REFRIGERANT TYPES.
30
Electrical And Gas Leak Checks
WARNING – RISK OF ELECTRIC SHOCK
ALL WIRING MUST COMPLY WITH LOCAL AND NATIONAL ELECTRICAL CODES, AND MUST BE
INSTALLED BY A LICENSED ELECTRICIAN.
BEFORE TEST RUN
Only perform test run after you have completed the following steps: · Electrical Safety Checks Confirm that the unit’s electrical system is safe and operating properly · Gas Leak Checks Check all flare nut connections and confirm that the system is not leaking · Confirm that gas and liquid (high and low pressure) valves are fully open
Electrical Safety Checks
After installation, confirm that all electrical wiring is installed in
accordance with local and national regulations, and according to the
Installation Manual.
BEFORE TEST RUN
Check Grounding Work Measure grounding resistance by visual detection and with
grounding resistance tester.
DURING TEST RUN
Check for Electrical Leakage During the Test Run, use an electroprobe and multimeter to perform a comprehensive electrical leakage test. If electrical leakage is detected, turn off the unit immediately and call a licensed electrician to find and resolve the cause of the leakage. Note: This may not be required for some locations in North America.
Gas Leak Checks
There are two different methods to check for gas leaks. Soap and Water Method
Using a soft brush, apply soapy water or liquid detergent to all pipe
connection points on the indoor unit and outdoor unit. The presence of bubbles
indicates a leak. Leak Detector Method
If using leak detector, refer to the device’s operation manual for proper
usage instructions.
Check-point of outdoor unit
Check-point of indoor unit
D
B
C
A
A: Low pressure stop valve B: High pressure stop valve C& D: Indoor unit flare
nuts
AFTER PERFORMING GAS LEAK CHECKS After confirming that the all pipe connection
points DO NOT leak, replace the valve cover on the outside unit.
31
Test Run
Test Run Instructions
You should perform the Test Run for at least 30 minutes. Connect power to the
unit. Press the ON/OFF button on the remote
controller to turn it on. Press the MODE button to scroll through the
following functions, one at a time: · COOLSelect lowest possible temperature
· HEATSelect highest possible temperature Let each function run for 5
minutes, and perform the following checks:
List of Checks to Perform
No electrical leakage
PASS/FAIL
Unit is properly grounded
All electrical terminals properly covered
Indoor and outdoor units are solidly installed
All pipe connection points do not leak
Outdoor (2):
Indoor (2):
Water drains properly from drain hose
All piping is properly insulated
Unit performs COOL function properly
Unit performs HEAT function properly
Indoor unit louvers rotate properly
Indoor unit responds to remote controller
DOUBLE-CHECK PIPE CONNECTIONS
During operation, the pressure of the refrigerant circuit will increase. This
may reveal leaks that were not present during your initial leak check. Take
time during the Test Run to double-check that all refrigerant pipe connection
points do not have leaks. Refer to Gas Leak Check section for instructions.
After the Test Run is successfully completed, and you confirm that all checks
points in List of Checks to Perform have PASSED, do the following: a. Using
remote control, return unit to normal operating temperature. b. Using
insulation tape, wrap the indoor refrigerant pipe connections that you left
uncovered during the indoor unit installation process.
IF AMBIENT TEMPERATURE IS BELOW 16°C(60°F) You can’t use the remote controller
to turn on the COOL function when the ambient temperature is below 16°C/60°F.
In this instance, you can use the MANUAL CONTROL button to test the COOL
function. Lift the front panel of the indoor unit. The MANUAL CONTROL button
is located
on the right-hand side of the unit. Press it 2 times to select the COOL
function. Perform Test Run as normal.
Manual control button
32
Packing And Unpacking The Unit
Instructions for packing and unpacking the unit:
Unpacking: Indoor unit:
1. Cut the sealing tape on the carton with a knife, one cut on the left, one
cut in the middle and one cut on the right.
2.Use the vice to take out the sealing nails on the top of the carton. 3.Open
the carton. 4.Take out the middle support plate if it is included. 5.Take out
the accessory package, and take out the connecting wire if it is included.
6.Lift the machine out of the carton and lay it flat. 7.Remove the left and
right package foam or the upper and lower packaging foam, untie the
packaging bag.
Outdoor Unit
1.Cut the packing belt. 2.Take the unit out of the carton. 3.Remove the foam
from the unit. 4.Remove the packaging bag from the unit.
Packing: Indoor unit:
1.Put the indoor unit into the packing bag. 2.Attach the left and right
package foam or the upper and lower packaging foam to the unit. 3.Put the unit
into the carton, then put accessory package in. 4.Close the carton and seal it
with the tape. 5.Using the packing belt if necessary.
Outdoor unit:
1.Put the outdoor unit into the packing bag. 2.Put the bottom foam into the
box. 3.Put the unit into the carton, then put the upper packaging foam on the
unit. 4.Close the carton and seal it with the tape. 5.Using the packing belt
if necessary.
NOTE: Please keep all packaging items if you may need in the future.
