Beijer ELECTRONICS SER0015 X2 Control Communication User Guide

June 8, 2024
Beijer ELECTRONICS

Beijer ELECTRONICS SER0015 X2 Control Communication

Beijer ELECTRONICS
SER0015 X2 Control Communication productFunction and area of use

This document provides guidelines when working with X2/BoX2 control as Modbus RTU master in CODESYS or BCS Tools, communicating with Beijer Frequency Inverter, BFI-E3, BFI-P2 or BFI-H3.

  • Note, it’s not possible to run CANopen or any other bus at the same time as Modbus RTU.
  • Note, this project contains four BFI of any type.

About this document

This quick start document should not be considered as a complete manual. It is an aid to be able to start up a normal application quickly and easily.

Copyright © Beijer Electronics, 2022

This documentation (below referred to as ‘the material’) is the property of Beijer Electronics. The holder or user has a non-exclusive right to use the material. The holder is not allowed to distribute the material to anyone outside his/her organization except in cases where the material is part of a system that is supplied by the holder to his/her customer. The material may only be used with products or software supplied by Beijer Electronics. Beijer Electronics assumes no responsibility for any defects in the material, or for any consequences that might arise from the use of the material. It is the responsibility of the holder to ensure that any systems, for whatever applications, which is based on or includes the material (whether in its entirety or in parts), meets the expected properties or functional requirements. Beijer Electronics has no obligation to supply the holder with updated versions.

Use the following hardware, software, drivers and utilities in order to obtain a stable application:

In this document, we have used the following software and hardware

Software:

  • BCS Tools 3.33 / CODESYS V3.5 SP13 Patch3
  • iX Developer 2.40 SP5 / SP6
  • BFI-Tools 2.8.0.0

Hardware:

  • X2 control (marine/extreme) or BoX2 pro SC/motion
  • BFI-P2 and BFI-H3 with at least firmware 2.40
  • BFI-E3 with at least firmware 3.00

For further information refer to

  • BFI-E3 / BFI-P2 / BFI-H3 User Guides
  • BFI-P2 Start-Up Manual KI00306C
  • BFI-H3 Start-Up Manual KI00363D
  • BFI-E3 Start-Up Manual KI00369B
  • Installation Manual X2 pro, X2 marine, X2 control
  • Beijer Electronics knowledge database, HelpOnline

This document and other quick start documents can be obtained from our homepage. Please use the address [email protected] for feedback.

System set up

Here comes a short description of what needs to be done and tools to be used to make X2 control work together with one or several BFI-P2/E3/H3 in a Modbus RTU network:Beijer ELECTRONICS SER0015 X2 Control Communication
figf-1

  1. Set up of Station number address and communication speed in each BFI

  2. Either set them up on the display of BFI, PC software BFI-Tools or a device with BFI-Tools Mobile. See chapter 7.7

  3. Set up other parameters in BFI-E3/P2/H3
    Either set them up on the display of BFI-E3, PC software BFI-Tools or a device with BFI-Tools Mobile. See chapter 7.8

  4. Software enable needs to be activated by a jumper between terminal 1 and 2 of BFI

  5. If BFI-P2 or BFI-H3: STO inputs need to be properly connected. Either to a Safety system or jumpers between terminal 1 to 12 and terminal 9 to 13 of BFI- P2 and BFI-H3.

  6. Set up the IP address of X2 control. See chapter 5.2

  7. Connect the serial cable from X2 control, CAB113, to serial port of BFI

  8. Termination of network
    CAB113 has built-in 120-ohm termination resistor. Make sure that the slave in the other end of network has another 120-ohm resistance. For BFI, see chapter 5.3.

  9. Download the PLC project to X2 control. Adjust the device “X2 control” to fit the used hardware. Size and Powerfail or cyclic must be correct. Default is X2 control 4 Power Fail.
    Use BCS Tools or CODESYS for the PLC project.

  10. Download the iX-project to X2 control. Set up type of HMI in project/settings. Default is X2 control 4. Use iX Developer.

Hardware

The following chapter describes the Modbus RTU connections of X2 control and BFI-P2/E3/H3.

