EBTRON GTC108e Fan Array Airflow Monitors Owner’s Manual

June 1, 2024
EBTRON

EBTRON GTC108e Fan Array Airflow Monitors

EBTRON GTC108e Fan Array Airflow Monitors

BACnet Protocol Implementation Conformance Statement

Date: 2/14/2024 Vendor Name: Ebtron, Inc.
Product Name: Gold Series GTC108e Application Software Version:

1.00
Product Model Number: GTC108e| Firmware Revision: 8.33
Product Description: Airflow and Temperature Measurement Device| BACnet Protocol Revision: 22

BACnet Standardized Device Profile (Annex L)

□ BACnet Operator Workstation (B-OWS)
□ BACnet Building Controller (B-BC)
□ BACnet Advanced Application Controller (B-AAC)
□ BACnet Application Specific Controller (B-ASC)
■ BACnet Smart Sensor (B-SS)
□ BACnet Smart Actuator (B-SA)

BACnet Interoperability Building Blocks Supported (Annex K)

DS-RP-B DS-RPM-B
DS-WP-B DS-WPM-B
DS-COV-B DM-DDB-B
DM-DOB-B DS-DCC-B
DM-RD-B

Segmentation Capability

□ Segmented requests supported Window Size
□ Segmented responses supported Window Size

Standard Object Types Supported: (See Table 1)

Data Link Layer Options

□ BACnet IP, (Annex J)
□ ISO 8802-3, Ethernet (Clause 7)
□ ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)
□ ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s)
■ MS/TP master (Clause 9), baud rate(s): 76,800 38,400 19,200 9,600
□ MS/TP slave (Clause 9), baud rate(s):
□ Point-To-Point, EIA 232 (Clause 10), baud rate(s):
□ Point-To-Point, modem, (Clause 10), baud rate(s):
□ LonTalk, (Clause 11), medium:
□ Other:

Device Address Binding

Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain other devices.) □Yes ■ No

Networking Options

□ Router, Clause 6 – List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc.
□ Annex H, BACnet Tunneling Router over IP
□ BACnet/IP Broadcast Management Device (BBMD)
Does the BBMD support registrations by Foreign Devices? □ Yes □ No

Character Sets Supported

Indicating support for multiple character sets does not imply that they can all be supported simultaneously.

■ ANSI X3.4/UTF-8
□ IBM tm/Microsoft tm DBCS
□ ISO 8859-1
□ ISO 10646 (UCS-2)
□ ISO 10646 (UCS-4)
□ JIS C 6226

If this product is a communication gateway, describe the types of non- BACnet equipment/networks(s) that the gateway supports:

TABLE 1 – Standard Object Types Supported (GTC108e)

Object| Create Object Service| Delete Object Service| Optional Properties Supported| Writeable Properties| Proprietary Properties| Property Range Restrictions| Special Requirements
Device – GTC108e| No| No|

  • Description
  • Location
  • Active COV Subscriptions

|

  • Object Identifier
  • Object Name
  • Description
  • Location
  • APDU Timeout

|

  • BBMD Remote Address
  • BBMD Remote Port
  • Time To Live
  • Service Tag

| None| None
Analog Input 1 – AMD Airflow| No| No|

  • Description
  • Reliability
  • COV Increment

|

  • Units
  • Out of Service
  • COV Increment
  • Present Value

| None| Units: FPM, CFM, MPS, LPS| None
Analog Input 2 – AMD Temperature| No| No|

  • Description
  • Reliability
  • COV Increment

|

  • Units
  • Out of Service
  • COV Increment
  • Present Value

| None| Units: °C or °F| None
Analog Input 4 – AMD Alarm Status| No| No|

  • Description
  • Reliability
  • COV Increment

|

  • Out of Service
  • Present Value

| None| None| None
Analog Input 5 – AMD Fan Alarm Status| No| No|

  • Description
  • Reliability
  • COV Increment

|

  • Out of Service
  • Present Value

| None| None| Fan Array
Analog Value 1 – AMD Area| No| No|

  • Description
  • Reliability

| | None| Units: sq ft or sq m| Fan Array
Analog Value 2 – Fan 1 Area| No| No|

  • Description

| | None| Units: sq ft or sq m| Fan Array
Analog Value 3 – Fan 2 Area| No| No|

  • Description

| | None| Units: sq ft or sq m| Fan Array
Analog Value 4 – Fan 3 Area| No| No|

  • Description

| | None| Units: sq ft or sq m| Fan Array
Analog Value 5 – Fan 4 Area| No| No|

  • Description

| | None| Units: sq ft or sq m| Fan Array
Analog Value 6 – Fan 5 Area| No| No|

  • Description

| | None| Units: sq ft or sq m| Fan Array
Analog Value 7 – Fan 6 Area| No| No|

  • Description

| | None| Units: sq ft or sq m| Fan Array
Analog Value 8 – Fan 7 Area| No| No|

  • Description

| | None| Units: sq ft or sq m| Fan Array
Object| Create Object Service| Delete Object Service| Optional Properties Supported| Writeable Properties| Proprietary Properties| Property Range Restrictions| Special Requirements
---|---|---|---|---|---|---|---
Analog Value 9 – Fan 8 Area| No| No|