33
OPERATION INSTRUCTIONS
NOTE
Different models have different front panel and display window. Not all the
indicators describing below are available for the air conditioner you
purchased. Please check the indoor display window of the unit you purchased.
Illustrations in this manual are for explanatory purposes. The actual shape of
your indoor unit may be slightly different. The actual shape shall prevail.
Indoor Unit Display
Front Panel
Air Outlet
Functional Filter
(On Back of Main Filter-Some Units)
Air Filter
Remote Control
Display window
ECO intelligent eye (some units)
Remote Control Holder
(purchase separately)
Display Windows
(Model A)
(Model B)
Display Code
Display Code Meanings
Displays temperature, operation feature and Error codes.
(Model C)
When ECO function is activated.
When Wireless Control feature is activated(some units).
TIMER ON is set (if the unit is OFF, ”
“remains on when TIMER ON is set ).
for 3s when
FRESH, UV-C lamp, SWING, TURBO, ECO, BREEZE AWAY, SILENCE or ECO INTELLIGENT EYE feature is turned on.
TIMER OFF is set.
for 3s when
FRESH, UV-C lamp, SWING, TURBO, ECO, BREEZE AWAY, SILENCE or ECO INTELLIGENT EYE feature is turned off.
When Active Clean feature is turned on(For Inverter split type ). When the Self clean feature is turned on (For fixed-speed type).
When defrosting(cooling & heating units only).
When 8 C (46 F)heating feature is turned on(some units).
34
Operating Temperature
When your air conditioner is used outside of the following temperature ranges,
certain safety protection features may activate and cause the unit to disable.
Inverter Split Type
Room Temp.
COOL Mode
16°C~32°C(60°F~90°F)
HEAT Mode
0°C~30°C(32°F~86°F)
DRY Mode
10°C~32°C(50°F~90°F)
Outdoor Temp.
0°C~50°C(32°F~122°F)
-15°C~50°C(5°F~122°F)
For models withlow temp. cooling systems.
-15°C~24°C(5°F~75°F)
0°C~50°C(32°F~122°F)
0°C~52°C(32°F~126°F)
For special tropical models
-15°C~24°C(5°F~75°F)
0°C~52°C(32°F~126°F)
For special tropical models
FOR OUTDOOR UNITS WITH AUXILIARY ELECTRIC HEATER
When outside temperature is below 0°C (32°F ), we strongly recommend keeping
the unit plugged in at all time to ensure smooth ongoing performance.
Fixed-speed Type
COOL Mode
Room Temp.
16°C~32°C (60°F~90°F)
HEAT Mode
0°C~30°C (32°F~86°F)
Outdoor Temp.
18°C~43°C (64°F~109°F)
-7°C~43°C (19°F~109°F)
For models with low-temp cooling systems
-7°C~24°C(19°F~75°F)
DRY Mode
10°C~32°C(50°F~90°F) 11°C~43°C (52°F~109°F) 18°C~43°C (64°F~109°F)
18°C~52°C (64°F~126°F)
For special tropical models
-7°C~24°C(19°F~75°F)
18°C~52°C (64°F~126°F)
For special tropical models
NOTE: Room relative humidity less than 80%. If the air conditioner operates in excess of this figure, the surface of the air conditioner may attract condensation. Please sets the vertical air flow louver to its maximum angle (vertically to the floor), and set HIGH fan mode.
35
To further optimize the performance of your unit, do the following:
Keep doors and windows closed. Limit energy usage by using TIMER ON and TIMER
OFF functions. Do not block air inlets or outlets. Regularly inspect and clean
air filters.
More features
NOTE
Not all the functions are available for the air conditioner you purchased,
please check the indoor display and remote control of your unit.
Auto-Restart If the unit loses power, it will automatically restart with the
prior settings once power has been restored.
Anti-mildew When turning off the unit from COOL, AUTO (COOL), or DRY modes,
the air conditioner will continue operate at very low power to dry up
condensed water and prevent mildew growth.
Wireless Control (Model dependent)
Wireless control allows you to control your air conditioner using your mobile
phone and a wireless connection. For the USB device access, replacement,
maintenance operations must be carried out by professional staff.
· Active Clean function(some units)
— The Active Clean Technology washes away dust when it adheres to the heat
exchanger by automatically freezing and then rapidly thawing the frost. A “pi-
pi” sound will be heard. The Active clean operation is used to produce more
condensed water to improve the cleaning effect, and the cold air will blow
out. After cleaning, the internal wind wheel then keeps operating with hot air
to blow-dry the evaporator, thus keeping the inside clean.
— When this function is turned on, the indoor unit display window appears “CL
” , after 20 to 45 minutes, the unit will turn off automatically and cancel
Active Clean function.
ECO Intelligent eye(some units) The system is controlled intelligently under
Intelligent eye mode. It can detect the people’s activities in the room. In
cooling mode, when you are away for 30 minutes, the unit will automatically
lower the frequency to save energy(for Inverter models only). And the unit
will automatically start and resume operation if sensing human activity again.
Refrigerant Leakage Detection(some units) The indoor unit will automatically
display “EL0C” when it detects refrigerant leakage.
Louver Angle Memory When turning on your unit, the louver will automatically
resume its former angle.
Breeze Away (some units)
This feature avoids direct air flow blowing on the body and make you feel
indulging in silky coolness.
Sleep Operation
The SLEEP function is used to decrease energy use while you sleep (and don’t
need the same temperature settings to stay comfortable).
Press the SLEEP button on remote control when in COOL mode, the unit will
increase the temperature by 1°C (2°F) after 1 hour, and will increase an
additional 1°C (2°F) after another hour. When in HEAT mode, the unit will
decrease the temperature by 1°C (2°F) after 1 hour, and will decrease an
additional 1°C (2°F) after another hour.
The sleep feature will stop after 8 hours and the system will keep running
with final situation.
SLEEP Operation
Cool mode(+1 C/2 F) per hour for the first two hours
Set
temperature
1hr
1hr
Keep running
Heat mode( -1 C/2 F) per hour for the first two hours
Saving energy during sleep
36
Setting Angle of Air Flow NOTE : Setting vertical angle of air flow(Remote
control)
While the unit is on, use the SWING/DIRECT button on remote control to set the
direction (vertical angle) of airflow. Please refer to the Remote Control
operation for details.
NOTE ON LOUVER ANGLES
Do not set louver at too vertical an angle for long periods of time When using
COOL or DRY mode. It would be condense the water on the louver blade, which
will drop on your floor or furnishings.
Setting the louver at too small an angle when using COOL or HEAT mode, can
reduce the performance of the AC due to restricted air flow.
According to the relative standards requirement, please sets the vertical air flow louver to its maximum angle under heating capacity test.
Heating Capacity
Test
NOTE
Do not move louver by hand. You can turn off the unit and unplug it for a few
seconds to restart the unit. It will be reset the louver when you try.
Setting horizontal angle of air flow(Manual operation)
The horizontal angle of the airflow must be set manually. Grip the deflector rod (See Fig.B) and manually adjust it to your preferred direction. For some units, the horizontal angle of the airflow can be set by remote control. please refer to the Remote Control Manual.
Deflector rod
Fig. B
CAUTION
Do not put your fingers in or near the blowerand suction side of the unit. The
high-speed fan inside the unit may cause injury.
37
Manual Operation(without remote)
CAUTION : For product use
The manual button is intended for testing purposes and emergency operation
only. Please do not use this function unless the remote control is lost and it
is absolutely necessary. To restore regular operation, use the remote control
to activate the unit. Unit must be turned off before manual operation.
To operate your unit manually:
Open the front panel of the indoor unit. Locate the MANUAL CONTROL button on
the
right-hand side of the unit. Press the MANUAL CONTROL button one time to
activate FORCED AUTO mode. Press the MANUAL CONTROL button again to
activate FORCED COOLING mode. Press the MANUAL CONTROL button a third time
to turn the unit off. Close the front panel.
Manual control button
38
Remote Control Operation
Model
Rated Voltage Signal Receiving Range Environment
RG10A(B2S)/BGEF, RG10A(B2S)/BGEFU1, RG10A1(B2S)/BGEF,RG10A2(B2S)/BGEFU1,
RG10A2(B2S)/BGCEFU1, RG10A2(B2S)/BGCEF, RG10A10(B2S)/BGEF
3.0V( Dry batteries R03/LR03×2) 8m
-5°C~60°C(23°F~140°F)
Quick Start Guide
1 FIT BATTERIES
6 PRESS POWER BUTTON
2 SELECT MODE
AUTO COOL DRY HEAT FAN
3 SELECT TEMPERATURE
5 POINT REMOTE TOWARD UNIT
4 SELECT FAN SPEED
AU-100%
Swing
My Mode Fo
Mode
HEDARCTYOAOULTO
SET TEMPERATURE LOMWEHDIGFAHN
On/Off Fan
Sleep
NOT SURE WHAT A FUNCTION DOES? Refer to the How to Use Basic Functions and How
to Use Advanced Functions sections of this manual for a detailed description
of how to use your air conditioner.
SPECIAL NOTE
· · If the indoor unit does not have a particular function, pressing that
function’s button on
·
MANUAL” on function description, the description of “USER’S MANUAL” shall
prevail.
39
Handling the Remote Controller
Inserting and Replacing Batteries Your air conditioning unit may come with two
batteries(some units). Put the batteries in the remote control before use. 1.
Slide the back cover from the remote control
downward, exposing the battery compartment. 2.Insert the batteries, paying
attention to match
up the (+) and (-) ends of the batteries with 3. the symbols inside the
battery compartment.
Slide the battery cover back into place.
BATTERY NOTES For optimum product performance: · Do not mix old and new
batteries, or · Do not leave batteries in the remote
control if you don’t plan on using the device for more than 2 months.