Modbus RTU of X2 control

The program example uses the RS485 port called COM2 on pin1 and pin6. Beijer
ELECTRONICS SER0015 X2 Control Communication figf-2

IP address setting of X2 control

The setting of the Ethernet ports in X2 control is being done on the X2 control itself.
Turn Power on and keep your finger attached to the screen. After a while follow the instructions as in the picture below. Beijer ELECTRONICS SER0015
X2 Control Communication figf-3

Modbus RTU port of BFI

Modbus RTU port in BFI depends on model. It has either one or two RJ45 connector with pin configuration as in figure below. All BFI IP66 has two RJ45 connectors for incoming and outgoing network cabling. All BFI IP20 and IP55 has one RJ45 for Modbus RTU connection. Beijer ELECTRONICS SER0015 X2
Control Communication figf-4

Name| Item

number

| Explanation
---|---|---
CAB113| 660000290| 3m cable with 9-pole D-sub and RJ-45 between X2 control, BFI- P2/H3/E3 for Modbus RTU communication including 120-ohm

termination resistor.

Splitter:

OPT-2-J45SP-BFI

| 63148| RS485 Serial communication Data Cable 2-port Splitter for BFI-P2, BFI-H3, BFI-E3 for Modbus RTU and CANopen.
Bus termination:

OPT-2-RJTRM-BFI

| 63202| RJ-45 with End termination, 120 ohms, RJ45 plug for CANopen and

Modbus RTU communication to BFI.

All BFI IP66 up to 22 kW has 2 serial ports in parallel which means that the splitter is not necessary.

The pin configuration of the RJ-45 in BFI

**** 1: See manual for each BFI

2: See manual for each BFI
3: 0 Volt
4: Optibus / Remote keypad / PC Connection –
5: Optibus / Remote keypad / PC Connection +
6: +24 Volt Remote keypad Power Supply
7: RS 485- Modbus RTU
8 : RS 485+ Modbus RTU
Warning: This is not an Ethernet connection.

Drawing CAB113

3m cable with 9-pole D-sub and RJ-45 between X2 control, BFI-P2/H3/E3 for Modbus RTU communication including 120-ohm termination resistor. Beijer
ELECTRONICS SER0015 X2 Control Communication figf-6

Function Block X2_BFI_ModbusRTU

Information Description
Library X2 BFI Modbus RTU
Versions of CODESYS and BCS Tools CODESYS runtime 3.5.13.30.7

Compiler: 3.5.13.30

Device (Beijer X2 control x -xxxxx) 3.5.13.30 iX image 775 or later

Modbus_Com: 3.5.11.20

Modbus Master: 3.5.13.10

Modbus_RTU_Slave: 3.5.10.30 Baud rate: 115,2 kbits/sec

Function Block| X2_BFI_ModbusRTU
Functionality| This function block is used to control and Read/Write Data

with a BFI-E3/P2/H3 by Modbus RTU.

PLC Types| X2 control (marine / extreme) or BoX2 pro (SC / motion)
Version| 1.0.2

Beijer ELECTRONICS SER0015 X2 Control Communication
figf-7

Input_Output Type Function
io_Drive strDRIVE_REF_BFI Reference to variables connected to BFI by Modbus

RTU.
io_BFI| IoDrvModbus.ModbusSla veComPort_Diag| Connection to Modbus slave (Name of the Modbus Slave)
io_BEHMI| strBFIDrvBEHMI| Reference to variables from/to HMI
Input| Type| Function
---|---|---
i_EnableComm| BOOL| Activate the communication between BFI and CODESYS channels.
i_Start| BOOL| Start of Drive. 0=>Stop 1=>Running.

Direction decided by sign of Set frequency.

i_FastStop| BOOL| 1 => Fast stop of motor with ramp in P2-25 for BFI-P2/H3 and P-24 for BFI-E3.
i_CoastingStop| BOOL| 1=> Coasting stop of motor. No output frequency.
i_SetFrequency| REAL| Set frequency for motor, 50.0=50.0 Hz. Positive value => Rotation clockwise. Negative value=> Rotation counter clockwise.
i_AccDecTime| REAL| Used if P5-07=Disabled in BFI-P2/H3 or P-12=4 in BFI-E3. If so,

Acceleration and Deceleration time [0.1 sec].

