Danfoss MCD 600 VLT Soft Starter Installation Guide

June 1, 2024
Danfoss

Danfoss MCD 600 VLT Soft Starter

Danfoss-MCD-600-VLT-Soft-Starter-PRODUCT-IMAGE

Product Information

Specifications

  • Connections: DB9 Connector
  • Settings: Configurable via software
  • Certification: CE, UL

Product Usage Instructions

Installation

Installing the Expansion Card:

  1. Push a small flat-bladed screwdriver into the slot in the center of the expansion port cover and ease the cover away from the soft starter.
  2. Line up the card with the expansion port.
  3. Gently push the card along the guide rails until it clicks into the soft starter.

Connecting to the Network:

  1. Restore control power.
  2. Connect field wiring via the DB9 plug.

Configuration

  • Preparations: Ensure all connections are secure and power is off before configuration.
  • PROFIBUS Address: Set the PROFIBUS address according to your network setup.
  • Enabling Network Control: Use software tools to enable network control features.

Data Structures

  • Operating Modes: Understand and select the appropriate operating mode for your application.

  • Soft Starter Control I/O Data Structure:
    Familiarize yourself with input and output data structure for control.

  • Soft Starter Monitoring I/O Data Structure:
    Monitor soft starter parameters using this structure.

  • Soft Starter Programming I/O Data Structure:
    Configure outputs and inputs based on your requirements.

    • Outputs: Define output behavior.
    • Inputs: Configure input signals.
  • Trip Codes: Learn about trip codes for error identification.

PROFIBUS Diagnostic Telegram and Flag

Diagnostic Telegram Structure: Understand the structure for diagnostic information transmission.

Supported Modes:

  • PROFIBUS Freeze Mode
  • PROFIBUS Sync Mode
  • PROFIBUS Clear Mode

FAQ

  • Q: Can I install the expansion card while the soft starter is powered?
    A: No, ensure the soft starter is isolated from mains voltage before installing or removing accessories.

  • Q: How do I set the PROFIBUS address?
    A: Refer to the manual for instructions on setting the PROFIBUS address based on your network configuration.

Installation Guide
PROFIBUS Card
VLT® Soft Starter MCD 600

Safety

  1. Disclaimer
    The examples and diagrams in this manual are included solely for illustrative purposes. The information contained in this manual is subject to change at any time and without prior notice. Responsibility or liability is never accepted for direct, indirect, or consequential damage resulting from the use or application of this equipment.

  2. Warnings

    • WARNING

    • SHOCK HAZARD
      Attaching or removing accessories while the soft starter is connected to mains voltage may cause personal injury.

    • Before attaching or removing accessories, isolate the soft starter from mains voltage.

    • WARNING

    • RISK OF PERSONAL INJURY AND EQUIPMENT DAMAGE

    • Inserting foreign objects or touching the inside of the soft starter while the expansion port cover is open may endanger personnel and can damage the soft starter.

    • Do not insert foreign objects in the soft starter with the port cover open. Do not touch the inside of the soft starter with the port cover open.

  3. Important User Information

    • Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start with-out warning.
    • The installer is responsible for following all instructions in this manual and for following correct electrical practice.
    • Use all internationally recognized standard practice for RS485 communication when installing and using this equipment.

Installation

Installing the Expansion Card
Procedure

  1. Push a small flat-bladed screwdriver into the slot in the center of the expansion port cover and ease the cover away from the soft starter.
  2. Line up the card with the expansion port.
  3. Gently push the card along the guide rails until it clicks into the soft starter.

Example

Illustration 1: Installation of the Expansion Cards
Connecting to the Network
The expansion card must be installed in the soft starter. Procedure

  1. Restore control power.
  2. Connect field wiring via the DB9 plug. Example

Table 1: DB9 Connector

Pin number Assignment
1 Shield
2 24 V DC negative (optional)
3 RxD/TxD-P
4 Not used
5 DGND
6 VP (end of bus slave only)
7 24 V DC positive (optional)
8 RxD/TxD/-N
9 DGND

Feedback LEDs

| Off| On
---|---|---
Power (red)| Device is not powered up.| Device is powered up and ready to go online.
Network (green)| No connection, offline or data exchange failure.| Device is online and in data exchange state.

