Danfoss SHA(X)22e…L BOCK Condensing Units
About these instructions
Read these instructions before assembly and before using the condensing unit.
This will avoid misunderstandings and prevent damage. Improper assembly and
use can result in serious or fatal injury. Observe the safety instructions
contained in these instructions and in the compressor instructions. These
instructions must be passed onto the end customer along with the unit in which
the condensing unit is installed.
Observe also the other documentation included with the condensing unit.
Note:
According to Commission Regulation (EU) 2015/1095 of May 5th 2015 implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to ecodesign requirements for professional condensing units, starting 2016 July 1st in the EU only products may be sold which fulfill minimum efficiency requirements. These minimum efficiency requirements must be documented by a certificate.
The matching certificate for your condensing unit can be created on the Internet on our software (VAP) under http://vap.bock.de/stationaryapplication/
Safety
Identification of safety instructions
DANGER
Indicates a dangerous situation which, if not avoided, will cause immediate
fatal or serious injury.
WARNING
Indicates a dangerous situation which, if not avoided, may cause fatal or
serious injury.
CAUTION
Indicates a dangerous situation which, if not avoided, may cause fairly
severe or minor injury.
ATTENTION
Indicates a situation which, if not avoided, may cause property damage.
INFO
Important information or tips on simplifying work.
Qualifications required of personnel
WARNING
Inadequately qualified personnel poses the risk of accidents, the consequence being serious or fatal injury. Work on compressors is therefore reserved for personnel which is qualified to work on pressurized refrigerant systems:
- For example, a refrigeration technician, refrigeration mechatronic engineer. As well as professions with comparable training, which enables personnel to assemble, install, maintain and repair refrigeration and air-conditioning systems. Personnel must be capable of assessing the work to be carried out and recognising any potential dangers.
Safety instructions
WARNING
Risk of accidents.
Refrigerating compressors are pressurised machines and as such call for
heightened caution and care in handling.
The maximum permissible overpressure must not be exceeded, even for testing
purposes.
Risk of burns!
- Depending on the operating conditions, surface temperatures of over 60°C on the discharge side or below 0°C on the suction side can be reached.
- Avoid contact with refrigerant necessarily. Contact with refrigerant can cause severe burns and skin damage.
Intended use
WARNING
The condensing unit may not be used in potentially explosive environments!
These assembly instructions describe the standard version of the condensing units named in the title manufactured by Bock. The condensing unit is intended for installation in a machine (within the EU according to the EU Directives 2006/42/EC Machinery Directive, 2014/68/EU Pressure Equipment Directive).
Commissioning is permissible only if the condensing unit has been installed in accordance with these assembly instructions and the entire system into which it is integrated has been inspected and approved in accordance with legal regulations.
Only refrigerants may be used which are released on http://vap.bock.de/stationaryapplication/
Any other use of the condensing unit is prohibited!
Product description
Short description
-
Condensing unit with vertical receiver
-
Condensing unit with horizontal receiver
Product description
Name plate (example)
- Type designation
- Machine number
- ND (LP): Max. admissible operating pressure suction side
HD (HP): Max. admissible operating pressure high-pressure side
Type key (example)
- HG – Hermetic Gas-Cooled (suction gas-cooled)
- X – Ester oil charge
- S – Stronger motor
- L = Aircooled condensing unit
Areas of application
Operating limits
- The operating limits of the condensing units differ to the respective compressor.
The really operating limits can be found on the Internet on our software (VAP) under vap.bock.de
Assembly
INFO
- New compressors are factory-filled with inert gas. Leave this service charge in the compressor for as long as possible and prevent the ingress of air.
- Immediately after connecting the Plusbox to the refrigeration system, close the shut-off valves in the suction, discharge lines etc. and evacuate the compressor.
- Check the condensingn unit for transport damage before starting any work.
Setting Up
|
- Do not lift manually
- Use lifting gear
- Transport preferably via forklift truck, alternatively bolted to a pallet
---|---
|
- Provide adequate clearance for maintenance work.
- Distance from wall to condenser minimum 300 mm.
|
- Do not use in a dusty, damp atmosphere or a combustible environment.
|
- Set up on an even surface or frame with sufficient load bearing capacity. Only set up on a slant after following consulting.
