Beijer ELECTRONICS GN-9287 Network Adapters User Guide
- June 1, 2024
- Beijer ELECTRONICS
Table of Contents
Beijer ELECTRONICS GN-9287 Network Adapters
Firmware upgrade instructions for G- and M-series adapters
Update via Ethernet (LAN cable)
For the FnIO Remote I/O network adapters with RJ45 Ethernet interface follow
this guide.
Modules supporting the IAP firmware update mode are: GN-9287/GL-9087/M9287
PROFINET, GN-9289 MODBUS TCP/UDP and GN-9284 CC-link IE Field Basic etc.
-
Adjust the IP address of the PC to be the same subnet as the Remote I/O adapter.
Network & Internet > Change adapter options > Internet Protocol Version 4 (TCP/IPv4) > Properties, then adjust the PC IP address and Subnet mask:
IP: 192.168.001.xxx (1..99) Subnet mask: 255.255.255.0 in this example
Note, the Beijer Remote I/O adapters normally uses the default IP: 192.168.1.100
Example, adjust PC Ethernet port to IP address: 192.168.1.99
-
Set the 10-pol dip switch of the network adapter to value 254 (dec) and restart the adapter, that will activate the IAP Mode. 254(dec) = Fixed IP Address 192.168.1.100 *
A value of 254(dec) = 00 1111 1110 (bin) counting from the dip switch No.1 as LSB bit.
Dip switch 2 to 8 = ON and dip switch 1, 9, and 10 = OFF
-
Below example show screenshots from GN-9289 Modbus TCP and M9287 / GN-9287 ProfiNet adapter during update procedure. Note, for other type of network adapters there may be differences, please check specification documents.
-
Power up / Restart the device, that will enter the IAP mode.
-
In IAP mode the MOD LED = Flashing Red/Green, and the NET LED = Stable green.
-
Ping the adapter from a command prompt: ping 192.168.1.100
-
Enter the web page from a standard web browser. 192.168.1.100
Login with User id and Password:
User ID : beijer
Password : beijer
-
Update firmware with binary file (Choose File):
-
Select the firmware file (*.bin):
Example: Beijer_GN-9289_INA_Rev1011_20230103.bin
Example: Beijer_M9287_Rev1005_20240223.bin
Example: Beijer_GN-9287_INA_Rev1112_20240223.bin
-
Press “Update Firmware” and the procedure will start.
-
When the update is completed, this message is shown:
-
Now reset all dip switches, then press “Reset Adapter”.
-
Power Off/On to Restart the device.
-
Before using the ProfiNet adapter, check that the adapter has completed the update:
a. Checking the ProfiNet adapter after firmware update using for example the free tool PRONETA from Siemens.
b. Picture show the M9287 F/W 1.005 = V1.5.0 in the dialog.
c. Picture show the GN-9287 F/W 1.112 = V1.112.0 in the dialog.
-
Before using the Modbus adapter, check that the adapter has completed the update:
a. Checking the Modbus TCP adapter via the built-in web server, use 192.168.1.100 (default IP)
b. Picture show the adapter GN-9289 F/W 1.011
-
Check the firmware version of the same adapter GN-9289 using IO Guide Pro
a. Select submenu: Tools > Protocol Messenger > Modbus, and device IP and Protocol: Modbus TCP
b. From the GN-9289 manual read out the Modbus address for the Firmware version
c. Send Modbus message on address (hex): 1003 Response: 010B (hex) = 1.011
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>