Firmware upgrade instructions for G- and M-series adapters

Update via Ethernet (LAN cable)

For the FnIO Remote I/O network adapters with RJ45 Ethernet interface follow this guide.
Modules supporting the IAP firmware update mode are: GN-9287/GL-9087/M9287 PROFINET, GN-9289 MODBUS TCP/UDP and GN-9284 CC-link IE Field Basic etc.

  1. Adjust the IP address of the PC to be the same subnet as the Remote I/O adapter.
    Network & Internet > Change adapter options > Internet Protocol Version 4 (TCP/IPv4) > Properties, then adjust the PC IP address and Subnet mask:
    IP: 192.168.001.xxx (1..99) Subnet mask: 255.255.255.0 in this example
    Note, the Beijer Remote I/O adapters normally uses the default IP: 192.168.1.100
    Example, adjust PC Ethernet port to IP address: 192.168.1.99
    Update via Ethernet \(LAN cable\)

  2. Set the 10-pol dip switch of the network adapter to value 254 (dec) and restart the adapter, that will activate the IAP Mode. 254(dec) = Fixed IP Address 192.168.1.100 *
    A value of 254(dec) = 00 1111 1110 (bin) counting from the dip switch No.1 as LSB bit.
    Dip switch 2 to 8 = ON and dip switch 1, 9, and 10 = OFF
    Update via Ethernet \(LAN cable\)

  3. Below example show screenshots from GN-9289 Modbus TCP and M9287 / GN-9287 ProfiNet adapter during update procedure. Note, for other type of network adapters there may be differences, please check specification documents.

  4. Power up / Restart the device, that will enter the IAP mode.

  5. In IAP mode the MOD LED = Flashing Red/Green, and the NET LED = Stable green.

  6. Ping the adapter from a command prompt: ping 192.168.1.100
    Update via Ethernet \(LAN cable\)

  7. Enter the web page from a standard web browser. 192.168.1.100
    Login with User id and Password:
    User ID : beijer
    Password : beijer
    Update via Ethernet \(LAN cable\)

  8. Update firmware with binary file (Choose File):
    Update via Ethernet \(LAN cable\)

  9. Select the firmware file (*.bin):
    Example: Beijer_GN-9289_INA_Rev1011_20230103.bin
    Update via Ethernet \(LAN cable\)
    Example: Beijer_M9287_Rev1005_20240223.bin
    Update via Ethernet \(LAN cable\)
    Example: Beijer_GN-9287_INA_Rev1112_20240223.bin
    Update via Ethernet \(LAN cable\)

  10. Press “Update Firmware” and the procedure will start.

  11. When the update is completed, this message is shown:
    Update via Ethernet \(LAN cable\)

  12. Now reset all dip switches, then press “Reset Adapter”.

  13. Power Off/On to Restart the device.

  14. Before using the ProfiNet adapter, check that the adapter has completed the update:
    a. Checking the ProfiNet adapter after firmware update using for example the free tool PRONETA from Siemens.
    b. Picture show the M9287 F/W 1.005 = V1.5.0 in the dialog.
    Update via Ethernet \(LAN cable\)
    c. Picture show the GN-9287 F/W 1.112 = V1.112.0 in the dialog.
    Update via Ethernet \(LAN cable\)

  15. Before using the Modbus adapter, check that the adapter has completed the update:
    a. Checking the Modbus TCP adapter via the built-in web server, use 192.168.1.100 (default IP)
    b. Picture show the adapter GN-9289 F/W 1.011
    Update via Ethernet \(LAN cable\)

  16. Check the firmware version of the same adapter GN-9289 using IO Guide Pro
    a. Select submenu: Tools > Protocol Messenger > Modbus, and device IP and Protocol: Modbus TCP
    Update via Ethernet \(LAN cable\)
    b. From the GN-9289 manual read out the Modbus address for the Firmware version
    Update via Ethernet \(LAN cable\)
    c. Send Modbus message on address (hex): 1003 Response: 010B (hex) = 1.011
    Update via Ethernet \(LAN cable\)