BATTERY DISPOSAL Do not dispose of batteries as unsorted municipal waste.
Refer to local laws for proper disposal of batteries.
NOTES FOR USING REMOTE CONTROL
The device could comply with the local national regulations. · In Canada, it
should comply with
CAN ICES-3(B)/NMB-3(B). · In USA, this device complies with part 15 of
the FCC Rules. Operation is subject to the following two conditions: (1) This
device may not cause harmful
interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation. This
equipment has been tested and found to comply with the limits for a Class B
digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications. However,
there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or
television reception,which can be determined by turning
to try to correct the interference by one or more of the following measures: ·
Reorient or relocate the receiving antenna. · Increase the separation between
the
equipment and receiver. · Connect the equipment into an outlet on a
is connected. · Consult the dealer or an experienced radio/TV
technician for help. · Changes or modifications not approved by the
party responsible for compliance could void user’s authority to operate the
equipment.
TIPS FOR USING REMOTE CONTROL
· The remote control must be used within 8 meters of the unit.
· The unit will beep when remote signal is received.
· Curtains, other materials and direct sunlight can interfere with the
infrared signal receiver.
· Remove batteries if the remote will not be used more than 2 months.
40
Buttons and Functions
1 4 5 8 9
12
Boost
Description
No.1
ON/OFF
No.2
2 No.3 3
No.4 6 7
No.5 10 11 13 14 No.6
No.7
MODE Auto > Cool > Dry > Heat > Fan
NOTE: HEAT mode is not supported by the cooling only appliance.
ECO/GEAR ECO > GEAR(75%) > GEAR(50%) > Previous setting mode > ECO TEMP.
Increases temperature in 1°C (1°F) increments. Max. temperature is 30°C
(86°F). (Press together & buttons at the same time for 3 seconds will
alternate the temperature display between the °C & °F).
SET
Air magic/UV lamp > Sleep > Follow Me > AP mode> Air magic/UV lamp
[]: Model dependent
OK Used to confirm the selected functions
TEMP.
No.8
Model:
RG10A2(B2S)/BGEFU1.
RG10A10(B2S)/BGEF(20-28°C/68-82°F).
RG10A(B2S)/BGEF & RG10A(B2S)/BGEFU1 ( Fresh feature is not available)
RG10A2(B2S)/BGCEFU1 & RG10A2(B2S)/ BGCEF(Cooling only models, AUTO mode and
HEAT mode are not available)
No.9 No.10 No.11
TEMP. Decreases temperature in 1°C (1°F) increments. Min. temperature is 16°C
(60°F)
FAN SPEED AU > 20% > 40% >60% > 80% > 100% Press the TEMP or button to
increase/ decrease the fan speed in 1% increments.
SWING Starts and stops the horizontal louver movement. Hold down for 2 seconds
to initiate vertical louver auto swing feature(some units).
BREEZE AWAY Avoids direct air flow blowing on the body (This feature is
available under cool, Fan and Dry mode only)
No.12
BOOST Boost Reach desired temperature in shortest possible time.
No.13
LED
LED
CLEAN No.14 Clean Used to start/stop the Self Clean or Active Clean function.
No.15 Boost
Clean
LOCK Press together these two buttons simultaneously for 5 seconds to lock the
keyboard. Press together these two buttons for 2 seconds to unlock the
keyboard.
41
Buttons and Functions
1 4 5 8 9
12
Boost
Model: RG10A1(B2S)/BGEF
Description
No.1
ON/OFF
No.2
2 No.3 3
No.4 6 7
No.5 10 11 13 14 No.6
No.7
MODE Auto > Cool > Dry > Heat > Fan
NOTE: HEAT mode is not supported by the cooling only appliance.
ECO/GEAR ECO > GEAR(75%) > GEAR(50%) > Previous setting mode > ECO TEMP.
Increases temperature in 1°C (1°F) increments. Max. temperature is 30°C
(86°F). (Press together & buttons at the same time for 3 seconds will
alternate the temperature display between the °C & °F).
SET
Breeze away> Sleep > Follow Me > AP mode > Breeze away
[]: Model dependent
OK Used to confirm the selected functions
TEMP.
No.8 No.9 No.10 No.11
TEMP. Decreases temperature in 1°C (1°F) increments. Min. temperature is 16°C
(60°F)
FAN SPEED AU > 20% >40% > 60% > 80% > 100% Press the TEMP or button to
increase/ decrease the fan speed in 1% increments.
SWING Starts and stops the horizontal louver movement. Hold down for 2 seconds
to initiate vertical louver auto swing feature(some units).
Air magic Used to start/stop the Air magic and UV-C lamp (if any) function.
No.12
Boost
BOOST Reach desired temperature in shortest possible time.
No.13
LED
LED
CLEAN No.14 Clean Used to start/stop the Self Clean or Active Clean function.
No.15 Boost
Clean
LOCK Press together these two buttons simultaneously for 5 seconds to lock the
keyboard. Press together these two buttons for 2 seconds to unlock the
keyboard.
