AMETEK 42-694 Hermetically Sealed Switches
Introduction
Read this Manual Before Installing
This manual provides information on Hermetically Sealed Switch Mechanisms. It
is important that all instructions are read carefully and followed in
sequence.
Conventions Used in this Manual
Certain conventions are used in this manual to convey specific types of
information. General technical material, support data, and safety information
are presented in narrative form. The following styles are used for notes,
cautions, and warnings.
Notes
Notes contain information that augments or clarifies an operating step. Notes
do not normally contain actions. They follow the procedural steps to which
they refer.
Cautions
Cautions alert the technician to special conditions that could injure
personnel, damage equipment, or reduce a component’s mechanical integrity.
Cautions are also used to alert the technician to unsafe practices or the need
for special protective equipment or specific materials. In this manual, a
caution indicates a potentially hazardous situation which, if not avoided, may
result in minor or moderate injury.
Warnings
Warnings identify potentially dangerous situations or serious hazards. In this
manual, a warning indicates an imminently hazardous situation which, if not
avoided, could result in serious injury or death.
WARNING! Explosion hazard. Do not connect or disconnect equipment unless
power has been switched off or the area is known to be non-hazardous.
Low Voltage Directive
For use in Installation Category II, Pollution Degree 2. If equipment is used
in a manner not specified by manufacturer, protection provided by equipment
may be impaired.
Warranty
All Magnetrol mechanical level and flow controls are war-ranted free of
defects in materials or workmanship for three full years from the date of
original factory ship-ment.
If returned within the warranty period; and, upon factory inspection of the
control, the cause of the claim is determined to be covered under the
warranty; then, Magnetrol will repair or replace the control at no cost to the
purchaser (or owner) other than transportation.
Magnetrol shall not be liable for misapplication, labor claims, direct or
consequential damage or expense arising from the installation or use of
equipment. There are no other warranties expressed or implied, exceptspecial
writ-ten warranties covering some Magnetrol products.
Quality Assurance
The quality assurance system in place at Magnetrol guarantees the highest
level of quality throughout the company. Magnetrol is committed to providing
full customer satisfaction both in quality products and quality service.
Magnetrol’s quality assurance system is registered to ISO 9001 affirming its
commitment to known inter-national quality standards providing the strongest
assurance of product/service quality available.
Copyright © 2021 AMETEK Magnetrol USA, LLC.
All rights reserved.
Performance specifications are effective with date of issue and are subject to
change without notice. Magnetrol® reserves the right to make changes to the
product described in this manual at any time without notice. Magnetrol makes
no warranty with respect to the accuracy of the information in this manual.
Reference Information
Principle of Operation
Figures 1 & 2 illustrate the simple and foolproof operating principle of mechanical level switches. Switching action is obtained through the use of a magnetic sleeve ➀, actuated by a float, displacer, or flow sensing device ➁, and a switching mechanism ➂. The basic component assemblies are separated by a non-magnetic, pressure tight enclosing tube ➃. The switch mechanism ➂ consists of a magnet ➄ and a snap acting (dry-contact) microswitch. The magnet is mounted on a swinging arm, which operates on a preci-sion stainless steel pivot. The microswitch is activated by the swinging arm moving the switch lever of the microswitch.
Operating Cycle
As level of a liquid in a vessel rises ( Figure 1 ), the float rides on
the liquid surface moving the magnetic sleeve upward in the enclosing tube and
into the field of the switch mechanism magnet. As a result, the magnet is
drawn in tightly to the enclosing tube causing the set screw to actuate the
switch arm, making or breaking the electrical circuit. As the liquid level
recedes ( Figure 2 ), the float and magnetic sleeve move downward until
the switch magnet releases and is drawn outward, away from the enclosing tube
by a tension spring. This in turn causes the set screw to move the switch
actuating arm in the opposite direction, thus reversing the switch action.
Switch mechanisms may include a single switch or multiple switches, depending
on operational requirements and the switching action desired.
Description
Magnetrol mechanical level controls are available with snap-action micro switches, hermetically sealed in a posi-tively pressurized capsule for extended switch mechanism and contact life.
Features
- Process temperatures from -50° to +550° F (-46° to + 288° C).
- Positively pressurized capsule isolates all moving parts of the switch mechanism from the environment.
- Glass-to-metal feed through prevents outside environment from contacting the switch mechanism and isolates the wiring.
- Designed to the hermetic sealing requirements of MIL-S-8805D.
- Direct replacement for most standard switches.
- Switch mechanism enclosed in a 316 stainless steel container.
- Available with SPDT or DPDT contacts.
- Standard HS switch contacts are silver (contact factory for optional gold contacts).
- 12″ (305 mm) long exposed wiring leads allow for connection away from the switch enclosure.
