TOSHIBA RKP002Z Remote Keypad Instruction Manual
- June 3, 2024
- Toshiba
Table of Contents
TOSHIBA RKP002Z Remote Keypad
NOTICE
- Make sure that this instruction manual is delivered to the end user of Remote Keypad.
- Read this manual before installing or operating the Remote Keypad. Keep it in a safe place for reference.
- All information contained in this manual are subject to change without notice. Please confirm the latest information on our web site “www.inverter.co.jp”.
Safety precautions
On the inverter and in its instruction manual, important information is
contained for preventing injuries to users, damages to assets, and for proper
use of the device.
Read the instruction manual attached to the inverter along with this
instruction manual to completely understand the safety precautions, the
symbols and indications shown below. Please adhere to the contents of these
manuals at all times.
Explanation of markings
Marking | Meaning of marking |
---|
Danger
| Indicates that errors in operation may lead to death or serious injury.
Warning| Indicates that errors in operation may lead to injury (1) to people
or that these errors may cause damage to physical property. (2)
- Such things as injury, burns or shock that will not require hospitalization or long periods of outpatient treatment.
- Physical property damage refers to wide-ranging damage to assets and materials.
Meanings of symbols
Marking | Meaning of marking |
---|---|
Indicates prohibition (Do not do it). |
What is prohibited will be described in or near the symbol in either text or picture form.
| Indicates something mandatory (must be done).
What is mandatory will be described in or near the symbol in either text or picture form.
| Indicates danger.
What is dangerous will be described in or near the symbol in either text or picture form.
| Indicates warning.
What the warning should be applied to will be described in or near the symbol in either text or picture form.
Limitation of use
- Never use this unit with any device other than TOSVERT series inverters. Doing so may cause an accident.
Handling in general
Danger
Never Disassemble
| Never disassemble, modify or repair the product.
Disassembling the product may cause electric shocks, fire or injuries. For repairs, call your sales/repair agency.
Prohibited
| Do not put or insert foreign objects such as waste cable, bars, or wires into the product. It may lead to electric shocks or fire.
Do not splash water over the product, and do not wipe the body with a wet cloth. It may lead to electric shocks or fire.
Mandatory
| Turn off input power before wiring.
Wait at least 15 minutes and check to make sure that the charge lamp (on the inverter unit) is no longer lit.
Turn off the power immediately in case of any abnormalities such as smoke, smell or abnormal noise.
Neglect of these conditions may lead to fire. For repairs, call your sales/repair agency.
Transportation and installation
Danger
Prohibited
| Do not install or operate the inverter if it is damaged or any part of it is missing. Operating a defective inverter may lead to electric shocks or fire.
For repairs, call your sales/repair agency.
Do not put any flammable material near the product.
It may catch fire due to the product sparking in the case of a malfunction.
Do not connect a LAN cable or telephone modular cable to Remote Keypad. Doing so may cause a failure or accident.
Mandatory
| Electrical construction work must be done by a qualified expert.
Connection of input power by someone who does not have expert knowledge may result in fire or electric shock.
Operate under the environmental conditions prescribed in the instruction manual. Operations under any other conditions may result in malfunction.
An emergency stop device must be installed that fits with system specifications (e.g. shut off input power then engage mechanical brake).
Operation cannot be stopped immediately by the inverter or Remote Keypad alone, thus risking an accident or injury.
Use the Toshiba-specified cable for connecting this optional unit. (Refer to page 4.) The use of any other option may result in an accident.
Warning
Prohibited
| Do not install the product in any place subject to vibrations or it may fall. This may lead to the product falling and causing injury.
Operations
Danger
Prohibited
| Do not apply a dropping shock or other physical shocks. Otherwise, damage or malfunction will result.
Do not pull on the cable and connector It may cause damage or error.
Even if this product is deactivated by an unusual event such as tripping, an operating error, power outage, etc. do not bring any regions of your body into contact with the inverter terminals when power is supplied to the inverter. Contact during the power-on status of the inverter can result in electric shock.
Mandatory
| Use an additional safety device with your inverter or system to prevent a serious accident due to the unit malfunctions. Usage without an additional safety device may cause an accident.
Make sure to check that the parameter data from this product is not accidently copied to the wrong inverter.