i_AnalogOutput1| INT| Value 0-1000 sets Analog output to 0-10 VDC or 4-20 mA.
i_Reset| BOOL| Reset an alarm or error message from BFI.
i_PrmReadExecute| BOOL| Read a value from a Parameter in BFI.
i_PrmWriteExecute| BOOL| Write a value to a Parameter in BFI.
i_PrmNumber| INT| Specifies parameter number to be read or written.
Input_Output| Type| Function
io_PrmValue| INT| Value to be written to a parameter or read value from a parameter.
Output| Type| Function
o_ComOk| BOOL| True=Communication up running without any errors.
o_CommunicationState| UINT| 0=Communication succeeded, 1-8=Command Error, 9-254=Some kind of Communication error, 255=Noting sent on bus
o_BEHMIEnabled| BOOL| BeHMI override enabled.
o_ReadyToRun| BOOL| BFI Ready to run. Power ON, Enabled, Safety ok.
o_SafetyOff| BOOL| Safe Torque off, False if STO wires is not connected. Not BFI-E3.
o_Run| BOOL| Start signal received by BFI.
o_Auto| BOOL| Only for BFI-H3. 1=Auto, 0= Hand.
o_MotorCurrent| REAL| Motor current / A.
o_OutputFrequency| REAL| Output frequency / Hz.
o_RunningHours| INT| Total Running Hours / Hours.
o_Alarm| BOOL| Alarm in inverter.
o_AlarmCode| STRING| Error code of the alarm, read automatically.
o_PrmDone| BOOL| Read or Write of parameter has been done.
o_DriveInfo| STRING| Drive ID, Type, Voltage, Firmware version, serial number.
o_PrmError| BOOL| Parameter operation error or not allowed message was sent to BFI.
o_OtherError| BOOL| Summary error bit.
o_ErrorDescription| STRING| Error and status description.
o_CommErrorCounter| UDINT| Total number of errors or interruptions of communication messages on the bus since PLC was put into Run. Can’t be reseted by user.

Program example CODESYS, BCS Tools and iX Developer

BFI and X2 control Start Up project is a very powerful tool providing a project starting point way beyond what would otherwise be possible.
The project contains one HMI-screen to handle the BFI, start/stop, read/write parameters, read type of BFI, handling alarms. The purpose of the screen is to keep them for future use by technicians and/or maintenance personnel. In addition, the project contains a CODESYS/BCS Tools PLC-program correctly configured for use with BFI with a function block comprising all standard drive functionality.

Explanation of the CODESYS/BCS Tools projectBeijer ELECTRONICS SER0015
X2 Control Communication figf-8

  1. Device (X2 control 4 – Powerfail)
    The X2 control hardware must be defined in detail due to allocation of memory. In this case a 4 inch. How to handle Retain data at Power interruption must also be chosen. Either cyclic storage or when power interruption occurs. With limited Retain data Power fail is a sufficient choice. Should be at least version 3.5.13.30. This or later versions are to be downloaded on www.beijerelectronics.com.

  2. Folder Beijer BFI Modbus RTU.
    Contain everything necessary for Modbus RTU control of BFI.

  3. gvlBFI
    Contain Structs for Variables connected on pins to/from FB, Variables to/from iX used inside FB and Variables connecting each BFI with corresponding input/output data (ModbusGenericSerialSlave I/O Mapping).

  4. gvlBFI_HMI
    Contain variables to be used together with HMI. Important are the constant describing number of BFI in network and Structure containing variables copied to/from HMI.

  5. prgBeijerMain_BFI
    Contain code for exchanging data between HMI and CODESYS/BCS Tools.

  6. prgBFI_ ModbusRTU
    Containing Function blocks, one FB for each BFI.

  7. Library Manager
    One of the libraries is X2_BFI_Modbus RTU. Contains the FB to control BFI by Modbus RTU. The FB is compiled and by that not possible to open up. Requires one FB per BFI.Beijer ELECTRONICS SER0015 X2 Control Communication
figf-9

  8. BFI Slaves
    BFI Slaves in the network. Important that each physical BFI has an individual IP address in CODESYS/BCS Tools corresponds with the setting in each BFI.