- CSA, FM, ATEX and IEC approved for hazardous and non-hazardous locations on selected models.
- Strain relief design prevents shearing from vibration and extends wiring life.
Applications
- Feedwater heater high and low alarm
- Primary steam drip pot
- Refinery applications
- Paper processing H2S atmosphere
- Offshore salt atmosphere
- Chemical plant corrosive atmosphere
- High temperature reactors, high and low alarm
Switch Specifications
Switch Series
➀
| ****
Switch Codes
| ****
Switch Type
| ****
Contact Material
| ****
Process Temperature Range ➁
| ****
Load
| Rating
---|---|---|---|---|---|---
Volts AC| Volts DC
120| 240| 480| 24| 120| 240
HS
| HA, HB, HE, HM, HS, HW| ****
Hermetic
| ****
Silver
| -50° to +550° F ➂
(-46 to +288° C)
| Non-inductive Amp Inductive Amp
Horsepower
| 5.0
—
1⁄8
| 5.0
—
1⁄4
| —
—
—
| 5.0
3.0
—
| 0.5
—
—
| 0.25
—
—
(X)HS
(x=gold contacts)
| Consult Factory| ****
Hermetic
| Gold Overlay| -50° to +550° F ➂
(-46 to +288° C)
| Non-inductive Amp Inductive Amp| 1.0
—
| —
—
| —
—
| 2.0
1.0
| —
—
| —
—
- For currents under 100 mA, gold contact switches should be used.
- Process temperatures are based on -40° to +160° F (-40° to +71° C) ambient temperatures
- On steam applications, temperature down-rated to +400° F (+204° C) process at +100° F (+38° C) ambient
Wiring
Circuits shown are for direct acting level switches and are reversed in side mounting float-in-tank models, which utilize a reversing float pivot.
Switch with Terminal Block
-
Make sure power to control wires is disconnected.
-
Remove switch housing cover.
- NEMA 4X – Remove screw, washer, and grommet at top of housing. Set aside.
- NEMA 4X/7/9 – Unscrew cover and set aside.
-
Bring in control wires through conduit connection.
-
Wire the switch as shown in figures below:
- SPDT Switch – Refer to Figure 5.
- DPDT Switch – Refer to Figure 6.
NOTE: Double pole action is obtained by simultaneous operation of the right and left side SPDT switches.
-
Dress wiring to ensure no interference or contact with switch housing cover during replacement.
NOTE: Observe all applicable electrical codes and proper wiring procedures. -
Prevent moisture seepage into the enclosure by installing approved seal-drain fittings in the conduit run leading into the unit.
Caution: In hazardous areas, do not power the unit until the enclo-sure cover is screwed down securely and properly sealed. -
Replace housing cover.
-
Turn on power to the unit.
-
Test switch action by varying liquid level in float chamber.
-
Check the cover to base fit to be certain gasketed joint is tight. A positive seal is necessary to prevent infiltration of mois-ture laden air or corrosive gases into switch housings.
NOTE: If switch mechanism fails to function properly, check vertical alignment of control housing.
Switch with Wiring Leads
-
Make sure power to control wires is disconnected.
-
Remove switch housing cover.
- NEMA 4X – Remove screw, washer, and grommet at top of housing. Set aside.
- NEMA 4X/7/9 – Unscrew cover and set aside.
-
Wiring leads will extend through conduit connection of the switch housing base. Each wiring lead is marked with a number from 1 to 3 for SPDT switches, or 1 to 6 for DPDT switches. Refer to Figures 7–9. These numbers correspond to the numbers marked on the terminal block models.
-
Wire the switch as shown in Figures 7–9.
NOTE: Observe all applicable electrical codes and proper wiring procedures.
Caution: In hazardous areas, do not power the unit until the enclo-sure cover is screwed down securely and properly sealed. -
Replace housing cover.
-
Turn on power to the unit.
-
Test switch action by varying liquid level in the float chamber of the control.
-
Check cover to base fit to be certain gasketed joint is tight.
NOTE: If switch mechanism fails to function properly, check vertical alignment of control housing.
Replacement Parts
Replacement parts for hermetically sealed switch mecha-nisms are available as a kit only. The kit consists of a switch assembly, a tubular spacer, and a flat switch washer. When ordering a kit, please be sure to specify:
- The model number of the level control in which the switch is installed, for example B75-1B20-HSA.
- The serial number of the level control in which the switch is installed (located on the plate attached to the control).
- The model code of the switch being replaced, e.g., HSA.
- The part number of the replacement switch kit.
- The quantity of replacement switch kits.
Replacement of the Switch Mechanism
Should the switch need to be replaced, it may be done by performing the following steps:
-
Disconnect all power to the control.
-
Remove switch housing cover.
-
Remove all control wiring from the switch terminal block or wiring leads.