Usage with wrong parameter may result in an accident.
Warning
Mandatory
| ▼ Set up “Communication error trip time ( f803 , f804 , see the inverter instruction manual for details)” to stop the inverter when Remote Keypad is deactivated by an
unusual event such as tripping, an operating error, power outage, failure, etc. Deactivated Remote Keypad may cause an accident, if the “Communication error trip time” is not properly set up.
Disposal
Warning
Mandatory
| If you dispose off this unit, have it done by a specialist in industrial waste disposal*. Improper disposal may result in explosion of capacitors or produce noxious gases, resulting in injury.
(*) Persons who specialize in the processing of waste and known as “Industrial Waste Product Collectors and Transporters” or “Industrial Waste Disposal Persons.” If the collection, transport and disposal of industrial waste is done by someone who is not licensed for that job, it is a punishable violation of the law (Laws in regard to cleaning
and processing of waste materials).
Notes on operation
Notes
| Avoid installing in a place where ambient temperature or/and humidity change sharply. Keep the transmission cable separate from the power cable of the inverter to prevent the inverter from malfunctioning due to electromagnetic noise.
It is recommended to install the unit on the panel board of a cabinet if it is used as a remote operation panel. Improperly installed units may result in damage and malfunction.
The integrity of data storage is guaranteed for up to 10 years.
The operating life of EEPROM (data storage device) is 10000 operations. Do not execute more than 10000 writing operations.
Do not turn off power or remove the connection cable between the inverter and Remote Keypad while a copying operation is in progress. If the inverter power is turned off or the connection cable is removed while parameters are being copied, data cannot be written correctly.
Do not copy data from Remote Keypad to inverter while the inverter is running. Some of the parameters cannot be written when the inverter is in operation.
When a copying operation is executed between two inverters with different capacities, some of the parameters that vary with the capacity of the inverters will also be copied. Therefore, when copying the parameters between inverters with different capacities or voltage class, the type information parameters of the inverter should always be initialized. See the inverter instruction manual on how to initialize their parameters.
Preface
Thank you for purchasing Remote Keypad (RKP002Z ) for TOSVERT series
inverters. Using this product, panel operation, display and adjustment of the
inverter can be remotely controlled from up to 5 meters away. You can copy
data from one place to another and then execute data comparison between the
inverter and the memory of Remote Keypad or between the memories of Remote
Keypad itself.
Before using Remote Keypad, carefully read this instruction manual in order to
completely and correctly utilize Remote Keypad’s excellent performance.
After reading this instruction manual, please keep it handy for future
reference.
- Part numbering
- Accessory check list
Remote Keypad is shipped together with the following accessories.
On opening the packing case, check to see if the following accessories are contained or not.
-
Instruction manual ……………………………………. 1 copy
(English: E6581277) -
Mounting screws (M3 x 12mm) ………………….. 4pcs.
(M3 screw tightening torque: 0.6 Nּ m)
N.B.: Remote Keypad (Part number: RKP002Z) is not provided with connection cable between an inverter and Remote Keypad. This should be purchased separately.
Part number of connection cable between an inverter and an option unit| Cable
length
---|---
CAB0011| 1.2m, 4ft
CAB0013| 3.6m, 12ft
CAB0015| 4.8m, 16ft
Overview
The following seven functions are available with Remote Keypad.
-
Function to serve as remote operation panel.
Remote Keypad can be used as a remote operation panel for the inverter. -
Copying function
Data can be copied from one memory to another memory among the four memories, three (memories A, B, C) on Remote Keypad and one on the inverter. -
Data copy from Remote Keypad to inverter
-
Data copy from inverter to Remote Keypad
-
Data copy from one memory to another memory on Remote Keypad
-
Simple copying function
Data stored in one of Remote Keypad’s memory may be transferred to the inverter’s memory by simple operation of two keys. -
Comparing function
Data stored in one of Remote Keypad’s memory can be compared with the data of inverter’smemory. In addition, data stored within any of the 3 Remote keypad memories (A, B, or C) can be
compared with each other. -
Memory protecting function
Data written on the inverter’s memory and the memories of Remote Keypad are protected by this function to protect against data damage. -
Memory initializing function
One of the memories (A, B, or C) on Remote Keypad can be initialized by this function.