How to add an additional BFI in the network

  • Enter GVL called gvlBFI_HMI. Adjust the global constant gvlBFI_HMI.gc_iNrOfDrive to number of BFI. If 5 BFI constant should be 5.
  • Enter GVL called gvlBFI. Adjust the global array variable gvlBFI.g_aDrive[]. Set the array to [1..Number of BFI in the network]. If 5 BFI constant should be 5.
  • Enter GVL called gvlBFI . Adjust the global array variable gvlBFI.g_aDriveBEHMI[]. Set the array to [1..Number of BFI in the network]. If 5 BFI constant should be 5.
  • Enter GVL called gvlBFI. If more than 8 BFI. Add variables for BFI9, Drive9 of type strDRIVE_REF_BFI. And for BFI10…
  • Add BFI into Modbus RTU network
    • Chose Modbus_Master_COM_port (Modbus Master, COM PORT)
    • Right click and ADD Device
    • Chose Modbus RTU Slave
    • Rename it. If it is BFI number 5, refactoring it to BFI5.
  • Choose the new BFI
    • In Folder General, set Slave address of the BFI. Must correspond with setting in BFI.
    • In Folder General, keep Response Timeout(ms): 50
    • In Folder Modbus Slave Channel, Copy all data from an existing BFI to new BFI.
    • In Folder MobusGenericSerialSlave I/OMapping, Copy all variable names from BFI_1, to the new BFI. If the new BFI will be BFI5 then: Rename
    • Application. Drive1.PlcToFromDrv.iRunningHours, to
    • Application. Drive5.PlcToFromDrv.iRunningHours,
  • Add FB for a new BFI in prgBFI_ModbusRTU. Copy network 1 and paste. If new BFI is to be number 5 then:
    • Change name fbControlBFI1 to fbControlBFI5
    • Change name Drive1 to Drive5
    • Change name BFI_1 to BFI_5
    • Change name for all [1] to [5] for all other variables in the network

How to remove BFI in the network

  • Enter GVL called gvlBFI_HMI. Adjust the global constant gvlBFI_HMI.gc_iNrOfDrive to number of BFI.
  • Enter GVL called gvlBFI. Adjust the global array variable gvlBFI.g_aDrive[]. Set the array to [1..Number of BFI in the network].
  • Enter GVL called gvlBFI . Adjust the global array variable gvlBFI.g_aDriveBEHMI[]. Set the array to [1..Number of BFI in the network].
  • Remove not used BFI in Modbus_RTU_Master

Enable/Disable Devices

If a BFI is not to be used in the network during commissioning or other reasons it can be excluded, and communication shut off. This can either be done in configuration or by a tag in the PLC-program. Go Offline, chose the Slave and then Disable Device. When to enable a device chose Enable Device instead.

It is also possible to control it in the plc-program by the red marked variable Beijer ELECTRONICS SER0015 X2 Control Communication
figf-11

Modbus RTU setting in CODESYS/BCS Tools

The setting of Modbus RTU ports must also be done in CODESYS/BCS Tools, both for the Master and for all Slaves. Beijer ELECTRONICS SER0015 X2 Control
Communication figf-12

  1. 2 is the name of the Modbus RTU port on Pin 1 and 6 of the Com port.

  2. Baud rate [bits per second] for transmitting data on the bus.
    Maximum working baud rate is decided by limitations of Modbus RTU Slaves, required bandwidth, network cable length and cross-area. Try to keep baud rate as low as possible to avoid communication interruption due to noise. 115200 is default in BFI.

  3. Parity “NONE” is default in BFI.

  4. Data Bits 8 is default in BFI.

  5. Stop Bits 1 is default in BFI.Beijer ELECTRONICS SER0015 X2 Control Communication figf-13

  6. Transmission Mode
    Must be set to RTU.

  7. Response Timeout
    The time from a message sent until a reply must have been received. 50 msec is a large value.

  8. Time between Frames
    Time that master is quiet, time between one message arriving until next message being sent.

  9. Auto-restart Communication
    The master is automatically trying to establish communication with a slave. If not used this must be done by plc-code.Beijer ELECTRONICS SER0015 X2 Control
Communication figf-14
    The time how often the Modbus master is to access the slaves are controlled by setting of a Task in Task Configuration. In this case a task called “BusTask” has been created and control how often the Modbus master access the network. Beijer ELECTRONICS SER0015 X2 Control Communication
figf-15

  10. Slave Addresses
    Slave Address of the BFI. Must correspond to the settings in BFI.

  11. Response Timeout
    Response Timeout[ms] Time interval for the master to wait for the response from the slave. This is especially configured for this slave node and overwrites the general response timeout setting of the respective master.Beijer ELECTRONICS SER0015 X2 Control Communication
figf-16
    Communication with a slave is defined as channels. Each channel is defined as Read or Write, how to read or write, time interval, Modbus address and amount of data. Following data are used in this example:

Channel 0: Cyclic Read of Digital status, Error codes, Output frequency and Motor current.
Channel 1: Cyclic Read of Total Running Hours once every minute.
Channel 2: Write of Command bits
Channel 3: Write of Frquency setpoint
Channel 4: Write of Acceleration and Deceleration time
Channel 5: Read of BFI data.
Channel 6: Read of serial number every time communication is established.
Channel 7: Write parameter number to access when required.
Channel 8: Read Parameter value when required.
Channel 9: Write parameter value when required.
Channel 10: Write to Analog Output.Beijer ELECTRONICS SER0015 X2
Control Communication figf-17

Data read from or written to a channel is copied to plc-variables in ModbusGenericSerialSlaveI/OMapping. Below is variables for BFI number1:

Digital control bits from BFI = > Application.Drive1.PlcToFromDrv.iStatusWord.
Output frequency from BFI = > Application.Drive1.PlcToFromDrv.iOutputFrequency
Motor current from BFI = > Application.Drive1.PlcToFromDrv.iMotorCurrent.
Running Hours from BFI = > Application.Drive1.PlcToFromDrv.iRunningHours
Digital control bits to BFI = > Application.Drive1.PlcToFromDrv.iCommandWord
Set frequency to BFI= > Application.Drive1.PlcToFromDrv.iSetFrequency
**Acceleration and Dec.time to BFI =

Application.Drive1.PlcToFromDrv.iSetFrequency
Detailed Drive info from BFI = > Application.Drive1.PlcToFromDrv.awDriveInfo
Serial number from BFI = > Application.Drive1.PlcToFromDrv.awDriveSerialnumber
Parameter number to/from BFI = > Application.Drive1.PlcToFromDrv.iPrmNumber
Read parameter value from BFI = > Application.Drive1.PlcToFromDrv.iPrmValueRead
Parameter value to be written = > Application.Drive1.PlcToFromDrv.iPrmValueWrite
Control of Analog Output = >** Application.Drive1.PlcToFromDrv.iAnalogOutput1

iX-project

CODESYS/BCS Tools project, X2Control_BFI_Modbus RTU, has a corresponding iX project. The project contains one Start_Screen and one BFI_Control Screen. Explanation of project:

  1. Choose which BFI to be monitored. Either tap in the figure or use Increase/Decrease buttons
  2. BFI data
    • Type of BFI
    • Input voltage and number of phases
    • Power
    • Physical size
    • Firmware version
    • Serial number
  3. Description of Communication error or User error.
  4. Actual status of BFI
    • Ready to Run or not
    • Safety Status (STO) in BFI-H3 and BFI-P2
    • Total Running Hours
    • Motor in Run or Stop
    • Motor current
    • Output frequency
    • If Alarm in BFI it is shown
    • Explanation of what the alarm code means
  5. Take control of the BFI from this menu. PLC-program is neglected.
  6. Start/stop- Coast- and Fast stop buttons.
  7. Frequency Setpoint.
  8. Acceleration/Deceleration Time to be used if P-12=4 in BFI-P2/E3.
  9. Parameter handling
    • Parameter number to be either tapped in or Increase/Decrease buttons
    • Name/Explanation of parameter is shown
    • Read Parameter value or to be written
    • Button Read Parameter
    • Button Write Parameter
    • Status whether Read/Write of parameter Succeeded or notBeijer ELECTRONICS SER0015 X2 Control Communication figf-18

It is possible to have a sheet containing Data from several BFI. But this needs to be configured in Symbol Manager of CODESYS/BCS Tools and then imported to iX Developer.

Parameter settings for Modbus RTU BFI-P2/E3/H3

Set following parameters in BFI-E3

  • P12=3: Modbus RTU control with Acceleration in P-03 and Deceleration time in P-04.
  • P12=4: Modbus RTU control with Acceleration and Deceleration time sent by Modbus RTU.
  • P14=201 to make all parameters available.
  • P25=13 Analog Output of BFI-E3 controlled by bus.
  • P36 = Node ID number. Default=1.
  • P36 = 115,2 Kbits/sec. Setting depending of network size, network length and how slaves are to be connected/disconnected.