42
Remote Screen Indicators
Information are displayed when the remote controller is power up.
Breeze Active Air magic/ Sleep
Away clean UV lamp mode mode
Follow Wireless* Low battery
me control (If flashes)
MODE display Displays the current mode
AUTO COOL DRY HEAT FAN
Transmission ECO GEAR Timer Indicator Feature Feature ON
Timer Lock OFF Feature
Slience Feature
Temperature/Timer/Fan speed display
Displays the set temperature by default, or fan speed or timer setting when
using TIMER ON/OFF functions.
FAN SPEED AUTO
SLIENCE
LOW
MED
HIGH
1% 2-20% 21-40% 41-60% 61-80% 81-100% Note: This fan speed can not be adjusted in AUTO or DRY mode.
Horizontal louver swing
Not available for this unit
Boost mode
[*]: Model dependent
NOTE 1. All indicators shown in the figure are for the purpose of clear
presentation. But during the actual
operation, only the relative function signs are shown on the display window.
43
How to Use Basic Functions
NOTE
Before operation, please ensure the unit is plugged in and power is available.
AUTO Mode Select AUTO mode
Set your desired temperature
MODE
Turn on the air conditioner
NOTE: 1. In AUTO mode, the unit will automatically select the COOL, FAN, or
HEAT function based on the set
temperature. 2. In AUTO mode, fan speed can not be set.
COOL or HEAT Mode Select COOL/HEAT mode
Set the temperature
Set the fan speed
Turn on the air conditioner
MODE
DRY Mode Select DRY mode
MODE
Set your desired temperature
Turn on the air conditioner
NOTE: In DRY mode, fan speed can not be set since it has already been automatically controlled.
FAN Mode Select FAN mode
Set the fan speed
Turn on the air conditioner
MODE
NOTE: In FAN mode, you can’t set the temperature. As a result , no temperature displays in remote screen. 44
Setting the TIMER
TIMER ON/OFF
TIMER ON setting
Press TIMER button to initiate the ON time sequence.
Press Temp. up or down button for for multiple times to set the desired time
to turn on the unit.
x5
Point remote to unit and wait 1sec, the TIMER ON will be activated.
1 sec
TIMER OFF setting
Press TIMER button to initiate the OFF time sequence.
Press Temp. up or down button for for multiple times to set the desired
x5
ON/OFF
MODE FAN
SLEEP
TEMP
SCHUOTRT TIMER ON
TIMERO
Point remote to unit and wait 1sec, the TIMER OFF will be activated.
1 sec
ON/OFF
MODE FAN
SLEEP
TEMP
SCHUOTRT TIMER ON
TIMERO
NOTE: 1. When setting the TIMER ON or TIMER OFF, the time will increase by 30
minutes increments with each
press, up to 10 hours. After 10 hours and up to 24, it will increase in 1 hour
increments. (For example, press 5 times to get 2.5h, and press 10 times to get
5h,) The timer will revert to 0.0 after 24. 2. Cancel either function by
setting its timer to 0.0h.
TIMER ON & OFF setting(example) Keep in mind that the time periods you set for both functions refer to hours after the current time.
xn
xn
1 sec
ON/OFF
MODE FAN
SLEEP
TEMP
SCHUOTRT TIMER ON
TIMERO
ON/OFF
MODE FAN
SLEEP
TEMP
SCHUOTRT TIMER ON
TIMERO
Timer starts
Unit turns
ON
Unit turns
OFF
Current time 1PM
2:00PM 3:00PM 3:30PM
2.5 hours later 5 hours later
4PM
5PM
6PM
Example: If current timer is 1:00PM, to set the timer as above steps, the unit will turn on 2.5h later (3:30PM)
45
How to Use Advanced Functions
Swing function
Press Swing button Swing
The horizontal louver will swing up and down automatically when pressing Swing button. Press again to make it stop.
Airflow direction Swing
If continue to press the SWING button, five
louver can be move at a certain range each time you press the button. Press
the button until the direction you prefer is reached.
LED DISPLAY LED
5s LED
Press this button more than 5 seconds(some units)
the display on the indoor unit.
Keep pressing this button more than 5 seconds, the indoor unit will display the actual room temperature. Press more than 5 seconds again will revert back to display the setting temperature.
BOOST Function Press Boost button
Boost
When you select Boost feature in COOL mode, the unit will blow cool air with
strongest wind setting to jump-start the cooling process.
When you select Boost feature in HEAT mode, the unit will blow heat air with
strongest wind setting to jump-start the heating process(some units). For
units with Electric heat elements, the Electric HEATER will activate and jump-
start the heating process.
46
ECO/GEAR function
following: ECO GEAR(75%) GEAR(50%) Previous setting mode
Note:This function is only available under COOL mode.
ECO……
ECO operation:
Under cooling mode, press this button, the remote controller will adjust the
temperature automatically to 24OC/75OF, fan speed of Auto to save energy (only
when the set temperature is less than 24 OC/75OF). If the set temperature is
above 24 OC/75OF, press the ECO button, the fan speed will change to Auto, the
set temperature will remain unchanged.