  • NOTICE
    • If communication is inactive, the soft starter may trip on Network Communications. If parameter 6-13 Network Communications is set to Soft Trip and Log or Trip Starter, the soft starter requires a reset.
  • NOTICE
    • If communication fails between the device and the network, the Bus Status LED goes off. When communication is restored, the Bus Status LED turns back on.

Configuration

  1. Preparations

  2. PROFIBUS Address
    Set the network address for the card via the soft starter (parameter 12-7 PROFIBUS Address). For details on how to configure the soft starter, see the VLT® Soft Starter MCD 600 Operating Guide.

NOTICE
The PROFIBUS Card reads the network address from the soft starter when control power is applied. If parameters are changed in the soft starter, cycle control power for the new values to take effect.

Enabling Network Control
The soft starter only accepts commands from the PROFIBUS Card if parameter 1-1 Command Source is set to Network.

NOTICE

  • If the reset input is active, the soft starter does not operate. If a reset switch is not required, fit a link across terminals RESET, COM+ on the soft starter.
  • If the PROFIBUS network fails, the device leaves data exchange mode after the network watchdog timeout period has expired. This timeout period is set at the Master configuration tool.
  • A Communication Timeout parameter in the GSD file sets how soon after this event the soft starter is forced into a trip state. Adjust the Communication Timeout parameter in the GSD file to any setting from 0–100 s. The default setting is 10 s.
  • NOTICE
  • If the Communication Timeout parameter is set to 0, the current state of the soft starter remains unchanged on a network failure. This gives the option of operating the soft starter via local control, but is NOT failsafe.

 Data Structures

Operating Modes
The GSD file contains 3 operating modes, supporting data I/O structures as follows:

Data structure| Basic mode| Extended mode| Parameter upload/download mode
---|---|---|---
Soft Starter Control I/O Data Structure| | |
Soft Starter Monitoring I/O Data Structure| ✗| |
Soft Starter Programming I/O Data Structure| ✗| ✗|

  • The basic mode allows starting and stopping the soft starter and reading limited information on operating status.
  • The extended mode defines more bytes allowing to read soft starter operating data such as actual motor current and motor tem-perature.
  • The parameter upload/download mode allows reading and writing soft starter parameter values.

Soft Starter Control I/O Data Structure

Table 2: Master/Slave Control Word Structure

Byte Bits Details
0 0–1 Reserved
2–3 0=Use soft starter remote input to select motor set 1=Use primary motor

set when starting

2=Use secondary motor set when starting 4=Reserved

4| 0=Stop action is a soft stop (as selected on the soft starter) 1=Stop action is a quick stop (coast to stop)
5–7| Reserved
1| 0| 0=Stop 1=Start
1–2| Reserved
3| 1=Reset
4–7| Reserved

NOTICE
Bit 4 of byte 0 must be set to 0 for the soft starter to start.

Table 3: Master/Slave Status Word Structure

Byte Bits Details
0 0–5 Motor current (%FLC) (1)
6
  • Command source
  • 0=Remote LCP, digital input, clock 1=Network

7| 1=Ramping (starting or stopping)
Byte| Bits| Details
---|---|---
1| 0| 1=Ready
1| 1=Starting, running, or stopping
2| 1=Tripped
3| 1=Warning
4–7| Reserved

Motor current (%FLC) shows current as a percentage of the set motor full load current. A value of 63 represents 200% full load current. To convert this value to a readable percentage, divide by 0.315. For models MCD6-0063B and smaller, this value is 10 times greater than the value shown on the LCP.