Set following parameters in BFI-P2 and BFI-H3

  • P1-12=4: Modbus RTU control.
  • P1-14=201 to make all parameters available.
  • P5-01= Node ID number. Default=1.
  • P5-02= 115,2 Kbits/sec. Setting depending of network size, network length and how slaves are to be connected/disconnected.
  • P5-07: Disable=Acceleration and Deceleration time set in parameter P1-03 and P1-04
  • P5-07: Enable= Acceleration and Deceleration time ramp sent by Modbus RTU.
  • P9-33= 2 Analog Output1 on terminal 8 of BFI-P2/H3 will be controllable from PLC.

Communication timeout

  • The reaction when communication interruption between Modbus RTU master and BFI is set in parameters of BFI.

Set following parameters in BFI-E3
Time until a reaction and how to react are to be set in P-36

  • 0: No reaction and drive continue with latest speed
  • t 30: Drive trips within 30 msec, t 100: Drive trips within 100 msec
  • t 1000: Drive trips within 1 sec t 3000: Drive trips within 1 sec
  • r 30: Coast to stop without trip within 30 msec, r 100: Coast to stop without trip within 100 msec
  • r 1000: Coast to stop without trip within 1 sec, r 3000: Coast to stop without trip within 3 sec.

Set following parameters in BFI-P2 and BFI-H3

  • P5-05=Timeout until BFI trip due to lost communication. If 0 then no trip.
  • P5-06=Drive behaviour if communication is lost.
    0: Alarm and trip
    1: Ramp to stop and trip
    2: Ramp to stop and no trip
    3: Preset speed 8 (P2-08)

Troubleshooting Communication problems

CODESYS/BCS Tools is the tool to check status of Modbus RTU communication.Beijer ELECTRONICS SER0015 X2 Control Communication
figf-19

Example of communication when no Slave is replying could look like: Beijer
ELECTRONICS SER0015 X2 Control Communication figf-20

Check following items if one or several slaves are not answering properly:

Hardware

  • If cable CAB113 is used, the setting in Modbus_COM(Modbus COM)/General COM Port must be set to 2.
  • Check cabling of the network and splitters.
  • COM Port 2 of X2 control means RS-485 TX+/RX+ on Pin1 and RS-485 TX-/RX- – is Pin6.
  • Termination resistor applied correctly in both end of network? CAB 113 has termination built in. And then another 120-ohm resistor needs to be applied. When all system is powered off the resistance between RS-485 TX+/RX+ on Pin1 and RS-485 TX-/RX- on Pin6 should be 60 ohms. If not check termination.
  • Power on to X2 Control?
  • Power turned on to BFI?
  • If slaves are disconnected/reconnected randomly there might be an EMC-problem with noise.
    Try to see if problems occur when a specific BFI is started or any other pattern.

Software or settings

  • Control of BFI by Modbus is set by P1-12=4 in BFI-P2/H3 and P-12=3 or 4 in BFI-E3
  • Communication speed setting in each slave corresponding to Master setting in CODESYS, P-36 in BFI-E3 or P5-03 in BFI-P2/H3?
  • No overlapping Station numbers, P-36 in BFI-E3 or P5-01 in BFI-P2/H3?
  • Station numbers of slaves corresponding with settings in CODESYS?
  • If using iX, make sure Com 2 setting is RS-485.Beijer ELECTRONICS SER0015 X2 Control Communication figf-21

Power failure in BFI-P2 or BFI-E3

Power 1230 or 3400 VAC Turned off to BFI-P2 = >

  • Communication is still working with BFI-P2 due to 24 VDC supply from network cables and the other BFI in network.
  • Diagnostic Message in CODESYS “EMCY Code 3207, Register 05
  • BFI is tripped showing Undervoltage alarm
  • Alarm can’t be reseted, disappears when power Turned on again.

Power 1230 or 3400 VAC Turned off to BFI-E3 = >

  • BFI-E3 turns black.
  • Module not found in CODESYS “Diag String “Polling for Object 0x1000

Communication is working but BFI-P2/E3 doesn’t run the motor correct:

  • Inhibit in display? Safe Torque Off signals are missing to BFI-P2/H3, terminal 12 and 13. Terminal 12 must be connected to a 24 VDC and terminal 13 to 0 VDC.

  • BFI-H3, is the Drive in Auto Mode? If not push Auto on keypad.

  • Software enable on terminal 2 in place? Must be connected to 24 VDC.

  • BFI-P2/H3/E3 is powered up?

  • No alarm in BFI-P2/E3/H3?

  • Parameter P1-12 = 4 in BFI-P2/H3 and P-12=3 or 4 in BFI-E3?

