FIELD CONTROLS CAS-6 Combustion Air System Instruction Manual

June 1, 2024
FIELD CONTROLS

FIELD CONTROLS CAS-6 Combustion Air System

FIELD CONTROLS CAS-6 Combustion Air System

INSTRUCTION MANUAL

Model: CAS-6, CAS-6SK, CAS-7, and CAS-7SK

This product is designed for use with any oil or gas fi red furnace, water heater, or boiler with 24 VAC or 120 VAC control systems. It may also be used with millivolt water heaters and more than one appliance. The CAS unit mechanically draws air into a structure and disperses it near the combustion air intake of an appliance. Refer to Diagrams A & B for guidance in setting up the CAS system based on the size and length of the connecting duct work and the input rating of the appliance.

ITEMS INCLUDED:

  • 1- CAS Unit (ETL Listed) “Fan-In-A-Drum”
  • 1- Star Kap (only on SK Models)
  • 2- Mounting Brackets for CAS Unit
  • 2- Wire/Conduit connectors
  • 1- 24VAC Control Relay (SPDT)
  • 1- 120VAC Control Relay (SPDT)

READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE PROCEEDING WITH

THE INSTALLATION.

This device MUST be installed by a qualifi ed agency in accordance with the manufacturer’s installation instructions. The defi nition of a qualifi ed agency is: any individual, fi rm, corporation or company which either in person or through a representative is engaged in, and is responsible for, the installation and operation of HVAC appliances, who is experienced in such work, familiar with all the precautions required, and has complied with all the requirements of the authority having jurisdiction.

Please retain these instructions after installation.

Installed By:_ Phone:___ Installation Date:___

GENERAL SYSTEM OPERATION

1. The thermostat (wall thermostat, or aquastat) calls for heat and energizes a relay which activates the CAS unit. After the CAS fan has come up to speed, an internal air pressure switch closes and completes the circuit to allow the burner to fi re. If the appliance is power vented, the venter will typically activate before the CAS unit.
2. After the heating requirement has been satisfi ed, the thermostat circuit will open and deactivate the burner and CAS unit.
3. For power vented systems with a post purge device, the power venter will operate for a period of time determined by the post purge timer setting after the burner has shut off to purge remaining fl ue gases from the vent system.

INSTALLATION SAFETY INSTRUCTIONS

CAUTION: This device must be installed by a qualifi ed installer in accordance with the manufacturer’s installation instructions.

1. This combustion air system must be installed by a qualifi ed installer. “Qualifi ed Installer” shall mean an individual who has been properly trained or a licensed installer.
2. Plan the system layout before installation to avoid the possibility of accidental contact with concealed wiring or plumbing inside walls.
3. Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage.

SIZING AND SETUP

Diagram A shows the maximum equivalent length and size of duct pipe that should be used when installing the CAS-6 system; Diagram B shows the same for the CAS-7. Using this table will help ensure that the proper amount of air is drawn into the structure as needed by the appliance. The defi ned regions shown correspond to the CAS’s airfl ow characteristics when using various sizes of duct pipe for the CAS-6 and CAS-7. Follow the guidelines below to properly size and set up the CAS system.

1. Determine the input fi ring rate of the appliance, or the total fi ring rate of multiple appliances that will be used.
2. Determine the location of the CAS unit according to the guidelines in the Installation section.
3. Determine where the intake air StarKap will be located based on the recommendations in the Installation section.
4. On Diagram A or B (as appropriate), locate the point that corresponds to the fi ring rate along the horizontal axis and draw a vertical line through this point.
5. The line should pass through at least one of the pipe size regions on the table. The regions correspond to the maximum equivalent lengths of the given diameter duct pipe that will be adequately sized for the application.
6. Calculate the equivalent length of the smaller diameter duct pipe that may be used with the particular CAS system, including elbows, reducer/increaser and other fi ttings (except the StarKap, see the Field Controls Contractor Reference Guide). The eff ects of the StarKap are already fi gured into the diagram,
so do not attempt to include any value for the StarKap in your calculation for equivalent length. Draw a horizontal line through the point corresponding to the equivalent length on the vertical axis.
7. Locate the intersection of the two drawn lines. If the intersection lies in the region for the equivalent length of pipe for which the equivalent length was calculated, then that diameter of duct pipe will be of suffi cient size for the application. If not, then repeat step 7 using a larger diameter duct, then proceed to step 9.
8. If the intersection of the two lines falls into the larger duct region, then that diameter duct will be of su ffi cient size for the application. If it falls to the right of the larger pipe region, then even larger pipe or additional CAS units will be required for the application. For assistance in this case, call Field Controls Technical Support at 1-800-742-8368.