NOTE: Pressing the ECO button, or modifying the mode or adjusting the set
temperature to less than 24OC/75 OF will stop ECO operation. Under ECO
operation, the set tmeperature should be 24O C/75OF or above, it may result in
just press the ECO button again to stop it.
GEAR operation: Press the ECO/GEAR button to enter the GEAR operation as
following: 75%(up to 75% electrial energy consumption) 50%(up to 50% electrial
energy consumption) Previous setting mode.
Under GEAR operation, the display on the remote controller will alternate
between electical energy consumption and set temperature.
Silence function
2s
Keep pressing Fan button for more than 2 seconds to activate/disable Silence function.
heating capacity. Press ON/OFF, Mode, Sleep, Boost or Clean button while operating will cancel silence function.
FP function Press this button 2 times during one second under HEAT Mode and
setting temperature of 16O C/60O F to activate the FP function.
2 The unit will operate at high fan speed (while compressor on) with
temperature automatically set to 8OC/46OF.
47
SET function
SET
SET or
OK
Press the SET button to enter the function setting, then press SET button or
TEMP or TEMP button to select the desired function. The selected symbol will
flash on the display area, press the OK button to confirm.
To cancel the selected function, just perform the same procedures as above.
Press the SET button to scroll through operation functions as follows: Breeze
Away( ) Air magic/UV lamp( ) Sleep( ) Follow Me( ) AP mode ( ) []: If your
remote controller has Breeze Away button or Air magic button, you can not use
the SET
button to select the Breeze Away or Air magic/UV lamp feature.
Breeze Away function (some units) :
This feature avoids direct air flow blowing on the body and makes you feel
indulging in silky coolness.
NOTE: This feature is available under cool, Fan and Dry mode only.
Air magic/UV-C function(some units) When the Air magic function is initiated,
the ion generator is energized and will help to purify the air inside. When
the UV function is initiated, the UV lamp emit UV-C radiation to help to
purify the air inside.
Sleep function The SLEEP function is used to decrease energy use while you
sleep(and don’t need the same temperature settings to stay comfortable).
NOTE: The SLEEP function is not available in FAN and DRY mode.
AP function(some units) : Choose AP mode to do wireless network configuration.
For some units, it doesn’t work by pressing the SET button. To enter the AP
mode, continuously press the LED button seven times in 10 seconds.
Follow me function The FOLLOW ME function enables the remote control to
measure the temperature at its current location and send this signal to the
air conditioner every 3 minutes interval. When using AUTO, COOL or HEAT modes,
measuring ambient temperature from the remote control(instead of from the
indoor unit itself) will enable the air conditioner to optimize the
temperature around you and ensure maximum comfort.
NOTE: Press and hold Boost button for seven seconds to start/stop memory
feature of Follow Me function.
,, ,,
If the memory feature is activated, On,,
displays for 3 seconds If the memory feature
iosnsttohpepsecdre, enO. F,,
displays for 3 seconds on the screen.
While the memory feature is activated,
press the ON/OFF button, shift the mode
or power failure will not cancel the Follow
me function.
48
CARE AND MAINTENANCE
CAUTION
· The cooling efficiency of your unit and your health would be damaged for the
glogged AC. Make sure to clean the filter every two weeks.
· Always TURN OFF your AC system and disconnect its power supply before
cleaning or maintenance.
· Do not touch air freshening (Plasma) filter at least 10 minutes after
turning off the unit.
· Only use a soft, dry cloth to wipe the unit clean. You can use a cloth
soaked in warm water to wipe it clean if the unit is especially dirty.
· Do not use chemicals or chemically treated cloths to clean the unit · Do not
use benzene, paint thinner, polishing powder or other solvents to clean
the unit. They can cause the plastic surface to crack or deform. · Do not use
water hotter than 40°C (104°F) to clean the front panel. This can
cause the panel to deform or become discolored.
Cleaning Your Indoor Unit, Air Filter
Step 1
The air filter is on the top of the air conditioner. Hold both side of the top
filter in the place marked with “PULL”, then pull it upwards.
Step 3
Clean the large air filter with warm, soapy water. Be sure to use a mild
detergent. Rinse the filter with fresh water, then shake off excess water. Dry
it in a cool, dry place, and refrain from exposing it to direct sunlight.
Hold both side of the top
PULL
filter in the place marked
with “PULL”, pull it upwards
Step 2
If your filter has a small air freshening filter, unclip it from the larger
filter. Clean this air freshening filter with a hand-held vacuum.
(Front)
(Back)
Don’t forget to install me back
Step 4
When dry, re-clip the air freshening filter to the larger filter, then install
the air filter back on the top of the indoor unit.
1. Flip to back
2. Remove air 3. Clean it by freshening filter vacuum cleaner off (some units)
49
CAUTION
· Before changing the filter or cleaning, turn off the unit and disconnect its
power supply.
· When removing filter, do not touch metal parts in the unit. The sharp metal
edges can cut you.