  • Variable Ready to Run must be 1 to run the BFI-P2/E3/H3. Check

    • if not, Software Enable signal on terminal 2=24VDC?
    • if not, Safe Torque Off terminals are properly connected on BFI-P2/H3?
    • if not, 3×400 or 1×230 VAC connected to BFI?
    • BFI-H3, Drive in “Hand mode”
  • Stop in display?

    • Start signal by bus is missing. As soon as BFI receives a start signal a value between 0 and Maximum speed is displayed instead of Stop.
  • H 0.0 in display?
    Start signal arrived but no speed setpoint

    • Speed sent to BFI-P2/E3/H3 must be a value between parameter value P1-01 and P1-02.
    • Speed into Function block is a REAL. Value 50.0 Hz means value 500 being sent to BFI-P2/E3
    • Check that sent speed by bus corresponds with value in P0-07 in BFI-P2/H3 and P0-03 in BFI-E3.
    • Check parameter P0-52:2 (word2 of the 4 cyclic words) in BFI-P2 and BFI-H3. This is the speed value send in cyclic data word2. The value is Hexadecimal. Mean if 50.0 Hz is sent(Value 500) P0-52:2 should be 01F4 in Hexadecimal. Corresponding register in BFI-E3 is P0-22:2.

BFI-P2/H3/E3 Modbus Register Mapping

MODBUS RTU Protocol Specification

The following table highlights the specification for the Modbus RTU implementation in BFI-P2/E3/H3.

Protocol Modbus RTU Setting
Error check CRC
Baud rate 9600bps, 19200bps, 38400bps, 57600bps,

115200bps (default)

| Adjustable in Parameter P5-03 in BFI-

P2/H3 and P-36 in BFI-E3

Data format| 1 start bit, 8 data bits, 1 stop bits, no parity. 1 start bit, 8 data bits, 2 stop bits, no parity. 1 start bit, 8 data bits, 1 stop bits, even parity.

1 start bit, 8 data bits, 1 stop bits, odd parity.

| Adjustable in Parameter P5-04 in BFI- P2/H3 and but not in BFI-E3
Physical signal| RS 485 (3-wire)|

Modbus Telegram Structure:

The following Modbus Commands are supported

  • 03 Read Holding Registers
  • 06 Write Single Holding Register
  • 16 Write Multiple Holding Register (only register 1-4) The telegram structure is as follow

Command 03 – Read Holding Registers

Master Telegram| Length| | Slave Response| Length
Slave Address| 1| Byte| Slave Address| 1| Byte
Function Code (03)| 1| Byte| Function Code (03)| 1| Byte
1st Register Address| 2| Bytes| Byte Count| 1| Byte
No. Of Registers| 2| Bytes| 1st Register Value| 2| Bytes
CRC Checksum| 2| Bytes| 2nd Register Value| 2| Bytes
| | | Etc…| |
| | | CRC Checksum| 2| Bytes
Command 06 – Write Single Holding Register

Master Telegram| Length| | Slave Response| Length
Slave Address| 1| Byte| Slave Address| 1| Byte
Function Code (06)| 1| Byte| Function Code 06| 1| Byte
Register Address| 2| Bytes| Register Address| 2| Bytes
Value| 2| Bytes| Register Value| 2| Bytes
CRC Checksum| 2| Bytes| CRC Checksum| 2| Bytes
| | | | |

Parameter Access Overview BFI-P2, BFI-H3 and BFI-E3

Modbus addresses for control, parameters and Actual status is to be found in Application note or Manuals for BFI-H3, BFI-E3 and BFI-P2.

About Beijer Electronics

Beijer Electronics is a multinational, cross-industry innovator that connects people and technologies to optimize processes for business-critical applications. Our offer includes operator communication, automation solutions, digitalization, display solutions and support. As experts in user-friendly software, hardware and services for the Industrial Internet of Things, we empower you to meet your challenges through leading-edge solutions. Beijer Electronics is a Beijer Group company.
Since its start-up in 1981, BEIJER GROUP has evolved into a multinational group with sales of 1.4 billion SEK 2020. BEIJER GROUP is listed on the NASDAQ Stockholm Main Market under the ticker BELE. www.beijergroup.com

Beijer ELECTRONICS SER0015 X2 Control Communication
figf-22

Contact us
Global offices and distributors

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Beijer ELECTRONICS User Manuals

Related Manuals