Soft Starter Monitoring I/O Data Structure
Table 4: Structure of Master/Slave Output Bytes Structure

Byte 2
Operating data request (data request numbers 1–16)

Table 5: Structure of Master/Slave Input Bytes in Response to an Operating Data Request

Byte Bit

Byte 2
Echo data request number
Byte 3
Bits 7–1 Reserved| Bit 0=1: Invalid data request number
Byte 4
Data value (high byte)
Byte 5
Data value (low byte)

NOTICE
An invalid data request number results in the invalid data request number bit being set to 1.

Table 6: Definition of Data Values

Data request number Description Bits Details
0 Reserved
1 Productio information 0–7 Reserved
8–15
  • Product type code:
  • 15=MCD 600

2| Starter state| 0–3| 1=Ready 2=Starting 3=Running
Data request number| Description| Bits| Details
---|---|---|---
| | |

  • 4=Stopping (including braking)
  • 5=Not ready (restart delay, restart temperature check, run simulation, reset input open)
  • 6=Tripped 7=Programming mode 8=Jog forward
  • 9=Jog reverse

4|

  • 0=Negative phase sequence
  • 1=Positive phase sequence (only valid if bit 6 = 1)

5| 1=Current exceeds FLC
6| 0=Uninitialized 1=Initialized
7| 1=Communication error between device and soft starter
8–15| See 4.5 Trip Codes
3| Motor current| 0–7| Average rms current across all phases (low byte)
8–15| Average rms current across all 3 phases (high byte)
4| Motor temperature| 0–7| Motor thermal model (%)
8–15| Reserved
5| % Power factor| 0–7| 100% = power factor of 1
8–15| Reserved
6| Power (kW)| 0–11| Power
12–15|

  • Power scale
  • 0=Multiply power by 10 to get W 1=Multiply power by 100 to get W 2=Power (kW)
  • 3=Multiply power by 10 to get kW

7| Power (kVA)| 0–11| Power
12–15|

  • Power scale
  • 0=Multiply power by 10 to get VA 1=Multiply power by 100 to get VA 2=Power (kVA)
  • 3=Multiply power by 10 to get kVA

8| Voltage| 0–13| Average rms voltage across all 3 phases
14–15| Reserved
9| Current| 0–13| Phase 1 current (rms)
14–15| Reserved
10| Current| 0–13| Phase 2 current (rms)
Data request number| Description| Bits| Details
---|---|---|---
| | 14–15| Reserved
11| Current| 0–13| Phase 3 current (rms)
14–15| Reserved
12| Voltage| 0–13| Phase 1 voltage
14–15| Reserved
13| Voltage| 0–13| Phase 2 voltage
14–15| Reserved
14| Voltage| 0–13| Phase 3 voltage
14–15| Reserved
15| Version| 0–7| Parameter minor version number
8–15| Parameter major version number
16| Digital input state| | For all inputs, 0=open, 1=closed (shorted)
0| Start/stop
1| Reserved
2| Reset
3| Input A
4| Input B
5–15| Reserved

Soft Starter Programming I/O Data Structure
The soft starter programming I/O data structure allows uploading (reading) and downloading (writing) starter parameter values across the network.

NOTICE
Do not change the default values of the advanced parameters (parameter group 20-** Advanced Parameters). Changing these val-ues may cause unpredictable behavior in the soft starter.

Outputs
Table 7: Structure of Master/Slave Output Bytes

Byte Bits Details
3 0–7 Parameter number to read/write
4 0 Reserved
1 1=Read parameter
2 1=Write parameter
Byte Bits Details
--- --- ---
3–7 Reserved
5 0–7 High byte parameter value to write to soft starter/0 data values for

read
6| 0–7| Low byte parameter value to write to soft starter/0 data values for read

Inputs
Table 8: Structure of Master/Slave Input Bytes

Byte Bits Details
6 0–7 Echo parameter number
7 0 1=Invalid parameter number
1 1=Invalid parameter value
2–7 Reserved
8 0–7 High byte parameter value read from soft starter
9 0–7 Low byte parameter value read from soft starter