Example: An oil fi red appliance fi ring at 10.5 gph where a CAS-7 unit needs to be placed at a location requiring 80′ of pipe from the StarKap, using two 90o elbows:

From Diagram B, a vertical line is drawn through the point at 10.5 gph on the Oil Firing Rate scale. For 80 feet of 10″ pipe, two 90 degree elbows, and two increaser/reducers, the equivalent length is 80 + 18 + 18 +
6 + 6 = 128′ of equivalent length. A horizontal line drawn through the point at 128′ on the Equivalent Length scale intersects the vertical line in the 12″ duct region of the diagram. Since the intersection is not in the 10″ duct region, recalculate the equivalent length using 12″ duct: 80 + 21 + 21 + 7 + 7 = 136′ of equivalent length. A horizontal line drawn through the 136 point on the Equivalent Length scale intersects the vertical line within the 12″ duct region of the diagram; therefore, 12″ duct will be of suffi cient size for the application.

DIA G RA M

DIA GRAM B

Equivalent Feet for Vent Pipe Fittings

Vent PIpe Fittings| Vent Pipe Diameter
8”| 10”| 12”| 14”
Tee| 50| 63| 75| 89
Y-Connection| 26| 32| 39| 45
90° Elbow| 14| 18| 21| 25
45° Elbow| 7| 9| 10| 13

Table 1

MAXIMUM EQUIVALENT LENGTH OF PIPE, INCLUDING STARKAP ®

CAS-6 OIL
(gph)| CAS-6 GAS
(BTU/hr)| 8″ duct| 10″ duct| 12″ duct
3| 420,000| 410| 1253| 3119
3.25| 455,000| 344| 1051| 2616
3.5| 490,000| 291| 890| 2217
3.75| 525,000| 249| 760| 1893
4| 560,000| 214| 653| 1627
4.25| 595,000| 185| 584| 1405
4.5| 630,000| 160| 489| 1217
4.75| 665,000| 139| 424| 1057
5| 700,000| 121| 369| 919
5.25| 735,000| 105| 321| 800
5.75| 805,000| 79| 241| 601
6| 840,000| 58| 176| 519
6.50| 910,000| 49| 151| 377
CAS-7 OIL
(gph)| CAS-7 GAS
(BTU/hr)| 10″ duct| 12″ duct| 14″ duct
6| 840,000| 469| 1167| 2523
6.5| 910,000| 381| 948| 2050
7| 980,000| 311| 776| 1678
7.5| 1,050,000| 256| 637| 1378
8.25| 1,155,000| 191| 476| 1029
9| 1,260,000| 142| 354| 766
9.75| 1,365,000| 104| 260| 563
10.5| 1,470,000| 74| 186| 403
11.25| 1,575,000| 51| 127| 274
12| 1,680,000| 31| 78| 207
12.75| 1,785,000| 15| 39| 114
12.88| 1,803,000| 13| 33| 72

INSTALLATION

PLACEMENT OF THE CAS UNIT

The motorized CAS unit should be located on a fl at horizontal surface near the combustion air intake of the appliance. Two mounting brackets are provided for securing the unit against a solid structure, such as a wall, column, or the side of the appliance itself. Use the included screws to attach the brackets to the CAS housing as shown in Figure 1. Secure the brackets to a solid structure with appropriate fasteners. It is not required to use the brackets as long as the unit is located so that it may not be bumped, moved, or tipped over.

INTAKE AIR STARKAP LOCATION

The StarKap should be located on an outside wall or roof maintaining clearances to other intake and exhaust vents in accordance
with the National Fuel Gas Code, ANSI Z223.1, manufacturer’s recommendations and/or local codes which are applicable. The StarKap should be located at least 10′ from a building exhaust outlet, equipment vent, or chimney termination.

INSTALLATION OF INTAKE AIR STARKAP

After determining the location of the StarKap, cut an appropriately sized hole in the wall or roof, taking precautions to avoid interference with wiring or other plumbing in the structure to be cut. Pre-attach a short length of duct to the StarKap if necessary. Insert the StarKap and secure with appropriate fasteners. Flash in the opening in accordance with local building codes.

INSTALLATION OF DUCT

Refer to Diagram A or B to determine what size pipe is needed. Connect the duct pipe from the top of the CAS unit to the StarKap. If using pipe of diff erent diameter than the CAS component connections, attach increaser/ reducer fi ttings as close to the CAS unit and to the StarKap as possible. The duct should be supported with appropriate mounting straps from fl oor joists, walls, or other solid structures. The straps should be placed so as to keep the duct work out of passageways. (See Figure 2) For best performance, install elbows or tees no closer than 3 pipe diameters from the inlet of the CAS unit.

WIRING

Wire the CAS unit in accordance with the National Electrical Code and applicable local codes. UNIT MUST BE GROUNDED. Check the ground circuit to make certain that the unit has been properly grounded. The wiring should be protected by an over-current circuit device rated at 20 amperes. CAUTION must be taken to ensure that the wiring does not come in contact with any heat source. All line voltage and control circuits between the CAS unit and the appliance MUST be wired in accordance with the National Electrical Code for Class I wiring or higher, according to the installation environment.

1. Remove the wiring access cover to access the wiring terminals.
2. Select the appropriate control relay for the appliance control system voltage from the two relays supplied with the CAS system (see illustration). Use the 24VAC relay for a 24V control system (typical gas-fi red),
or the 120VAC relay for a 120V control system (typical oil-fi red). Install the selected relay into the socket provided on the wiring panel, and secure with the wire retaining clip.
3. Use the enclosed conduit connectors or like connectors to route the appropriate wires through the CAS housing. The incoming ground wire must be attached to the green grounding screw located near the wire terminals. The following sections describe the most common applications. The references to various series of control kits implies that any kit in that series may be used. Such as when a fi gure refers to a CK-60 series kit, a CK-60, 61, 62, etc. may be used. If further information or additional wiring diagrams are needed please consult Field Controls’ technical support.

INTERNAL WIRING CONNECTIONS FOR THE CAS UNIT

Refer to Figure 3 for the internal wiring of the CAS-6/7 unit.

EXTERNAL WIRING CONNECTIONS

Refer to Figure 4 for typical 120 VAC oil fi red burner or Figure 5 for 24 VAC gas fi red burner connections that should be used when connecting the CAS unit. Refer to Figure 6 for connecting a single 120 VAC appliance
to the CAS, or Figure 7 for 24 VAC. The three wires BURNER, WHITE, and ORANGE in Figure 4 correspond to the same wires shown in Figures 6 & 10. The three wires labeled 1, 2, and 3 in Figure 5 correspond to the same wires shown in Figures 7-9. Refer to Figures 8-10 for connecting multiple appliances to one CAS unit. Note that an RJR-5 or RJR-6 relay and/or a CAC-24, CAC-120 or DIP-1 are required on certain multiple-appliance applications. Figure 11 shows how the pressure switch port on the CAC/DIP-1 should be attached to the CAS. Note that the correct 1⁄4″ plastic tubing on the top of the CAS unit must be cut and a 3-way male barb TEE suitable for 1⁄4″ tubing installed as shown in order to connect the CAC pressure port/DIP-1.

Figure 4

Figure 6

Figure 7

Figure 8

Figure 9

Figure 10

MAINTENANCE

1. Inspect the system annually to ensure proper operation by observing that the fan activates when a call for heat occurs and deactivates when the call for heat is satisfi ed.
2. Disconnect power to the CAS unit and repeat Step 1. NOTE: The unit should not run and the appliance should not fi re in this condition.
3. Inspect the duct pipe for loose joints, damage, and security to the CAS unit and StarKap.
4. Clear any obstructions, if present, from the inlet of the StarKap and the outlet of the CAS unit.
5. Periodically, the fan blade chamber may need cleaning. First, disconnect the power supply to the CAS. Next, disconnect the duct pipe from the unit. Then remove the top pan and clean the fan housing area as needed. Reattach the top pan, reconnect the duct pipe and the power supply.

CAUTION: A minimum clearance of 1″ must be maintained between the bottom of the fan blade and the top of the metal surface underneath. FAILURE TO MAINTAIN THIS CLEARANCE MAY RESULT IN A FIRE HAZARD AND WILL VOID THE WARRANTY.

REPLACEMENT PARTS

The following items are available for replacement, if needed. In order to replace these parts, power must be disconnected and the unit must be disassembled. If this is necessary, take note of the positions and locations of whatever items that may need to be removed to replace other items. If in doubt, please consult Field Controls Technical Support at 1-800-742-8368.

MODEL ITEM DESCRIPTION PART NUMBER
CAS-6 AC Motor 46363400
Blower Wheel 46363600
Pressure Switch 46363500
Timer Relay 46144700
24 VAC Control Relay SPDT 46080200
120 VAC Control Relay SPDT 46111100
CAS-7 AC Motor 46363400
Blower Wheel 46363700
Pressure Switch 46363500
Timer Relay 46144700
24 VAC Control Relay SPDT 46080200
120 VAC Control Relay SPDT 46111100

Specifications:

  • Model: CAS-6, CAS-6SK, CAS-7, CAS-7SK

  • Compatibility: Oil or gas fired furnace, water heater, boiler
    with 24 VAC or 120 VAC control systems, millivolt water
    heaters

  • Items Included:

    • CAS Unit (ETL Listed) Fan-In-A-Drum
    • Star Kap (only on SK Models)
    • Mounting Brackets for CAS Unit
    • Wire/Conduit connectors
    • 24VAC Control Relay (SPDT)
    • 120VAC Control Relay (SPDT)

Warranty

For warranty information about this or any Field Controls product, visit: www.fieldcontrols.com/warranty


FAQ:

Q: Can this system be used with both oil and gas appliances?

A: Yes, this product is designed for use with both oil and gas fired appliances.

Q: Is professional installation required?

A: Yes, this system must be installed by a qualified installer to ensure proper setup and safety.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

FIELD CONTROLS User Manuals

Related Manuals