FHM-CN1
Pre-assembled Mixing Shunt
Installation overview
Installation procedure
The FHM-CN1 must be connected to a system according to the illustrations.
-
Pre-mounted union nut (1) for connection to the primary side pipe. The union nut to control valve must be tightened with a torque of at least 85 Nm without any sealing materials.
-
Pre-mounted union nut (2) for connection to the secondary side pipe or directly on a Danfoss manifold.
The nut to mixing shunt must be tightened with a torque of 15 to 25 Nm with enclosed rubber gasket. -
FTC thermostatic sensor is in package.
Mount it on the valve according to the enclosed instruction.
A Flow of primary side
B Flow of secondary side
C Return of primary side
D Return of secondary side
Tips
- If the primary side pipe is coming from the bottom, the bend 4 (088U0821) can be ordered as an accessory. The bend must be tightened to the mixing shunt with a torque of 30 to 40 Nm.
- Connection 5 and 6 are tightened from the factory. Please double check them during installation. If loosening or leaks occur due to transportation or moving, please tighten:
• connection 5 at a torque of at least 85 Nm
• connection 6 at a torque of 15 to 25 Nm
A Flow of primary side
B Flow of secondary side
C Return of primary side
D Return of secondary side
RoHS compliance
Part Name | Hazardous Substances Table |
---|---|
Pb | Hg |
Pump | X |
Brass parts | X |
O: Indicates that this hazardous substance contained in all of the homogeneous
material for this part is below the limit requirement in GB/T 26572.
X: Indicates that this hazardous substance contained in at least one of the
homogeneous material for this part is above the limit requirement in GB/T
26572.
Danfoss AS
Climate Solutions
danfoss.com
+45 7488 2222
Any information, including, but not limited to information on selection of
product, its application or use, product design, weight, dimensions, capacity
or any other technical data in product manuals, catalogues descriptions,
advertisements, etc. and whether made available in writing, orally,
electronically, online or via download, shall be considered informative, and
is only binding if and to the extent, explicit reference is made in a
quotation or order confirmation. Danfoss cannot accept any responsibility for
possible errors in catalogues, brochures, videos and other material.
Danfoss reserves the right to alter its products without notice. This also
applies to products ordered but not delivered provided that such alterations
can be made without changes to form, fit or function of the product.
All trademarks in this material are property of Danfoss A/S or Danfoss group
companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All
rights reserved.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>