Danfoss FCD 302 VLT Decentral Drive Installation Guide
- June 1, 2024
- Danfoss
Table of Contents
Danfoss FCD 302 VLT Decentral Drive Installation Guide
declares under our sole responsibility that the
Product category: Frequency Converter
Type designation(s): FCD302PXXXT4
Character XXX: K37, K55, K75, 1K1, 1K5, 2K2, 3K0
may be any number or letter indicating drive options which do not impact this DoC.
The meaning of the 39 characters in the type code string can be found in
appendix 00729776.
Covered by this declaration is in conformity with the following directive(s),
regulation(s), standard(s) or other normative document(s), provided that the
product is used in accordance with our instructions
Low Voltage Directive 2014/35/EU
EN61800-5-1 :2007 + A1:2017
Adjustable speed electrical power drive systems Part 5-1: Safety requirements
Electrical, thermal and energy.
EMC Directive 2014/30/EU
EN61800-3:2004+A1:2012
Adjustable speed electrical power drive systems Part 3: EMC requirements
and specific test methods
RoHS Directive 2011/65/EU including amendment 2015/863.
EN IEC 63000 :2018
Technical documentation for the assessment of electrical and electronic
products with respect to the restriction of hazardous substances
Commission Regulation (EU) 2019/1781 under the Ecodesign Directive
2009/125/EC including amendment in Commission Regulation (EU) 2021/341
EN61800-9-2:2017
Adjustable speed electrical power drive systems- Part 9-2 : Ecodesign for
power drive systems, motor starters, power electronics and their driven
applications Energy efficiency indicators for power drive systems and motor
starters
Date: 2021.11.12Place of issue:| Issued by| Date: 2020.11.12Place of
issue| Approved by
---|---|---|---
Graasten, DK| S ignature:
Name: Martin Skov HolmTitle: Head of PM – EU| G raasten, DK| Sig
nature:
Name: Michael QuitzauTitle: Head of PM&D, Denmark
Danfoss only vooches for the correctness of the English version of this declaration, in the event of the declarason being translated in any other language, the translator concemed shall be liable for the conectness of the translation
ID No: 00729677
This doc is managed by 50080577
Revision No : 4,6
Machine Directive 2006/42/EC
EN/IEC 61800-5-2:2007
(Safe Stop function conforms with STO-Safe Torque Off, SIL 2 Capability)
Other standards considered:
EN ISO 13849- 1:2015
(Safe Stop function, PL d (MTTFd=14000 years, DC-90%, Category 3) EN/IEC
61508-1:2010, EN/IEC 61508-2:2010 (Safe Stop function, SIL 2 (PFH1E-10/h,
1E-8/h for specific variants, PFD1E-10, 1E-4 for specific variants, SFF>99%,
HFT=0))
EN/IEC 62061:2005 + A1:2013
(Safe Stop function, SILCL 2)
Adjustable speed electrical power drive systems – Part 5-
2: Safety requirements – Functional
Safety of machinery – Safety-related parts of control
systems – Part 1: General principles for design
Functional safety of electrical/electronic/programmable electronic safety-
related systems
Part 1 : General requirements
Part 2 : Requirements for electrical/electronic / programmable electronic
safety-related systems Safety of machinery Functional safety of safety-related
electrical, electronic and programmable electronic control systems
Further information can be found in manufacturers declarations:
EU Declaration of conformity 00730213 A.1, 00730215 A.1 and 00730217 A.1 or
newer / Manufacturers declaration 00596226 Α.9 or newer.
Instructions
Safety and Installation Awareness
Both an installation and a safety guide are provided with the VLT® Decentral
Drive FCD 302. Before starting installation, familiarize yourself with all
safety guidelines and precautions in the safety guide. Additional resources –
including the operating guide and design guide – can be downloaded at
www.danfoss.com.
Safety Symbols
The following symbols are used in this guide:
D A N G E R
Indicates a hazardous situation which, if not avoided, will result in death
or serious injury.
W A R N I N G
Indicates a hazardous situation which, if not avoided, could result in
death or serious injury.