Trip Codes

Code Description
0 No trip
1 Excess start time
2 Motor overload
3 Motor thermistor
4 Current imbalance
5 Frequency
6 Phase sequence
7 Instantaneous overcurrent
8 Power loss
9 Undercurrent
10 Heatsink overtemperature
11 Motor connection
12 Input A trip
13 FLC too high
14 Unsupported option (function not available in inside delta)
15 Communications card fault
16 Forced network trip
17 Internal fault
Code Description
--- ---
18 Overvoltage
19 Undervoltage
23 Parameter out of range
24 Input B trip
26 L1 phase loss
27 L2 phase loss
28 L3 phase loss
29 L1-T1 shorted
30 L2-T2 shorted
31 L3-T3 shorted
33 Time-overcurrent (bypass overload)
34 SCR overtemperature
35 Battery/clock
36 Thermistor circuit
47 Overpower
48 Underpower
56 LCP disconnected
57 Zero speed detect
58 SCR itsm
59 Instantaneous overcurrent
60 Rating capacity
70 Current read err L1
71 Current read err L2
72 Current read err L3
73 Remove mains volts (mains voltage connected in run simulation)
74 Motor connection T1
75 Motor connection T2
76 Motor connection T3
77 Firing fail P1
78 Firing fail P2
79 Firing fail P3
80 VZC fail P1
Code Description
--- ---
81 VZC fail P2
82 VZC fail P3
83 Low control volts
84–96 Internal fault x. Contact the local supplier with the fault code (x).

 PROFIBUS Diagnostic Telegram and Flag

  1. Diagnostic Telegram Structure
    The PROFIBUS Card supports external diagnostics. The following telegram is sent to the Master if the soft starter trips or if a parameter is changed at the soft starter.
Byte Detail
0 User diagnostic length (always set = 3)
1 Trip code
2 Changed parameter number
  1. PROFIBUS Trip Code
    When the soft starter trips, a diagnostic flag is set at the Master and the trip code is reported in byte 1. When the soft starter is reset, the diagnostic flag and trip code data are reset = 0, if the trip condition does not still exist (see 4.5 Trip Codes).

  2. Changed Parameter Number
    If a parameter number is changed via the LCP, the affected parameter number is reported in byte 2. When the Master reads or writes the changed parameter, byte 2 is reset = 0.
    A changed parameter number does not set a diagnostic flag.

Supported Modes

  1. PROFIBUS Freeze Mode
    In Freeze Mode, inputs are only updated with new data from the soft starter when another Freeze action is carried out. An unfreeze action returns the device to normal operation.

  2. PROFIBUS Sync Mode
    In Sync Mode, commands to the soft starter are not processed until another sync action is carried out. An unsync action returns the device to normal operation.

  3. PROFIBUS Clear Mode
    If the Master sends a global clear command, the device sends a quick stop command to the soft starter.

 Specifications

  1. Connections
    • Soft starter 6-way pin assembly
    • Network 5-way male and unpluggable female connector (supplied)
    • Maximum cable size 2.5 mm2 (14 AWG)
  2. Settings
    • Address range 1–125
    • Data rate (bps) 9.6 kb/s–12.0 Mb/s (auto-detect)
  3. Certification
    • RCM IEC 60947-4-2
    • CE EN 60947-4-2
    • RoHS Compliant with EU Directive 2011/65/EU

Illustration 2: PROFIBUS International

  • Danfoss A/S
  • Ulsnaes 1
  • DK-6300 Graasten
  • vlt-drives.danfoss.com
  • Danfoss can accept no responsibility for possible errors in catalogs, brochures, and other printed material. Danfoss reserves the right to alter its products without notice. This
    also applies to products already on order provided that such alterations can be made without sub sequential changes being necessary in specifications already agreed. All
    trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved

Danfoss-MCD-600-VLT-Soft-Starter- \(3\)

Danfoss A/S © 2021.05
AQ277154583779en-000201 / 175R1181

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals