EBTRON GTM116e Thermal Dispersion Airflow And Temperature Measurement Owner’s Manual
- June 1, 2024
- EBTRON
Table of Contents
EBTRON GTM116e Thermal Dispersion Airflow And Temperature Measurement
BACnet Protocol Implementation Conformance Statement
Date: 2/14/2024 | Vendor Name: Ebtron, Inc. |
---|---|
Product Name: Gold Series GTM116e | Application Software Version: |
4.17
Product Model Number: GTM116e| Firmware Revision: 8.28
Product Description: Airflow and Temperature Measurement Device with
Integral Relative Humidity| BACnet Protocol Revision: 22
.
BACnet Standardized Device Profile (Annex L):
- BACnet Operator Workstation (B-OWS)
- BACnet Building Controller (B-BC)
- BACnet Advanced Application Controller (B-AAC)
- BACnet Application Specific Controller (B-ASC)
- BACnet Smart Sensor (B-SS)
- BACnet Smart Actuator (B-SA)
BACnet Interoperability Building Blocks Supported (Annex K):
DS-RP-B | DS-RPM-B |
---|---|
DS-WP-B | DS-WPM-B |
DS-COV-B | DM-DDB-B |
DM-DOB-B | DS-DCC-B |
DM-RD-B | NM-FDR-A |
Segmentation Capability
- Segmented requests supported
- Window Size
- Segmented responses supported
- Window Size
Standard Object Types Supported
Data Link Layer Options
- BACnet IP, (Annex J)
- Option: Register as a Foreign Device
- ISO 8802-3, Ethernet (Clause 7)
- ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)
- ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s)
- MS/TP master (Clause 9), baud rate(s):
- MS/TP slave (Clause 9), baud rate(s):
- Point-To-Point, EIA 232 (Clause 10), baud rate(s):
- Point-To-Point, modem, (Clause 10), baud rate(s):
- LonTalk, (Clause 11), medium:
- Other:
Device Address Binding:
Is static device binding supported? (This is currently necessary for two-way
communication with MS/TP slaves and certain other devices.)
- Yes
- No
Networking Options
- Router, Clause 6 – List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc.
- Annex H, BACnet Tunneling Router over IP
- BACnet/IP Broadcast Management Device (BBMD) Does the BBMD support registrations by Foreign Devices?
- Yes
- No
Character Sets Supported:
Indicating support for multiple character sets does not imply that they can
all be supported simultaneously.
- ANSI X3.4/UTF-8
- ISO 10646 (UCS-2)
- IBM/Microsoft DBCS
- ISO 10646 (UCS-4)
- ISO 8859-1
- JIS C 6226
If this product is a communication gateway, describe the types of non-BACnet equipment/networks(s) that the gateway supports:
TABLE 2 – Standard Object Types Supported (GTM116e)
Object| Create Object
Service
| Delete Object
Service
| Optional
Properties Supported
| Writeable Properties| Proprietary Properties| Property Range
Restrictions| Special Requirements
Device – GTM116e| No| No| • Description
• Location
• Active COV Subscriptions
| • Object Identifier
• Object Name
• Description
• Location
• APDU Timeout
| • BBMD Remote Address
• BBMD Remote Port
• Time To Live
• Service Tag
| None|
Analog Input 1 –
AMD Airflow
| No| No| • Description
• Reliability
• COV Increment
| • Units
• Out of Service
• COV Increment
• Present Value
| None| Units: FPM, CFM, MPS, LPS|
Analog Input 2 –
AMD Temperature
| No| No| • Description
• Reliability
• COV Increment
| • Units
• Out of Service
• COV Increment
• Present Value
| None| Units: °C or °F|
Analog Input 3 –
AMD Pressure
| No| No| • Description
• Reliability
• COV Increment
| • Units
• Out of Service
• COV Increment
• Present Value
| None| Units: iWG or Pa| -B
Analog Input 4 –
AMD Alarm Status
| No| No| • Description
• Reliability
• COV Increment
| • Out of Service
• Present Value
| None| None|
Analog Input 21 –
RH
| No| No| • Description
• Reliability
• COV Increment
| • Out of Service
• COV Increment
• Present Value
| None| | -P w/H
Analog Input 22 –
Dew Point
| No| No| • Description
• Reliability
• COV Increment
| • Units
• Out of Service
• COV Increment
• Present Value
| None| Units: °C or °F| -P w/H
Analog Input 23 –
Enthalpy
| No| No| • Description
• Reliability
• COV Increment
| • Units
• Out of Service
• COV Increment
• Present Value
| None| Units: Btu/lb or kJ/kg| -P w/H
Analog Value 1 –
AMD Area
| No| No| • Description
• Reliability
| | None| Units: sq ft or sq m|
Analog Value 10 –
Traverse Status
| No| No| • Description
• Reliability
| Present Value| None| Only write 0 – 3|
Analog Value 21 –
Node 1 Velocity
| No| No| • Description
• Reliability
| | None| Units: FPM, MPS| Enabled in AV 10
Object| Create Object Service| Delete Object Service|
Optional Properties Supported| Writeable Properties| Proprietary
Properties| Property Range Restrictions| Special Requirements
---|---|---|---|---|---|---|---
Analog Value 22 –
Node 2 Velocity
| No| No| • Description
• Reliability
| | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 23 –
Node 3 Velocity
| No| No| • Description
• Reliability
| | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 24 –
Node 4 Velocity
| No| No| • Description
• Reliability
| | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 25 –
Node 5 Velocity
| No| No| • Description
• Reliability
| | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 26 –
Node 6 Velocity
| No| No| • Description
• Reliability
| | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 27 –
Node 7 Velocity
| No| No| • Description
• Reliability
| | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 28 –
Node 8 Velocity
| No| No| • Description
• Reliability
| | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 29 –
Node 9 Velocity
| No| No| • Description
• Reliability
| | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 30 –
Node 10 Velocity
| No| No| • Description
• Reliability
| | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 31 –
Node 11 Velocity
| No| No| • Description
• Reliability
| | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 32 –
Node 12 Velocity
| No| No| • Description
• Reliability
| | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 33 –
Node 13 Velocity
| No| No| • Description
• Reliability
| | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 34 –
Node 14 Velocity
| No| No| • Description
• Reliability
| | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 35 –
Node 15 Velocity
| No| No| • Description
• Reliability
| | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 36 –
Node 16 Velocity
| No| No| • Description
• Reliability
| | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 41 –
Node 1 Temperature
| No| No| • Description
• Reliability
| | None| Units: °C or °F| Enabled in AV 10
Analog Value 42 –
Node 2
Temperature
| No| No| • Description
• Reliability
| | None| Units: °C or °F| Enabled in AV 10
Analog Value 43 –
Node 3 Temperature
| No| No| • Description
• Reliability
| | None| Units: °C or °F| Enabled in AV 10
Analog Value 44 –
Node 4
Temperature
| No| No| • Description
• Reliability
| | None| Units: °C or °F| Enabled in AV 10
Analog Value 45 –
Node 5 Temperature
| No| No| • Description
• Reliability
| | None| Units: °C or °F| Enabled in AV 10
Analog Value 46 –
Node 6
Temperature
| No| No| • Description
• Reliability
| | None| Units: °C or °F| Enabled in AV 10
Analog Value 47 –
Node 7 Temperature
| No| No| • Description
• Reliability
| | None| Units: °C or °F| Enabled in AV 10
Object| Create Object Service| Delete Object Service|
Optional Properties
Supported
| Writeable Properties| Proprietary Properties| Property Range
Restrictions| Special Requirements
---|---|---|---|---|---|---|---
Analog Value 48 –
Node 8 Temperature
| No| No| • Description
• Reliability
| | None| Units: °C or °F| Enabled in AV 10
Analog Value 49 –
Node 9 Temperature
| No| No| • Description
• Reliability
| | None| Units: °C or °F| Enabled in AV 10
Analog Value 50 –
Node 10 Temperature
| No| No| • Description
• Reliability
| | None| Units: °C or °F| Enabled in AV 10
Analog Value 51 –
Node 11 Temperature
| No| No| • Description
• Reliability
| | None| Units: °C or °F| Enabled in AV 10
Analog Value 52 –
Node 12 Temperature
| No| No| • Description
• Reliability
| | None| Units: °C or °F| Enabled in AV 10
Analog Value 53 –
Node 13 Temperature
| No| No| • Description
• Reliability
| | None| Units: °C or °F| Enabled in AV 10
Analog Value 54 –
Node 14 Temperature
| No| No| • Description
• Reliability
| | None| Units: °C or °F| Enabled in AV 10
Analog Value 55 –
Node 15 Temperature
| No| No| • Description
• Reliability
| | None| Units: °C or °F| Enabled in AV 10
Analog Value 56 –
Node 16 Temperature
| No| No| • Description
• Reliability
| | None| Units: °C or °F| Enabled in AV 10
Network Port 1| No| No| • Description
• Network Number
• Network Number Quality
• Mac Address
• APDU Length
• BACnet IP Mode
• IP Address
• IP UDP Port
• IP Subnet Mask
• IP Default Gateway
• IP DNS Server
• IP DHCP Enable
• Foreign Device BBMD Address
• Foreign Device Subscription
Lifetime
| • BACnet IP Mode
• Foreign Device BBMD Address
• Foreign Device Subscription Lifetime
| None| None| None
- EBTRON Inc. 1663 Hwy. 701 S., Loris SC 29569
- Toll Free: 800.2EBTRON (800.232.8766)
- Fax: 843.756.1838
- Internet: www.EBTRON.com
Specifications
- Product Name: Gold Series GTM116e
- Product Model Number: GTM116e
- Product Description: Airflow and Temperature Measurement Device with Integral Relative Humidity
- Vendor Name: Ebtron, Inc.
- Application Software Version: 4.17
- Firmware Revision: 8.28
- BACnet Protocol Revision: 22
Frequently Asked Questions (FAQ)
Q: Does the BBMD support registrations by Foreign Devices?
A: Yes, the BBMD supports registrations by Foreign Devices.
Q: Is static device binding supported for two-way communication?
A: Yes, static device binding is supported for two-way communication with
MS/TP slaves and certain other devices.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>