  • Description

| | None| Units: sq ft or sq m| Fan Array
Analog Value 10 – Traverse Status| No| No|

  • Description
  • Reliability

| Present Value| None| Only write 0 – 3| None
Analog Value 21 – Node 1 Velocity| No| No|

  • Description
  • Reliability

| | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 22 – Node 2 Velocity| No| No|

  • Description
  • Reliability

| | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 23 – Node 3 Velocity| No| No|

  • Description
  • Reliability

| | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 24 – Node 4 Velocity| No| No|

  • Description
  • Reliability

| | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 25 – Node 5 Velocity| No| No|

  • Description
  • Reliability

| | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 26 – Node 6 Velocity| No| No|

  • Description
  • Reliability

| | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 27 – Node 7 Velocity| No| No|

  • Description
  • Reliability

| | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 28 – Node 8 Velocity| No| No|

  • Description
  • Reliability

| | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 41 – Node 1 Temperature| No| No|

  • Description
  • Reliability

| | None| Units: °C or °F| Enabled in AV 10
Analog Value 42 – Node 2 Temperature| No| No|

  • Description
  • Reliability

| | None| Units: °C or °F| Enabled in AV 10
Analog Value 43 – Node 3 Temperature| No| No|

  • Description
  • Reliability

| | None| Units: °C or °F| Enabled in AV 10
Analog Value 44 – Node 4 Temperature| No| No|

  • Description
  • Reliability

| | None| Units: °C or °F| Enabled in AV 10
Analog Value 45 – Node 5 Temperature| No| No|

  • Description
  • Reliability

| | None| Units: °C or °F| Enabled in AV 10
Analog Value 46 – Node 6 Temperature| No| No|

  • Description
  • Reliability

| | None| Units: °C or °F| Enabled in AV 10
Analog Value 47 – Node 7 Temperature| No| No|

  • Description
  • Reliability

| | None| Units: °C or °F| Enabled in AV 10
Analog Value 48 – Node 8 Temperature| No| No|

  • Description
  • Reliability

| | None| Units: °C or °F| Enabled in AV 10
Analog Value 101 – Fan 1 Flow| No| No|

  • Description
  • Reliability

| | None| Units: FPM, CFM, MPS, LPS| Fan Array
Analog Value 102 – Fan 2 Flow| No| No|

  • Description

  • Reliability

| | None| Units: FPM, CFM, MPS, LPS| Fan Array
Analog Value 103 – Fan 3 Flow| No| No|

  • Description
  • Reliability

| | None| Units: FPM, CFM, MPS, LPS| Fan Array
Analog Value 104 – Fan 4 Flow| No| No|

  • Description
  • Reliability

| | None| Units: FPM, CFM, MPS, LPS| Fan Array
Analog Value 105 – Fan 5 Flow| No| No|

  • Description
  • Reliability

| | None| Units: FPM, CFM, MPS, LPS| Fan Array
Object| Create Object Service| Delete Object Service| Optional Properties Supported| Writeable Properties| Proprietary Properties| Property Range Restrictions| Special Requirements
---|---|---|---|---|---|---|---
Analog Value 106 – Fan 6 Flow| No| No|

  • Description
  • Reliability

| | None| Units: FPM, CFM, MPS, LPS| Fan Array
Analog Value 107 – Fan 7 Flow| No| No|

  • Description
  • Reliability

| | None| Units: FPM, CFM, MPS, LPS| Fan Array
Analog Value 108 – Fan 8 Flow| No| No|

  • Description
  • Reliability

| | None| Units: FPM, CFM, MPS, LPS| Fan Array
Analog Value 111 – Fan 1 Temperature| No| No|

  • Description
  • Reliability

| | None| Units: °C or °F| Fan Array
Analog Value 112 – Fan 2 Temperature| No| No|

  • Description
  • Reliability

| | None| Units: °C or °F| Fan Array
Analog Value 113 – Fan 3 Temperature| No| No|

  • Description
  • Reliability

| | None| Units: °C or °F| Fan Array
Analog Value 114 – Fan 4 Temperature| No| No|

  • Description
  • Reliability

| | None| Units: °C or °F| Fan Array
Analog Value 115 – Fan 5 Temperature| No| No|

  • Description
  • Reliability

| | None| Units: °C or °F| Fan Array
Analog Value 116 – Fan 6 Temperature| No| No|

  • Description
  • Reliability

| | None| Units: °C or °F| Fan Array
Analog Value 117 – Fan 7 Temperature| No| No|

  • Description
  • Reliability

| | None| Units: °C or °F| Fan Array
Analog Value 118 – Fan 8 Temperature| No| No|

  • Description
  • Reliability

| | None| Units: °C or °F| Fan Array
Network Port 1| No| No|

  • Description
  • Network Number
  • Network Number Quality
  • Mac Address
  • APDU Length
  • Max Master
  • Max Info Frames

|

  • Max Master
  • Max Info Frames

| None| None| None

Customers Support

EBTRON Inc. 1663 Hwy. 701 S., Loris SC 29569
Toll Free: 800.2EBTRON (800.232.8766)
Fax: 843.756.1838
Internet: www.EBTRON.com

Logo