- Preferably on vibration damper or mounting rubbers.
|
- Sun protection: If the condensing unit is set up outdoors, it has to be protected from direct sunlight.
Maintenance
Preparation
WARNING
Before starting any work on the compressor:
-
Switch off the compressor and secure it to prevent a restart.
-
Relieve compressor of system pressure.
-
Prevent air from infiltrating the system!
After maintenance has been performed: -
Connect safety switch.
-
Evacuate compressor.
-
Release switch-on lock.
Work to be carried out
To avoid system-related problems, the following service work must be carried out on the Plusbox:
-
Cleaning: A dirty condenser leads to performance losses!
Visual inspections and possible condenser cleaning therefore required on a monthly base. We recommend using compressed air and a soft brush for cleaning. -
Further maintenance work in accordance with the instructions for assembly on the compressor.
Technical Data
Type| Fan / Condenser (230 V – 1- 50 Hz)| Receiver
capacity| Weight
---|---|---|---
Max. working current 50 Hz| Max. power consumption 50
Hz| Air flow 50 Hz
A| W| m³/h| Ltr.| kg
| | | |
SHG12P/60-4 SL| 2,60| 550| 6300| 6,0| 115
SHG12P/75-4 L| 2,60| 550| 6300| 6,0| 114
SHG12P/75-4 SL| 2,60| 550| 6300| 6,0| 115
SHG12P/90-4 L| 2,60| 550| 6300| 6,0| 115
SHG12P/90-4 SL| 2,60| 550| 6300| 6,0| 115
SHG12P/110-4 L| 2,60| 550| 6300| 6,0| 115
SHG12P/110-4 SL| 2,60| 550| 6300| 6,0| 115
SHG22e/125-4 L| 2,60| 550| 6300| 6,0| 140
SHG22e/125-4 SL| 2,60| 550| 6300| 6,0| 140
SHG22e/160-4 L| 2,60| 550| 6300| 6,0| 140
SHG22e/160-4 SL| 2,60| 550| 6300| 6,0| 142
SHG22e/190-4 L| 2,60| 550| 5900| 8,0| 149
SHG22e/190-4 SL| 2,60| 550| 5900| 8,0| 151
SHG34e/215-4 L| 2,60| 550| 5900| 8,0| 167
SHG34e/215-4 SL| 2,60| 550| 5900| 10,0| 174
SHG34e/255-4 L| 2,60| 550| 5900| 8,0| 166
SHG34e/255-4 SL| 2,60| 550| 5900| 10,0| 174
SHG34e/315-4 L| 2,60| 550| 5900| 8,0| 169
SHG34e/315-4 SL| 2 x 2,60| 2 x 550| 9700| 14,0| 182
SHG34e/380-4 L| 2 x 2,60| 2 x 550| 9700| 14,0| 179
SHG34e/380-4 SL| 2 x 2,60| 2 x 550| 10400| 14,0| 210
SHG44e/475-4 L| 2 x 2,60| 2 x 550| 10400| 14,0| 257
SHG44e/475-4 SL| 4 x 2,60| 4 x 550| 19700| 14,0| 317
Type| Fan / Condenser (230 V – 1- 50 Hz)| Receiver
capacity| Weight
---|---|---|---
Max. working current 50 Hz| Max. power consumption 50
Hz| Air flow 50 Hz
A| W| m³/h| Ltr.| kg
| | | |
SHG44e/565-4 L| 2 x 2,60| 2 x 550| 10400| 14,0| 281
SHG44e/565-4 SL| 4 x 2,60| 4 x 550| 18600| 23,0| 330
SHG44e/665-4 L| 4 x 2,60| 4 x 550| 19700| 23,0| 326
SHG44e/665-4 SL| 4 x 2,60| 4 x 550| 18600| 23,0| 328
SHG44e/770-4 L| 4 x 2,60| 4 x 550| 18600| 23,0| 329
SHG44e/770-4 SL| 4 x 2,60| 4 x 550| 21200| 35,0| 346
SHG56e/850-4 L| 4 x 2,60| 4 x 550| 18600| 23,0| 352
SHG56e/850-4 SL| 4 x 2,60| 4 x 550| 21200| 35,0| 386
SHG56e/995-4 L| 4 x 2,60| 4 x 550| 21200| 23,0| 376
SHG56e/995-4 SL| 4 x 2,60| 4 x 550| 21200| 35,0| 388
SHG56e/1155-4 L| 4 x 2,60| 4 x 550| 21200| 23,0| 381
SHG56e/1155-4 SL| 4 x 2,60| 4 x 550| 20000| 35,0| 407
