Danfoss 132B0369 Bus Decoupling Kit VLT Midi Drive Instruction Manual
- June 1, 2024
- Danfoss
Table of Contents
Danfoss 132B0369 Bus Decoupling Kit VLT Midi Drive
Installation Instructions
The bus decoupling kit ensures mechanical xation and electrical screening of cables for the following control cassette variants:
- Control cassette with PROFIBUS.
- Control cassette with PROFINET.
- Control cassette with CAN open.
- Control cassette with Ethernet.
Each bus decoupling kit contains 1 horizontal decoupling plate and 1 vertical decoupling plate. Mounting the vertical decoupling plate is optional. The vertical decoupling plate provides better mechanical support for PROFINET and Ethernet connectors and cables.
Items Supplied
Ordering number | Items supplied |
---|---|
132B0369 | Bus decoupling kit, containing the following items: |
- Horizontal decoupling plate.
- Vertical decoupling plate.
- 4 M3x6 screws.
Table 1.1 Items Supplied
Safety Instructions
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors, which can remain charged even when the frequency converter is not powered. High voltage can be present even when the warning LED indicator lights are o. Failure to wait the specied time after power has been removed before performing service or repair work can result in death or serious injury.
- Stop the motor.
- Disconnect AC mains and remote DC-link power supplies, including battery back-ups, UPS, and DClink connections to other frequency converters.
- Disconnect or lock PM motor.
- Wait for the capacitors to discharge fully. The minimum waiting time is specied in Table 1.2.
- Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the capacitors are fully discharged.
Voltage [V] | Power range [kW (hp)] | Minimum waiting time (minutes) |
---|---|---|
200–240 | 0.37–3.7 (0.5–5) |
4
380–480| 0.37–7.5 (0.5–10)|
4
11–22 (15–30)|
15
Table 1.2 Discharge Time
Mounting
To mount the bus decoupling kit:
- Place the horizontal decoupling plate on the control cassette that is mounted on the frequency converter, and fasten the plate using 2 screws, as shown in Illustration 1.1. Tightening torque 0.7–1.0 Nm.
- Optional: Mount the vertical decoupling plate as follows:
2a Remove the 2 mechanical springs and 2 metal clamps from the horizontal
plate.
2b Mount the mechanical springs and metal clamps on the vertical plate.
2c Fasten the plate with 2 screws, as shown in Illustration 1.2.
Tightening torque 0.7– 1.0 Nm.
NOTICE
If the IP21 top cover is used, do not mount the vertical decoupling plate, because its height aects the proper installation of the IP21 top cover.
1 | Mechanical springs |
---|---|
2 | Metal clamps |
3 | Screws |
Illustration 1.1 Fasten the Horizontal Decoupling Plate with Screws
1 | Vertical decoupling plate |
---|---|
2 | Screws |
Illustration 1.2 Fasten the Vertical Decoupling Plate with Screws
Both Illustration 1.1 and Illustration 1.2 show PROFINET sockets.
The actual sockets are based on the type of the control cassette mounted on
the frequency converter.
- Push the PROFIBUS/PROFINET/CAN open/Ethernet cable connectors into the sockets in the control cassette.
- 4a Place the PROFIBUS/CAN open cables between the spring-loaded metal clamps to establish mechanical xation and electrical contact between the screened sections of the cables and the clamps.
4b Place the PROFINET/Ethernet cables between the spring-loaded metal clamps to establish mechanical xation between the cables and the clamps.
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Customer Support
Danfoss A/S Ulsnaes1 DK-6300 Graasten vl-drives.danfoss.com
References
Read User Manual Online (PDF format)