-
Loosen the clamp screw at the top of the switch by turning it counterclockwise. Refer to Figure 4 on page 4.
-
If replacing an existing single hermetically sealed switch: Lift the switch assembly and the switch spacer or washer off of the enclosing tube. Discard these parts.
If replacing a single switch which used a baffle plate: Lift the entire switch assembly and the baffle plate off the enclosing tube. Retain baffle plate for identification of type. Discard the switch assembly. Refer to Figure 1 0.
NOTE: If replacing two switches which were nested (terminals opposite), the top switch will activate when the level is 1″ (25 mm) higher than the original actuation level.
If replacing two existing hermetically sealed switches with wiring leads: Lift both switch assemblies and the switch spacer or washer off of the enclosing tube. Discard these parts.
If replacing two (terminals in line) stacked switches which used a baffle plate: Lift both switch assemblies and the baffle plate off of the enclosing tube. Discard these parts. -
For all switch housings with baffle plates, examine the baffle plate to determine which type it is. A “Type A” baffle plate has a bracket riveted to the bottom of the plate. See Figure 12 on page 8. A “Type B” baffle plate has no such bracket. See Figure 13 on page 8.
For all switch housings with Type A baffle plates: Slide the new tubular switch spacer over the enclosing tube. Discard the switch washer included in the replacement switch parts kit.
For switch housings with Type B baffle plates: Slide the new switch washer over the enclosing tube. Discard the tubular switch spacer included in the replacement switch parts kit.
Caution: When replacing switches which used baffle plates, either the switch spacer or the washer must be used to ensure that the actuation levels for the control remain the same. -
Single switches: Slide the new hermetically sealed switch over the enclosing tube until it rests on top of the switch spacer or washer. Refer to Figure 11
Two switches with wiring leads: Slide one new hermetically sealed switch over the enclosing tube until it rests on top of the switch spacer or washer. Slide the second switch over the enclosing tube until it rests on top of the first switch. Discard the spacer and washer included in the second switch’s parts kit.
Caution: When replacing a hermetically sealed switch with wiring leads, be sure the side of the switch with the clamp screw is on top. The switch will not actuate if it is installed upside down. -
Tighten the clamp screw at the top of the switch by turning it clockwise until the switch is secure on the enclosing tube.
-
Replace the control wires on the appropriate terminals or wiring leads of the new switch. Refer to Figures 5–9 on pages 3–4 as necessary.
-
Replace the switch housing cover.
-
Turn on power to the unit.
-
Test switch action by varying liquid level in the float chamber.
REPLACEMENT SWITCH MECHANISMS
Switch Series| Contacts| Quantity| 8th, 9th & 10th Digits|
Bottom Mech| Top Mech
---|---|---|---|---|---
HS Terminal Block ➀
| SPDT| 1| HA9, HM3, HM4| 89-8301-002| —
DPDT| 1| HB9, HM7, HM8| 89-8301-001| —
HS Wiring Leads ➀
| SPDT| 1| HMC, HeK, HMJ, HMK| 89-8301-004| —
2| HMn, HMP| 89-8301-004
DPDT| 1| HMF, HeT, HMS, HMT| 89-8301-003| —
2| HMY, HMZ| 89-8301-003
Switch Housing Replacement Assemblies
When ordering replacement parts for an existing Magnetrol instrument, please specify:
- Model and serial numbers of control.
- Description and part number of replacement kit.
The proper replacement switch housing kit and parts can be determined by the last three characters of the model number. In Section 5.0, Switch and Housing Model Codes on page 11, locate the eighth, ninth and tenth digit com-bination of your model number in the chart. The heading of the column in which your combination is located iden-tifies the housing material. Follow the row in which your code is located to the right to identify the housing height. Replacement housing kits are listed according to cover height and housing material in Section 4.1 below.
Aluminum Housings
Die cast aluminum NEMA 4X housing replacements are available for general purpose or weather proof installations. Explosion proof NEMA 4X/7/9 and Class I, Div 1, Group B housing replacements are available for hazardous atmosphere locations. Die cast aluminum housings are finished with a baked-on polyester powder coat paint.
NOTE: Consult your local representative on applications to meet NEMA and other codes not covered in this bulletin.