SHG66e/1340-4 L| 4 x 2,60| 4 x 550| 21200| 23,0| 452
SHG66e/1340-4 SL| 4 x 2,60| 4 x 550| 20000| 35,0| 474
SHGZ7/1620-4 L| 4 x 2,60| 4 x 550| 20000| 35,0| 499
SHGZ7/1860-4 L| 4 x 2,60| 4 x 550| 20000| 35,0| 496
SHGZ7/2110-4 L| 4 x 2,60| 4 x 550| 20000| 35,0| 494
Type| Fan / Condenser (230 V – 1- 50 Hz)| Receiver
capacity| Weight
---|---|---|---
Max. working current 50 Hz| Max. power consumption 50
Hz| Air flow 50 Hz
A| W| m³/h| Ltr.| kg
| | | |
SHA22e/125-4 L| 2,60| 550| 6300| 6,0| 142
SHA22e/160-4 L| 2,60| 550| 6300| 6,0| 144
SHA22e/190-4 L| 2,60| 550| 5900| 8,0| 152
SHA34e/215-4 L| 2,60| 550| 5900| 8,0| 170
SHA34e/255-4 L| 2,60| 550| 5900| 8,0| 169
SHA34e/315-4 L| 2,60| 550| 5900| 8,0| 172
SHA34e/380-4 L| 2 x 2,60| 2 x 550| 9700| 14,0| 181
SHA44e/475-4 L| 2 x 2,60| 2 x 550| 10400| 14,0| 266
SHA44e/565-4 L| 2 x 2,60| 2 x 550| 10400| 14,0| 270
SHA44e/655-4 L| 4 x 2,60| 4 x 550| 19700| 23,0| 325
Dimensions and connections
SHG
Type
|
Dimensions
---|---
A| B| C| D| E
mm
SHG12P/60-4 SL| 1086| 1060| 745| 570| 750
SHG12P/75-4 L| 1086| 1060| 745| 570| 750
SHG12P/75-4 SL| 1086| 1060| 745| 570| 750
SHG12P/90-4 L| 1086| 1060| 745| 570| 750
SHG12P/90-4 SL| 1086| 1060| 745| 570| 750
SHG12P/110-4 L| 1086| 1060| 745| 570| 750
SHG12P/110-4 SL| 1086| 1060| 745| 570| 750
SHG22e/125-4 L| 1086| 1060| 745| 570| 750
SHG22e/125-4 SL| 1086| 1060| 745| 570| 750
SHG / SHGZ
Type
|
Dimensions
---|---
A| B| C| D| E
mm
SHG22e/160-4 L| 1086| 1060| 745| 570| 750
SHG22e/160-4 SL| 1086| 1060| 745| 570| 750
SHG22e/190-4 L| 1086| 1060| 746| 570| 750
SHG22e/190-4 SL| 1086| 1060| 746| 570| 750
SHG34e/215-4 L| 1086| 1060| 746| 570| 750
SHG34e/215-4 SL| 1086| 1060| 746| 570| 750
SHG34e/255-4 L| 1086| 1060| 746| 570| 750
SHG34e/255-4 SL| 1086| 1060| 746| 570| 750
SHG34e/315-4 L| 1086| 1060| 746| 570| 750
SHG34e/315-4 SL| 1208| 1140| 696| 750| 1043
SHG34e/380-4 L| 1208| 1140| 696| 750| 1043
SHG34e/380-4 SL| 1224| 1140| 796| 750| 1043
SHG44e/475-4 L| 1224| 1140| 796| 750| 1043
SHG44e/475-4 SL| 1249| 1140| 1306| 750| 1043
SHG44e/565-4 L| 1224| 1140| 796| 750| 1043
SHG44e/565-4 SL| 1249| 1140| 1306| 750| 1046
SHG44e/665-4 L| 1249| 1140| 1306| 750| 1046
SHG44e/665-4 SL| 1249| 1140| 1306| 750| 1046
SHG44e/770-4 L| 1249| 1140| 1306| 750| 1046
SHG44e/770-4 SL| 1249| 1140| 1606| 750| 1046
SHG56e/850-4 L| 1251| 1140| 1306| 750| 1044
SHG56e/850-4 SL| 1251| 1140| 1606| 750| 1044
SHG56e/995-4 L| 1251| 1140| 1606| 750| 1044
SHG56e/995-4 SL| 1251| 1140| 1606| 750| 1044
SHG56e/1155-4 L| 1251| 1140| 1606| 750| 1044
SHG56e/1155-4 SL| 1251| 1140| 1606| 750| 1044
SHG66e/1340-4 L| 1251| 1140| 1606| 750| 1075
SHG66e/1340-4 SL| 1251| 1140| 1606| 750| 1075
SHGZ7/1620-4 L| 1251| 1140| 1606| 750| 1225
SHGZ7/1860-4 L| 1251| 1140| 1606| 750| 1225
SHGZ7/2110-4 L| 1251| 1140| 1606| 750| 1225
SHA
Type
|
Dimensions
---|---
A| B| C| D| E
mm
SHA22e/125-4 L| 1086| 1060| 745| 570| 773
SHA22e/160-4 L| 1086| 1060| 745| 570| 773
SHA22e/190-4 L| 1086| 1060| 746| 570| 773
SHA34e/215-4 L| 1086| 1060| 746| 570| 756