In addition, Remote keypad can be reprogrammed to default setting. -
Remote Keypad parameter editing function
Remote Keypad parameters are programmable.
Memory configuration
Remote Keypad has three memories (A, B, and C) to retain three kinds of parameter for the inverter.
Names and functions of main parts
The drawings below show names and functions of main parts.
Front view
Reverse view
- These lamps are not lit when Remote Keypad is connected to VF-S11, VF-nC1, VF-S9, VF-A7, VF-P7 etc.
- The lamp is not lit when Remote Keypad is connected to an inverter without [EASY] key.
Operation keys and their functions in “COPY MODE”
The operation key’s functions in “COPY MODE” are explained in the following
table.
Operation key | Function | Operation key | Function |
---|
| Memory A key
(Exclusive key for simple copying)
In the simple copying function, this key is used to specify memory A of Remote Keypad as the origin of transmission data.
(In “REMOTE KEYPAD MODE”: RUN key)
|
| Memory B key
(Exclusive key for simple copying)
In the simple copying function, this key is used to specify memory B of Remote Keypad as the origin of transmission data.
(In “REMOTE KEYPAD MODE”: STOP key)
| Memory C key
(Exclusive key for simple copying)
In the simple copying function, this key is used to specify memory C of Remote Keypad as the origin to transmission data.
(In “REMOTE KEYPAD MODE”: DOWN key)
|
| SFT key
is used for selecting a function (copying, comparing, protecting data) or for selecting a memory from among inverter’s memory and memories (A, B, and C) of Remote Keypad.
(In “REMOTE KEYPAD MODE”: UP key)
| ESC key
is used to return to previous setting
(In “REMOTE KEYPAD MODE”: MODE key)
|
| ENT key
is used to chose a function or memory or to execute the chosen function.
(In “REMOTE KEYPAD MODE”: ENT key)
| Invalid in “COPY MODE”
(In “REMOTE KEYPAD MODE”: EASY key)
|
Connection and start-up
Connect Remote Keypad with the inverter according to the procedure stated below.
-
Set Communication Mode Switch (refer to page.7) on the reverse side of Remote Keypad. The position varies for the inverter series.
RS485: The inverter with RS485 (2-wire type) port (ex: VF-AS1, etc.)
LOGIC: The inverter with Common Serial Port (ex: VF-S11, VF-nC1, VF-S9, VF-A7, VF-P7). -
Set communication baud rate (the inverter parameter “f800”) to 9600, 19200 or 38400bps (programmed by default setting at the factory).
-
Turn off the input power to the inverter, wait at least 15 minutes, and insure that the charge lamp on the inverter is no longer lit.
-
Connect an inverter-unit connection cable (optional) between the communication connector of Remote Keypad and that of the inverter. At this time, be careful not to apply excessive force to the
connectors. (See the instruction manual of the inverter for connection to the communication port of the inverter.) -
After wiring, fix the wires on the surface of the wall in the panel board and so on.
-
Turn on the inverter, and Remote Keypad starts-up automatically showing a lit panel in the display window.
-
Using in “COPY MODE”, check that the “COPY MODE” lamp is lit.
-
In order to change from “REMOTE KEYPAD MODE” to the “COPY MODE”, turn off the power ofinverter and insure that the Remote Keypad is also turned off. Then, turn on the power of the inverter (Remote Keypad) while holding down the [ENT] key of Remote Keypad.
N.B.: When disconnecting Remote Keypad from the inverter, follow step (3) of the above procedure.
Functions in detail
Remote Keypad can be used as remote operation panel (“REMOTE KEYPAD MODE”) or
parameter
back-up device (“COPY MODE”). When the “COPY MODE” lamp is lit when turning
power on, Remote
Keypad operates in “COPY MODE”, otherwise in “REMOTE KEYPAD MODE”.
Procedure to switch the operation mode
According to the procedure described in “3. Connection and start-up”, turn on
the power of Remote
Keypad while holding down the [ENT] key of Remote Keypad. Operation mode
changes.