REPLACEMENT PARTS
Cover Height| Housing Material| neMA 4X| neMA 4X/7/9|
neMA 7/9| Group B
---|---|---|---|---|---
Short
| CS cover, alum base| 89-6509-003| —| —| —
Cast Aluminum| 89-6582-023| 89-6582-023| 89-6592-032
Cast Iron| —| 89-6582-002| —
Tall
| CS cover, alum base| 89-6510-003| —| —| —
Cast Aluminum| 89-6582-024| 89-6582-024| 89-6582-033
Cast Iron| —| 89-6582-005| 89-6582-008
Housing Material| enclosure Type| Gasket| O-ring| Cover
Hardware
---|---|---|---|---
CS cover, alum base| NEMA 4X| —| —| 89-6508-001
Cast Aluminum
| NEMA 4X| ****
12-2201-253
| ****
12-2201-116
| ****
—
NEMA 4X/7/9
Group B
Cast Iron
| NEMA 7/9| ****
12-2201-249
7/9 with drain
Group B
Cast Iron Housings
Cast Iron NEMA 7/9 housing replacements are available for hazardous atmosphere locations. Both Class I, Div. 1, Groups C& D and Group B versions are available. The grey iron cover and base are finished with a baked-on polyester powder coat paint.
NOTE: Consult your local representative on applications to meet NEMA and other codes not covered in this bulletin.
Carbon Steel Housings
Carbon steel NEMA 4X switch housings are available for general purpose and
weather proof installations. The hous-ing base is cast from aluminum while the
cover is made from cold rolled steel. The housings are finished with a baked-
on polyester powder coat paint.
NOTE: Consult your local representative on applications to meet NEMA and
other codes not covered in this bulletin.
Switch and Housing Model Codes
The following charts identify the switch and housing model codes used with the
buoyancy products. The eighth, ninth and tenth digit combinations may be used
to identify the type and number of switches, number of contacts, switch magnet
strength as well as housing type, size and options. The switch and housing
codes in bold are currently valid and available in combination with various
buoy-ancy products. The unbolded codes are no longer valid and should be
replaced by the appropriate valid code.
example model number:
neMA 4 Carbon Steel
|
neMA 4X Carbon Steel
|
neMA 7/9 Cast Iron
|
neMA 4X Cast Aluminum
| neMA 4X/7/9 Cast Aluminum|
Group B Cast Iron
| neMA 4X/7/9 Group B Cast Aluminum| ATeX
Cast Aluminum 1″ nPT
|
Wiring Type
|
Set Points
|
Switch Contacts
|
Housing Height
|
Switch Type
---|---|---|---|---|---|---|---|---|---|---|---|---
HSA| HSB| HSC| HMB| HMC| —| HeK| —|
Pigtails
|
1
| SPDT| Short|
550° F
5 Amp
HSD| HSe| HSF| HME| HMF| —| HeT| —| DPDT
HSG| HSH| HSJ| HMH| HMJ| HSK| HMK| —| SPDT|
Tall
HSQ| HSR| HSS| HMR| HMS| HST| HMT| —| DPDT
HSL| HSM| HSn| HMM| HMn| HSP| HMP| —| 2| SPDT
HSW| HSX| HSY| HMX| HMY| HSZ| HMZ| —| DPDT
HWY| HWV| HWS| —| HES| —| —| —|
Terminal Block
|
1
| SPDT| Short
HWU| HWZ| HWW| —| HEW| —| —| —| DPDT
HS1| HS2| HS3| HM2| HM3| HS4| HM4| HA9| SPDT|
Tall
HS5| HS6| HS7| HM6| HM7| HS8| HM8| HB9| DPDT
For gold contact option, consult factory.
ASSURED QUALITY & SERVICE COST LESS
Service Policy
Owners of Magnetrol controls may request the return of a control or any part
of a control for complete rebuilding or replacement. They will be rebuilt or
replaced promptly. Controls returned under our service policy must be returned
by Prepaid transportation. Magnetrol will repair or replace the control at no
cost to the purchaser (or owner) other than transportation if:
- Returned within the warranty period; and
- The factory inspection finds the cause of the claim to be covered under the warranty.
If the trouble is the result of conditions beyond our con-trol; or, is NOT
covered by the warranty, there will be charges for labor and the parts
required to rebuild or replace the equipment. In some cases it may be
expedient to ship replacement parts; or, in extreme cases a complete new
control, to replace the original equipment before it is returned. If this is
desired, notify the factory of both the model and serial numbers of the
control to be replaced. In such cases, credit for the materials returned will
be determined on the basis of the applicability of our warranty.
No claims for misapplication, labor, direct or consequen-tial damage will be
allowed.
Return Material Procedure
So that we may efficiently process any materials that are returned, it is essential that a “Return Material Authorization” (RMA) number be obtained from the factory, prior to the material’s return. This is available through Magnetrol’s local representative or by contacting the factory. Please supply the following information:
- Company Name
- Description of Material
- Serial Number
- Reason for Return
- Application
Any unit that was used in a process must be properly cleaned in accordance
with OSHA standards before it is returned to the factory.
A Material Safety Data Sheet (MSDS) must accompany material that was used in
any media.
All shipments returned to the factory must be by prepaid transportation.
All replacements will be shipped F.O.B. factory.