Danfoss AB-QM VA41 Actuator Selection Installation Guide

June 1, 2024
Danfoss

Danfoss AB-QM VA41 Actuator Selection

Installation Guide

ABNM A5 LOG/LIN for AB-QM, 0-10 V Proportional Fits AB-QM DN 10-32 / ½-1¼ inch

Specifications

Certifications TÜV SÜD – Production monitored, Safety tested
Environmental Protection IP54 in any position with the cable plugged in

Mounting/demounting

  1. Remove the cover from the Danfoss AB-QM VA41 valve.
  2. Ensure the correct orientation of the valve insert by matching the shape of the insert with the actuator housing. Do not force.
  3. Place the actuator onto the valve insert.
  4. Press down until a click is heard, indicating the parts are securely fastened.

Electrical Connection & Dimensions

  • Temperature range for operation: min. 0°C (32°F) to max. 60°C (140°F)
  • Control signal: 0-10 V (DC)
  • Power supply: 24 V (AC or DC depending on the type)
  • Dimensions: Max 61.8 mm (2.43 inch) width, Max 60 mm (2.35 inch) height

Unlock the NC version (First Open Function)

  1. Rotate the actuator approximately 3mm to unlock.
  2. Apply power for more than 6 minutes to initiate the first open function.
  3. Rotate the actuator back approximately 0.5mm after the function is triggered.

NO/NC version

The maximum operating temperature for both NO (Normally Open) and NC (Normally Closed) versions is 60°C.

Auto Calibration

The actuator has an auto-calibration feature for NO and NC versions, detecting the open/close point during the calibration process, approximately 6 minutes for unlocking NC, and around 30 minutes for regular operation.

FAQ

How do I know if the actuator is securely attached to the valve?

You should hear a ‘click’ sound indicating that the actuator is properly attached.

What is the temperature range within which the actuator can operate?

The actuator can operate within a temperature range of 0°C (32°F) to 60°C (140°F).

What are the voltage requirements for the actuator?

The control signal is 0-10 V (DC), and the power supply is 24 V (AC or DC depending on the type).

How does the auto-calibration feature work?

The auto-calibration feature automatically detects the open/closed point. It takes approximately 6 minutes to unlock the NC version and 30 minutes for regular operation calibration.

What should I do if the actuator does not fit onto the valve insert?

Do not force the actuator onto the valve insert; ensure the shapes match and try again gently. If it still does not fit, check for correct compatibility.

Installation Guide

ABNM A5 LOG/LIN for AB-QM, 0-10 V Proportional

Fits to AB-QM DN 10-32 / ½-1¼ inch

Mounting /demounting

Danfoss-AB-QM-VA41-Actuator-Selection-fig-2

Electrical Connection & Dimensions

Danfoss-AB-QM-VA41-Actuator-Selection-fig-3

Unlock NC version (First Open Function)Danfoss-AB-QM-VA41-Actuator-
Selection-fig-4

NO/NC versionDanfoss-AB-QM-VA41-Actuator-Selection-
fig-5

Auto Calibration

Danfoss-AB-QM-VA41-Actuator-Selection-fig-6

  • Danfoss can accept no responsibility for possible errors in catalogs, brochures, and other printed material. Danfoss reserves the right to alter its products without notice.
  • This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.
  • All trademarks in this material are the property of the respective companies.
  • Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals