EBTRON GTM116e Thermal Dispersion Airflow And Temperature Measurement Owner’s Manual

June 1, 2024
EBTRON

EBTRON GTM116e Thermal Dispersion Airflow And Temperature Measurement

BACnet Protocol Implementation Conformance Statement

Date: 2/14/2024 Vendor Name: Ebtron, Inc.
Product Name: Gold Series GTM116e Application Software Version:

4.17
Product Model Number: GTM116e| Firmware Revision: 8.28
Product Description: Airflow and Temperature Measurement Device with Integral Relative Humidity| BACnet Protocol Revision: 22

.

BACnet Standardized Device Profile (Annex L):

  • BACnet Operator Workstation (B-OWS)
  • BACnet Building Controller (B-BC)
  • BACnet Advanced Application Controller (B-AAC)
  • BACnet Application Specific Controller (B-ASC)
  • BACnet Smart Sensor (B-SS)
  • BACnet Smart Actuator (B-SA)

BACnet Interoperability Building Blocks Supported (Annex K):

DS-RP-B DS-RPM-B
DS-WP-B DS-WPM-B
DS-COV-B DM-DDB-B
DM-DOB-B DS-DCC-B
DM-RD-B NM-FDR-A

Segmentation Capability

  • Segmented requests supported
    • Window Size
  • Segmented responses supported
    • Window Size

Standard Object Types Supported

Data Link Layer Options

  • BACnet IP, (Annex J)
  • Option: Register as a Foreign Device
  • ISO 8802-3, Ethernet (Clause 7)
  • ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)
  • ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s)
  • MS/TP master (Clause 9), baud rate(s):
  • MS/TP slave (Clause 9), baud rate(s):
  • Point-To-Point, EIA 232 (Clause 10), baud rate(s):
  • Point-To-Point, modem, (Clause 10), baud rate(s):
  • LonTalk, (Clause 11), medium:
  • Other:

Device Address Binding:
Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain other devices.)

  • Yes
  • No

Networking Options

  • Router, Clause 6 – List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc.
  • Annex H, BACnet Tunneling Router over IP
  • BACnet/IP Broadcast Management Device (BBMD) Does the BBMD support registrations by Foreign Devices?
    • Yes
    • No

Character Sets Supported:
Indicating support for multiple character sets does not imply that they can all be supported simultaneously.

  • ANSI X3.4/UTF-8
  • ISO 10646 (UCS-2)
  • IBM/Microsoft DBCS
  • ISO 10646 (UCS-4)
  • ISO 8859-1
  • JIS C 6226

If this product is a communication gateway, describe the types of non-BACnet equipment/networks(s) that the gateway supports:

TABLE 2 – Standard Object Types Supported (GTM116e)

Object| Create Object

Service

| Delete Object

Service

| Optional

Properties Supported

| Writeable Properties| Proprietary Properties| Property Range Restrictions| Special Requirements
Device – GTM116e| No| No| •  Description

•  Location

•  Active COV Subscriptions

| •  Object Identifier

•  Object Name

•  Description

•  Location

•  APDU Timeout

| • BBMD Remote Address

• BBMD Remote Port

• Time To Live

• Service Tag

| None|
Analog Input 1 –

AMD Airflow

| No| No| •  Description

•  Reliability

•  COV Increment

| •  Units

•  Out of Service

•  COV Increment

•  Present Value

| None| Units: FPM, CFM, MPS, LPS|
Analog Input 2 –

AMD Temperature

| No| No| •  Description

•  Reliability

•  COV Increment

| •  Units

•  Out of Service

•  COV Increment

•  Present Value

| None| Units: °C or °F|
Analog Input 3 –

AMD Pressure

| No| No| •  Description

•  Reliability

•  COV Increment

| •  Units

•  Out of Service

•  COV Increment

•  Present Value

| None| Units: iWG or Pa| -B
Analog Input 4 –

AMD Alarm Status

| No| No| •  Description

•  Reliability

•  COV Increment

| •  Out of Service

•  Present Value

| None| None|
Analog Input 21 –

RH

| No| No| •  Description

•  Reliability

•  COV Increment

| •  Out of Service

•  COV Increment

•  Present Value

| None|  | -P w/H
Analog Input 22 –

Dew Point

| No| No| •  Description

•  Reliability

•  COV Increment

| •  Units

•  Out of Service

•  COV Increment

•  Present Value

| None| Units: °C or °F| -P w/H
Analog Input 23 –

Enthalpy

| No| No| •  Description

•  Reliability

•  COV Increment

| •  Units

•  Out of Service

•  COV Increment

•  Present Value

| None| Units: Btu/lb or kJ/kg| -P w/H
Analog Value 1 –

AMD Area

| No| No| •  Description

•  Reliability

|  | None| Units: sq ft or sq m|
Analog Value 10 –

Traverse Status

| No| No| •  Description

•  Reliability

| Present Value| None| Only write 0 – 3|
Analog Value 21 –

Node 1 Velocity

| No| No| •  Description

•  Reliability

|  | None| Units: FPM, MPS| Enabled in AV 10
Object| Create Object Service| Delete Object Service| Optional Properties Supported| Writeable Properties| Proprietary Properties| Property Range Restrictions| Special Requirements
---|---|---|---|---|---|---|---
Analog Value 22 –

Node 2 Velocity

| No| No| •  Description

•  Reliability

|  | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 23 –

Node 3 Velocity

| No| No| •  Description

•  Reliability

|  | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 24 –

Node 4 Velocity

| No| No| •  Description

•  Reliability

|  | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 25 –

Node 5 Velocity

| No| No| •  Description

•  Reliability

|  | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 26 –

Node 6 Velocity

| No| No| •  Description

•  Reliability

|  | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 27 –

Node 7 Velocity

| No| No| •  Description

•  Reliability

|  | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 28 –

Node 8 Velocity

| No| No| •  Description

•  Reliability

|  | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 29 –

Node 9 Velocity

| No| No| •  Description

•  Reliability

|  | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 30 –

Node 10 Velocity

| No| No| •  Description

•  Reliability

|  | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 31 –

Node 11 Velocity

| No| No| •  Description

•  Reliability

|  | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 32 –

Node 12 Velocity

| No| No| •  Description

•  Reliability

|  | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 33 –

Node 13 Velocity

| No| No| •  Description

•  Reliability

|  | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 34 –

Node 14 Velocity

| No| No| •  Description

•  Reliability

|  | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 35 –

Node 15 Velocity

| No| No| •  Description

•  Reliability

|  | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 36 –

Node 16 Velocity

| No| No| •  Description

•  Reliability

|  | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 41 –

Node 1 Temperature

| No| No| •  Description

•  Reliability

|  | None| Units: °C or °F| Enabled in AV 10
Analog Value 42 –

Node 2

Temperature

| No| No| •  Description

•  Reliability

|  | None| Units: °C or °F| Enabled in AV 10
Analog Value 43 –

Node 3 Temperature

| No| No| •  Description

•  Reliability

|  | None| Units: °C or °F| Enabled in AV 10
Analog Value 44 –

Node 4

Temperature

| No| No| •  Description

•  Reliability

|  | None| Units: °C or °F| Enabled in AV 10
Analog Value 45 –

Node 5 Temperature

| No| No| •  Description

•  Reliability

|  | None| Units: °C or °F| Enabled in AV 10
Analog Value 46 –

Node 6

Temperature

| No| No| •  Description

•  Reliability

|  | None| Units: °C or °F| Enabled in AV 10
Analog Value 47 –

Node 7 Temperature

| No| No| •  Description

•  Reliability

|  | None| Units: °C or °F| Enabled in AV 10
Object| Create Object Service| Delete Object Service| Optional Properties

Supported

| Writeable Properties| Proprietary Properties| Property Range Restrictions| Special Requirements
---|---|---|---|---|---|---|---
Analog Value 48 –

Node 8 Temperature

| No| No| •  Description

•  Reliability

|  | None| Units: °C or °F| Enabled in AV 10
Analog Value 49 –

Node 9 Temperature

| No| No| •  Description

•  Reliability

|  | None| Units: °C or °F| Enabled in AV 10
Analog Value 50 –

Node 10 Temperature

| No| No| •  Description

•  Reliability

|  | None| Units: °C or °F| Enabled in AV 10
Analog Value 51 –

Node 11 Temperature

| No| No| •  Description

•  Reliability

|  | None| Units: °C or °F| Enabled in AV 10
Analog Value 52 –

Node 12 Temperature

| No| No| •  Description

•  Reliability

|  | None| Units: °C or °F| Enabled in AV 10
Analog Value 53 –

Node 13 Temperature

| No| No| •  Description

•  Reliability

|  | None| Units: °C or °F| Enabled in AV 10
Analog Value 54 –

Node 14 Temperature

| No| No| •  Description

•  Reliability

|  | None| Units: °C or °F| Enabled in AV 10
Analog Value 55 –

Node 15 Temperature

| No| No| •  Description

•  Reliability

|  | None| Units: °C or °F| Enabled in AV 10
Analog Value 56 –

Node 16 Temperature

| No| No| •  Description

•  Reliability

|  | None| Units: °C or °F| Enabled in AV 10
Network Port 1| No| No| •  Description

•  Network Number

•  Network Number Quality

•  Mac Address

•  APDU Length

•  BACnet IP Mode

•  IP Address

•  IP UDP Port

•  IP Subnet Mask

•  IP Default Gateway

•  IP DNS Server

•  IP DHCP Enable

•  Foreign Device BBMD Address

•  Foreign Device Subscription

Lifetime

| •  BACnet IP Mode

•  Foreign Device BBMD Address

•  Foreign Device Subscription Lifetime

| None| None| None

  • EBTRON Inc. 1663 Hwy. 701 S., Loris SC 29569
  • Toll Free: 800.2EBTRON (800.232.8766)
  • Fax: 843.756.1838
  • Internet: www.EBTRON.com

Specifications

  • Product Name: Gold Series GTM116e
  • Product Model Number: GTM116e
  • Product Description: Airflow and Temperature Measurement Device with Integral Relative Humidity
  • Vendor Name: Ebtron, Inc.
  • Application Software Version: 4.17
  • Firmware Revision: 8.28
  • BACnet Protocol Revision: 22

Frequently Asked Questions (FAQ)

Q: Does the BBMD support registrations by Foreign Devices?
A: Yes, the BBMD supports registrations by Foreign Devices.

Q: Is static device binding supported for two-way communication?
A: Yes, static device binding is supported for two-way communication with MS/TP slaves and certain other devices.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>