“REMOTE KEYPAD MODE”
In “REMOTE KEYPAD MODE”, operation is the same as operation on the panel of
the inverter. For details, see instruction manual of the inverter. Data
entered through Remote Keypad takes priority over data entered through the
inverter’s control panel. However, if Remote Keypad is deactivated by an
unexpected event such as an abnormality, the inverter’s input keys remain
functional.
“COPY MODE”
In “COPY MODE”, storing and loading the parameters are permitted. Editing the
parameters is not permitted.
Copying function “copy”
The data stored in a memory can be copied to another memory selected from
among four memories (the inverter’s memory and Remote Keypad memories A, B,
and C). Remote Keypad can not be used to copy parameters from one inverter to
another inverter of a different series.
N.B.: To copy the data to the inverter’s memory, do it when the inverter has
stopped. If you copy the data to the inverter while the inverter is running,
some of the parameters fail to be copied.
Operating procedure
- If the [ESC] key is pressed, Remote Keypad returns to previous status (except when executing).
- When the memory protection function is actuated, Remote Keypad inhibits copying data with “prot” appearing in the display window.
- If there is no data in memory A of Remote Keypad upon selection as data to copy from, the display shows “err.a” which means copying data is impossible. (When the memory B or C is selected in the same condition, “err.b” or “err.c” appears in the display window.)
Simple copying function
The data stored in the memory A, B or C of Remote Keypad can be copied to the
inverter’s memory with simple operation of two keys to select one of the
memories A, B and C. Use this function to set the same parameters to more than
two inverters. Remote Keypad can not copy parameters to from one inverter to
another inverter of a different series. What differs from the “Copying
function” in
Section 4.3.1 is the key operation and the contents of parameters to be copied
are the same for both functions. It is impossible to copy data from the
inverter’s memory to a memory of Remote Keypad in this function.
N.B.: To copy data to the inverter’s memory, do it when the inverter has stopped. If you copy data to the inverter while the inverter is running, some of the parameters may fail to be copied.
Operating procedure
- If the [ESC] key is pressed, Remote Keypad returns to previous status (except when executing).
- When the memory protection function is actuated, Remote Keypad inhibits copying data with “prot” appearing in the display window.
- If there is no data in memory A of Remote Keypad upon selection as data to copy from, the display shows“err.a” which means copying data is impossible. (When the memory B or C is selected in the same condition, “err.b” or “err.c” appears in the display window.)
The same operation as above can also be used to copy data from memory B or memory C of Remote Keypad to the inverter.
Since the [ A ], [ B ], and [ C ] keys are provided to be used exclusively for the simple copying function, those keys cannot be used for other functions.
Comparing function “comp”
This function enables the operator to compare data stored in two memories
selected from among four memories (the inverter’s memory and Remote Keypad
memories A, B, and C) as well as to
search for parameters that differ from each other.
The comparing function cannot be used for editing parameters because it is
provided only for searching parameters that differ from each other. Use the
“REMOTE KEYPAD MODE” function described in section 4.2 to edit parameters.
Operating procedure
- If the [ESC] key is pressed, Remote Keypad returns to previous status (except when executing).
Memory protection function “prot”
The memory protection function protects the selected memory from being
overwritten.
When this function is initiated copying data to the memory is prohibited.
Reading the memory data is permitted.
When all the memories are initialized by memory initialization function (clr),
the LED indications are as follows: “in”, “a”, “b”, “c” = “off”, “sup” = “on”
This is also the default setting at the time of shipment.
Operating procedure
If the [ESC] key is pressed, Remote Keypad returns to previous status (except
when executing).
(*1) The Protecting operation of “sup” is different from that provided for
other memories and is shown below.
With the same inverter types (capacity, voltage class)
: Protection disabled (write permitted),
With different inverter types (capacity, voltage class)
“–”: Write protected (write prohibited)
In this case, copying operation of parameters from one inverter to another inverter of a different capacity or a different voltage class.
Memory initializing function “clr”
A selected one of the memories either memory A, B, C of Remote Keypad is
enable to be initialized with this function. In addition, all memories
including system memory of Remote Keypad is also enable to be initialized.
Operating procedure
- If the [ESC] key is pressed, Remote Keypad returns to previous status (except when executing).
- When the memory protection function is actuated, Remote Keypad prohibits the initialization of memory with “prot” appearing in the display window.
Remote Keypad parameter editing function
This function allows the user to edit the parameters of Remote Keypad.
Remote Keypad parameter list
Warning
It is recommended to set the automatic comparing function “f-02” to “1”
(default). When “0” is selected, programming errors (caused by environmental
circumstances, peripheral devices, etc.) will not be automatically detected.
This could result in an accident, if the inverter is operating with the wrong
parameters.
Operating procedure
- If the [ESC] key is pressed, Remote Keypad returns to previous status (except when executing).
- The memory protection function (write protection) can not protect Remote Keypad parameter.
- The memory initialization function initializes Remote Keypad parameter when “sys (selecting all memories)” is selected.
Before making a service call
If a problem arises, please see the following trouble-shooting tables. If the problem can not be solved, please contact a Toshiba distributor.
Error message
Malfunction indications: Indicated by flashing LED display
Procedure to reset Remote Keypad
There are two methods to reset the micro controller unit inside Remote Keypad.
-
Method 1:
Reset the power source of Remote Keypad. -
Method 2:
If [STOP] key is pressed while an error message is displayed, “clr” flashes for one second. If you press the [STOP] key again when “clr” flashes, Remote Keypad will be reset.
Warning indications
Warning indications: Indicated by flashing LED display.
Other problems
Phenomenon | Problem and Solutions |
---|---|
Display is extinguished. | Check the connection of the serial communication |
cable. Check the kind of the serial communication cable.
Check that the power of the inverter is turned on.
% lamp and Hz lamp are not lit| When Remote Keypad is connected to the
following inverters, % lamp and Hz lamp is not lit. VF-S11, VF-nC1, VF-S9,
VF-A7, VF-P7, etc.
Key is not effective| It needs to be repaired. [EASY] key is effective only
for the inverter with [EASY] key.
Parameters can not be written| Some parameters can not be written while the
inverter is running. See the instruction manual of the inverter.
Copying the parameters between inverters of different series is impossible.
Outline drawing
Following is the outline drawing of Remote Keypad
(Unit: mm)
Mounting
Mount Remote Keypad on the front of the panel board as illustrated below.
On the front of the panel board, cut the area shown below for mounting Remote
Keypad. Then, fix Remote Keypad on the panel board with the mounting screws
(M3 x 12) supplied as accessories.
(M3 screw tightening torque: 0.6 Nּ m)
Unit: mm
(The front view of the panel board)
Specifications
Item | Specifications |
---|---|
Part number | RKP002Z |
Applicable model | Model with either an RS485 (2-wire type) connector or a |
common serial connector (optional) with a baud rate of 9600, 19200 or
38400bps.
Communication| Automatic search:
Baud rate: 9600, 19200, 38400bps Parity: even, odd, none
Communication method:
RS485 (2-wire type) or Common Serial Communication, switched by Communication Mode Switch
Service environment
| Indoor operation at an altitude of 1,000m or less and free from direct
sunlight, potentially corrosive or explosive gases, steam, dust particles,
dust/dirt, and machining fluids including grinding liquid and coolant
Ambient temperature| -10 to +50°C
Storage temperature| -25 to +65°C
Relative humidity| 20 to 93% (free from condensation and vapor)
Vibration| 5.9m/s2 (0.6G) or less (10 to 55Hz)
Cooling method| self-cooling
Warranty
Any part of the unit that is proved to be defective will be repaired free of charge under the following conditions:
- This product will be repaired free of charge, if problem/fault occurs under normal handling within one year of delivery and is caused obviously by a design or manufacturing defect.
- The warranty applies only to the delivered unit.
- For the following kinds of failure or damage, the repair cost shall be borne by the customer even within the warranty period.
- Failure or damage caused by improper or incorrect use or handling, or unauthorized repair or modification of the inverter.
- Failure or damage caused by the unit falling or an accident during transportation after thepurchase.
- Failure or damage caused by fire, salty water or wind, corrosive gas, earthquake, storm or flood, lightning, abnormal voltage supply, or other natural disasters.
- Damage due to the use of Remote Keypad for non-intended purposes.
- If an additional warranty is provided then those conditions will also apply.
Read User Manual Online (PDF format)