SHA34e/255-4 L| 1086| 1060| 746| 570| 756
SHA34e/315-4 L| 1086| 1060| 746| 570| 756
SHA34e/380-4 L| 1208| 1140| 696| 750| 1043
SHA44e/475-4 L| 1224| 1140| 796| 750| 1043
SHA44e/565-4 L| 1224| 1140| 796| 750| 1043
SHA44e/655-4 L| 1243| 1140| 1306| 750| 1043
Connections
SHG
Type
|
Connections 1
---|---
SV| FLA| SI| Y1| Y2
mm I Inch| mm I Inch| Inch| Inch| Inch
SHG12P/60-4 SL| 16 / 5/8| 12 / 1/2| –| 7/16 UNF| 7/16 UNF
SHG12P/75-4 L| 16 / 5/8| 12 / 1/2| –| 7/16 UNF| 7/16 UNF
SHG12P/75-4 SL| 16 / 5/8| 12 / 1/2| –| 7/16 UNF| 7/16 UNF
SHG12P/90-4 L| 16 / 5/8| 12 / 1/2| –| 7/16 UNF| 7/16 UNF
SHG12P/90-4 SL| 16 / 5/8| 12 / 1/2| –| 7/16 UNF| 7/16 UNF
SHG12P/110-4 L| 16 / 5/8| 12 / 1/2| –| 7/16 UNF| 7/16 UNF
SHG12P/110-4 SL| 16 / 5/8| 12 / 1/2| –| 7/16 UNF| 7/16 UNF
SHG22e/125-4 L| 22 / 7/8| 12 / 1/2| –| 7/16 UNF| 7/16 UNF
SHG22e/125-4 SL| 22 / 7/8| 12 / 1/2| –| 7/16 UNF| 7/16 UNF
SHG22e/160-4 L| 22 / 7/8| 12 / 1/2| –| 7/16 UNF| 7/16 UNF
SHG22e/160-4 SL| 22 / 7/8| 12 / 1/2| –| 7/16 UNF| 7/16 UNF
SHG22e/190-4 L| 22 / 7/8| 16 / 5/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHG22e/190-4 SL| 22 / 7/8| 16 / 5/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHG34e/215-4 L| 28 / 1 1/8| 16 / 5/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHG34e/215-4 SL| 28 / 1 1/8| 16 / 5/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHG34e/255-4 L| 28 / 1 1/8| 16 / 5/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHG34e/255-4 SL| 28 / 1 1/8| 16 / 5/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHG34e/315-4 L| 28 / 1 1/8| 16 / 5/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHG34e/315-4 SL| 28 / 1 1/8| 16 / 5/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHG34e/380-4 L| 28 / 1 1/8| 16 / 5/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHG34e/380-4 SL| 28 / 1 1/8| 16 / 5/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHG44e/475-4 L| 35 / 1 3/8| 16 / 5/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHG44e/475-4 SL| 35 / 1 3/8| 16 / 5/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHG44e/565-4 L| 35 / 1 3/8| 16 / 5/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHG44e/565-4 SL| 42 / 1 5/8| 22 / 7/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHG44e/665-4 L| 42 / 1 5/8| 22 / 7/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHG44e/665-4 SL| 42 / 1 5/8| 22 / 7/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHG44e/770-4 L| 42 / 1 5/8| 22 / 7/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHG44e/770-4 SL| 42 / 1 5/8| 22 / 7/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHG56e/850-4 L| 54 / 2 1/8| 22 / 7/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHG56e/850-4 SL| 54 / 2 1/8| 22 / 7/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHG56e/995-4 L| 54 / 2 1/8| 22 / 7/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHG56e/995-4 SL| 54 / 2 1/8| 22 / 7/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHG56e/1155-4 L| 54 / 2 1/8| 22 / 7/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHG56e/1155-4 SL| 54 / 2 1/8| 22 / 7/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHG
SHGZ
SHAType|
Connections 1
---|---
SV| FLA| SI| Y1| Y2
mm I Inch| mm I Inch| Inch| Inch| Inch
SHG66e/1340-4 L| 54 / 2 1/8| 22 / 7/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHG66e/1340-4 SL| 54 / 2 1/8| 22 / 7/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHGZ7/1620-4 R…L| 54 / 2 1/8| 22 / 7/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHGZ7/1860-4 R…L| 54 / 2 1/8| 22 / 7/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHGZ7/2110-4 R…L| 54 / 2 1/8| 22 / 7/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHA22e/125-4 L| 16 / 5/8| 12 / 1/2| –| 7/16 UNF| 7/16 UNF
SHA22e/160-4 L| 16 / 5/8| 12 / 1/2| –| 7/16 UNF| 7/16 UNF
SHA22e/190-4 L| 16 / 5/8| 16 / 5/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHA34e/215-4 L| 22 / 7/8| 16 / 5/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHA34e/255-4 L| 22 / 7/8| 16 / 5/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHA34e/315-4 L| 22 / 7/8| 16 / 5/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHA34e/380-4 L| 22 / 7/8| 16 / 5/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHA44e/475-4 L| 35 / 1 3/8| 16 / 5/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHA44e/565-4 L| 35 / 1 3/8| 16 / 5/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SHA44e/655-4 L| 35 / 1 3/8| 22 / 7/8| 1/2 NPTF| 7/16 UNF| 7/16 UNF
SV = Suction line shut off valve
FLA = Liquid outlet
SI = Connection safety valve
Y1 = Connection liquid side, lockable
Y2 = Connection liquid side, not lockable
1 Further compressor connections can be found in the assembly instructions of the compressor.
Customer Support
Danfoss A/S
Climate Solutions • danfoss.com • +45 7488 2222
Any information, including, but not limited to information on selection of
product, its application or use, product design, weight, dimensions, capacity
or any other technical data in product manuals, catalogues descriptions,
advertisements, etc. and whether made available in writing, orally,
electronically, online or via download, shall be considered informative, and
is only binding if and to the extent, explicit reference is made in a
quotation or order confirmation. Danfoss cannot accept any responsibility for
possible errors in catalogues, brochures, videos and other material. Danfoss
reserves the right to alter its products without notice. This also applies to
products ordered but not delivered provided that such alterations can be made
without changes to form, fit or function of the product.
All trademarks in this material are property of Danfoss A/Sor Danfoss group
companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All
rights reserved.
References
- vap.bock.de
- VAP for Stationary Applications 11.13.3 (online) - Start
- Danfoss BOCK® Compressors: Eco-Friendly Solutions for Refrigeration Systems | Danfoss
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>