Danfoss AB-QM VA41 Actuator Selection Installation Guide
- June 1, 2024
- Danfoss
Table of Contents
Danfoss AB-QM VA41 Actuator Selection
Installation Guide
ABNM A5 LOG/LIN for AB-QM, 0-10 V Proportional Fits AB-QM DN 10-32 / ½-1¼ inch
Specifications
Certifications | TÜV SÜD – Production monitored, Safety tested |
---|---|
Environmental Protection | IP54 in any position with the cable plugged in |
Mounting/demounting
- Remove the cover from the Danfoss AB-QM VA41 valve.
- Ensure the correct orientation of the valve insert by matching the shape of the insert with the actuator housing. Do not force.
- Place the actuator onto the valve insert.
- Press down until a click is heard, indicating the parts are securely fastened.
Electrical Connection & Dimensions
- Temperature range for operation: min. 0°C (32°F) to max. 60°C (140°F)
- Control signal: 0-10 V (DC)
- Power supply: 24 V (AC or DC depending on the type)
- Dimensions: Max 61.8 mm (2.43 inch) width, Max 60 mm (2.35 inch) height
Unlock the NC version (First Open Function)
- Rotate the actuator approximately 3mm to unlock.
- Apply power for more than 6 minutes to initiate the first open function.
- Rotate the actuator back approximately 0.5mm after the function is triggered.
NO/NC version
The maximum operating temperature for both NO (Normally Open) and NC (Normally Closed) versions is 60°C.
Auto Calibration
The actuator has an auto-calibration feature for NO and NC versions, detecting the open/close point during the calibration process, approximately 6 minutes for unlocking NC, and around 30 minutes for regular operation.
FAQ
How do I know if the actuator is securely attached to the valve?
You should hear a ‘click’ sound indicating that the actuator is properly attached.
What is the temperature range within which the actuator can operate?
The actuator can operate within a temperature range of 0°C (32°F) to 60°C (140°F).
What are the voltage requirements for the actuator?
The control signal is 0-10 V (DC), and the power supply is 24 V (AC or DC depending on the type).
How does the auto-calibration feature work?
The auto-calibration feature automatically detects the open/closed point. It takes approximately 6 minutes to unlock the NC version and 30 minutes for regular operation calibration.
What should I do if the actuator does not fit onto the valve insert?
Do not force the actuator onto the valve insert; ensure the shapes match and try again gently. If it still does not fit, check for correct compatibility.
Installation Guide
ABNM A5 LOG/LIN for AB-QM, 0-10 V Proportional
Fits to AB-QM DN 10-32 / ½-1¼ inch
Mounting /demounting
Electrical Connection & Dimensions
Unlock NC version (First Open Function)
NO/NC version
Auto Calibration
- Danfoss can accept no responsibility for possible errors in catalogs, brochures, and other printed material. Danfoss reserves the right to alter its products without notice.
- This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.
- All trademarks in this material are the property of the respective companies.
- Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>