C A U T I O N
Indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
N O T I C E
Indicates information considered important, but not hazard-related (for
example, messages relating to property damage)
Safety Precautions
W A R N I N G
LACK OF SAFETY AWARENESS
This installation guide gives important information on how to prevent injury
and damage to the equipment or the system. Ignoring this information can lead
to death, serious injury, or severe damage to the equipment.
- Ensure the dangers and safety measures present in the application are understood.
- Before performing any electrical work on the drive, lock out and tag out all power sources from the drive
W A R N I N G
HIGH VOLTAGE
AC drives contain high voltage when connected to AC mains input, DC supply,
or load sharing. Failure to perform installation, start-up, and maintenance by
qualified personnel can result in death or serious injury.
- Only qualified personnel must perform installation, start-up, and maintenance.
W A R N I N G
UNINTENDED START
When the drive is connected to the AC mains, the motor may start at any time,
causing risk of death, serious injury, and equipment or property damage. The
motor may start by activation of an external switch, a fieldbus command, an
input reference signal from the LCP or LOP, via remote operation using MCT 10
Set-up software, or after a cleared fault condition.
- Press [Off] on the LCP before programming parameters.
- Disconnect the drive from the mains whenever personal safety considerations make it necessary to avoid unintended motor start.
- Check that the drive, motor, and any driven equipment are in operational readiness
W A R N I N G
DISCHARGE TIME
The drive contains DC-link capacitors, which can remain charged even when the
drive is not powered. High voltage can be present even when the warning
indicator lights are off. Failure to wait the specified time after power has
been removed before performing service or repair work could result in death or
serious injury.
- Stop the motor.
- Disconnect AC mains, permanent magnet type motors, and remote DC-link supplies, including battery back-ups, UPS, and DC-link connections to other drives.
- Wait for the capacitors to discharge fully. The time for full discharge of the capacitors is minimum 4 minutes for VLT® Decentral Drive FCD 302, 400 V AC, 0.37–3.0 kW (0.5 4.0 hp).
- Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the capacitors are fully discharged.
C A U T I O N
INTERNAL FAILURE HAZARD
An internal failure in the drive can result in serious injury when the drive
is not properly closed.
- Ensure that all safety covers are in place and securely fastened before applying power.
Tools Required
Table 1: Recommended Tools and Equipment
Equipment | Size | Description |
---|---|---|
Screwdrivers | – | – |
Socket (Hex) | 8 | For fastening inverter screws/mounting of brackets |
Slotted | 0.4×2.5 | For spring loaded power and control terminals |
Slotted/Torx | 1.0×5.5/TX20 | For cable clamps inside the installation box |
Spanner | 19, 24, 28 | For blind-plugs |
Verifying the Shipment and the Contents
Ensure that the items supplied and the information on the nameplate
correspond to the order confirmation.
Illustration 1: Example nameplate
- Type code
- Ordering number
- Serial number
- Power rating
- Input voltage, frequency, and current (at low/high voltages)
- Output voltage, frequency, and current (at low/high voltages)
- Enclosure type and protection rating
- Maximum ambient temperature
- Certifications
- Enclosure rating
Additional Resources
The full operating guide for VLT® Decentral Drive FCD 302 and the Safe Torque
Off operating guide are available online at
http://[drives.danfoss.com.](http://drives.danfoss.com.)
Table 2: Additional Resources
Document | Contents |
---|---|
VLT® Decentral Drive FCD 302 Operat- ing Guide | Information about the |
installation, commissioning, and operation of the FCD 302.
VLT® Frequency Converters Safe Tor- que Off Operating Guide| Information about
functional safety standards, Danfoss VLT® FC Series Safe Torque Off (STO)
function, the related installation and commissioning, and service and mainte-
nance for STO.
Dimensions
There are 2 sizes of FCD 302:
- Variants PK37, PK55, PK75, and P1K1 are the small size unit.
- Variant P3K0 is the large size unit
Illustration 2: P K37, PK55, PK75, P1K1
Documents / Resources
|
Danfoss FCD 302 VLT Decentral
Drive
[pdf] Installation Guide
FCD 302 VLT Decentral Drive, FCD 302, VLT Decentral Drive, Decentral Drive,
Drive
---|---