· Do not use water to clean the inside of the indoor unit. This can destroy
insulation and cause electrical shock.
· Do not expose filter to direct sunlight when drying. This can shrink the
filter. · Any maintenance and cleaning of outdoor unit should be performed by
an
authorized dealer or a licensed service provider. · Any unit repairs should be
performed by an authorized dealer or a licensed
service provider.
Air Filter Reminders (Optional)
Display window: “CL” Display window: “nF”
Air Filter Cleaning Reminder · After 240 hours of use, the display window on
the indoor unit will flash “CL.”
This is a reminder to clean your filter. After 15 seconds, the unit will
revert to its previous display. · To reset the reminder, press the LED button
on your remote control 4 times, or press the MANUAL CONTROL button 3 times. If
you don’t reset the reminder, the “CL” indicator will flash again when you
restart the unit. Air Filter Replacement Reminder · After 2,880 hours of use,
the display window on the indoor unit will flash “nF.” This is a reminder to
replace your filter. After 15 seconds, the unit will revert to its previous
display. · To reset the reminder, press the LED button on your remote control
4 times, or press the MANUAL CONTROL button 3 times. If you don’t reset the
reminder, the “nF” indicator will flash again when you restart the unit.
Maintenance your AC.
Maintenance Long Periods of Non-Use
If you plan not to use your air conditioner for an extended period of time, do
the following:
Maintenance Pre-Season Inspection
After long periods of non-use, or before periods of frequent use, do the
following:
Clean all filters
Turn on FAN function until unit dries out completely
Check for damaged wires Clean all filters
Check for leaks
Turn off the unit and disconnect the power
Remove batteries from remote control
Make sure nothing is blocking all air inlets and outlets
50
Replace batteries
TROUBLESHOOTING
CAUTION
If any of the following conditions occurs, turn off your unit immediately! ·
The power cord is damaged or abnormally warm · You smell a burning odor · The
unit emits loud or abnormal sounds · A power fuse blows or the circuit breaker
frequently trips · Water or other objects fall into or out of the unit DO NOT
ATTEMPT TO FIX THESE YOURSELF! CONTACT AN AUTHORIZED SERVICE PROVIDER
IMMEDIATELY.
Common Issues
The following problems are not a malfunction and in most situations will not
require repairs.
Issue Unit does not turn on when pressing ON/OFF button
The unit changes from COOL/HEAT mode to FAN mode
Possible Causes
The Unit has a 3-minute protection feature that prevents the unit from
overloading. The unit cannot be restarted within three minutes of being turned
off.
The unit may change its setting to prevent frost from forming on the unit.
Once the temperature increases, the unit will start operating in the
previously selected mode again.
The set temperature has been reached, at which point the unit turns off the
compressor. The unit will continue operating when the temperature fluctuates
again.
The indoor unit emits white mist
Both the indoor and outdoor units emit white mist
In humid regions, a large temperature difference between the room’s air and
the conditioned air can cause white mist.
When the unit restarts in HEAT mode after defrosting, white mist may be
emitted due to moisture generated from the defrosting process.
The indoor unit makes noises
A rushing air sound may occur when the louver resets its position.
A squeaking sound may occur after running the unit in HEAT mode due to
expansion and contraction of the unit’s plastic parts.
Low hissing sound during operation: This is normal and is caused by refrigerant gas flowing through both indoor and outdoor units.
Both the indoor unit and outdoor unit make noises
Low hissing sound when the system starts, has just stopped running, or is
defrosting: This noise is normal and is caused by the refrigerant gas stopping
or changing direction.
Squeaking sound: Normal expansion and contraction of plastic and metal parts
caused by temperature changes during operation can cause squeaking noises.
51
Issue
The outdoor unit makes noises
Dust is emitted from either the indoor or outdoor unit
Possible Causes
The unit will make different sounds based on its current operating mode.
The unit may accumulate dust during extended periods of non-use, which will be
emitted when the unit is turned on. This can be mitigated by covering the unit
during long periods of inactivity.
The unit emits a bad odor
The unit may absorb odors from the environment (such as furniture, cooking,
cigarettes, etc.) which will be emitted during operations.
The unit’s filters have become moldy and should be cleaned.
The fan of the outdoor unit does not operate
During operation, the fan speed is controlled to optimize product operation.
Operation is erratic, unpredictable, or unit is unresponsive
Interference from cell phone towers and remote boosters may cause the unit to
malfunction.
In this case, try the following:
· Disconnect the power, then reconnect. · Press ON/OFF button on remote
control to restart operation.
NOTE: If problem persists, contact a local dealer or your nearest customer
service center. Provide them with a detailed description of the unit
malfunction as well as your model number.
CAUTION
When troubles occur, please check the following points before contacting a
repair company.
Problem
Poor Cooling Performance
Possible Causes
Temperature setting may be higher than ambient room temperature
Solution Lower the temperature setting
The heat exchanger on the indoor or outdoor unit is dirty
Clean the affected heat exchanger
The air filter is dirty
Remove the filter and clean it according to instructions
The air inlet or outlet of either unit is blocked
Doors and windows are open
Excessive heat is generated by sunlight
Turn the unit off, remove the obstruction and turn it back on
Make sure that all doors and windows are closed while operating the unit
Close windows and curtains during periods of high heat or bright sunshine
Too many sources of heat in the room (people, computers, electronics, etc.)
Reduce amount of heat sources
Low refrigerant due to leak or long-term use
SILENCE function is activated (optional function)
Check for leaks, re-seal if necessary and top off refrigerant
SILENCE function can lower product performance by reducing operating
frequency. Turn off SILENCE function.
52
Problem
The unit is not working
The unit starts and stops frequently
Poor heating performance
Indicator lamps continue flashing Error code appears and begins with the
letters as the following in the window display of indoor unit: · E(x), P(x),
F(x) · EH(xx), EL(xx), EC(xx) · PH(xx), PL(xx), PC(xx)
Possible Causes Power failure
Solution Wait for the power to be restored
The power is turned off
Turn on the power
The fuse is burned out Remote control batteries are dead
Replace the fuse Replace batteries
The Unit’s 3-minute protection has been activated
Wait three minutes after restarting the unit
Timer is activated
Turn timer off
There’s too much or too little refrigerant in the system
Incompressible gas or moisture has entered the system.
The compressor is broken
The voltage is too high or too low
Check for leaks and recharge the system with refrigerant.
Evacuate and recharge the system with refrigerant
Replace the compressor
Install a manostat to regulate the voltage
The outdoor temperature is extremely low
Use auxiliary heating device
Cold air is entering through doors and windows
Low refrigerant due to leak or long-term use
Make sure that all doors and windows are closed during use
Check for leaks, re-seal if necessary and top off refrigerant
The unit may stop operation or continue to run safely. If the indicator lamps continue to flash or error codes appear, wait for about 10 minutes. The problem may resolve itself. If not, disconnect the power, then connect it again. Turn the unit on. If the problem persists, disconnect the power and contact your nearest customer service center.
NOTE: If your problem persists after performing the checks and diagnostics above, turn off your unit mmediately and contact an authorized service center.
53
TRADEMARKS, COPYRIGHTS AND LEGAL STATEMENT
logo, word marks, trade name, trade dress and all versions thereof are
valuable assets of Midea Group and/or its affiliates (“Midea”), to which Midea
owns trademarks, copyrights and other intellectual property rights, and all
goodwill derived from using any part of an Midea trademark. Use of Midea
trademark for commercial purposes without the prior written consent of Midea
may constitute trademark infringement or unfair competition in violation of
relevant laws.
This manual is created by Midea and Midea reserves all copyrights thereof. No
entity or individual may use, duplicate, modify, distribute in whole or in
part this manual, or bundle or sell with other products without the prior
written consent of Midea.
All the described functions and instructions were up to date at the time of
printing this manual. However, the actual product may vary due to improved
functions and designs.
DISPOSAL AND RECYCLING
Important instructions for environment(European Disposal Guidelines)
Compliance with the WEEE Directive and Disposing of the Waster Product: This
product complies with EU WEEE Directive (2012/19/EU). This product bears a
classification symbol for waster electrical and electronic equipment (WEEE).
This symbol indicates that this product shall not be disposed with other
household wastes at the end of its service life. Used device must be returned
to official collection point for recycling of electrical electronic devices.
To find these collection systems please contact to your local authorities or
retailer where the product was purchased. Each household performs important
role in recovering and recycling of old appliance. Appropriate disposal of
used appliance helps prevent potential negative consequences for the
environment and human health.
54
DATA PROTECTION NOTICE
For the provision of the services agreed with the customer, we agree to comply
without restriction with all stipulations of applicable data protection law,
in line with agreed countries within which services to the customer will be
delivered, as well as, where applicable, the EU General Data Protection
Regulation (GDPR). Generally, our data processing is to fulfil our obligation
under contract with you and for product safety reasons, to safeguard your
rights in connection with warranty and product registration questions. In some
cases, but only if appropriate data protection is ensured, personal data might
be transferred to recipients located outside of the European Economic Area.
Further information are provided on request. You can contact our Data
Protection
MideaDPO@midea.com. To exercise your rights such as right to object your
personal date being processed for direct marketing purposes, please contact us
via MideaDPO@midea.com. To find further information, please follow the QR
Code.
The design and specifications are subject to change without prior notice for
product improvement. Consult with the sales agency or manufacturer for
details. Any updates to the manual will be uploaded to the service website,
please check for the latest version.
Importer: MIDEA SCOTT & ENGLISH ELECTRONICS SDN BHD. NO.16 JALAN CHAN SOW
LIN,55200 KUALA LUMPUR
Manufacturer: GD Midea Air-Conditioning Equipment Co,.Ltd. Lingang Road
Beijiao Shunde Foshan Guangdong People’s Republic of China 528311
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>