EBTRON GTC108e Fan Array Airflow Monitors
BACnet Protocol Implementation Conformance Statement
Date: 2/14/2024 | Vendor Name: Ebtron, Inc. |
---|---|
Product Name: Gold Series GTC108e | Application Software Version: |
1.00
Product Model Number: GTC108e| Firmware Revision: 8.33
Product Description: Airflow and Temperature Measurement Device|
BACnet Protocol Revision: 22
BACnet Standardized Device Profile (Annex L)
□ BACnet Operator Workstation (B-OWS)
□ BACnet Building Controller (B-BC)
□ BACnet Advanced Application Controller (B-AAC)
□ BACnet Application Specific Controller (B-ASC)
■ BACnet Smart Sensor (B-SS)
□ BACnet Smart Actuator (B-SA)
BACnet Interoperability Building Blocks Supported (Annex K)
DS-RP-B | DS-RPM-B |
---|---|
DS-WP-B | DS-WPM-B |
DS-COV-B | DM-DDB-B |
DM-DOB-B | DS-DCC-B |
DM-RD-B |
Segmentation Capability
□ Segmented requests supported Window Size
□ Segmented responses supported Window Size
Standard Object Types Supported: (See Table 1)
Data Link Layer Options
□ BACnet IP, (Annex J)
□ ISO 8802-3, Ethernet (Clause 7)
□ ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)
□ ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s)
■ MS/TP master (Clause 9), baud rate(s): 76,800 38,400 19,200 9,600
□ MS/TP slave (Clause 9), baud rate(s):
□ Point-To-Point, EIA 232 (Clause 10), baud rate(s):
□ Point-To-Point, modem, (Clause 10), baud rate(s):
□ LonTalk, (Clause 11), medium:
□ Other:
Device Address Binding
Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain other devices.) □Yes ■ No
Networking Options
□ Router, Clause 6 – List all routing configurations, e.g., ARCNET-Ethernet,
Ethernet-MS/TP, etc.
□ Annex H, BACnet Tunneling Router over IP
□ BACnet/IP Broadcast Management Device (BBMD)
Does the BBMD support registrations by Foreign Devices? □ Yes □ No
Character Sets Supported
Indicating support for multiple character sets does not imply that they can all be supported simultaneously.
■ ANSI X3.4/UTF-8
□ IBM tm/Microsoft tm DBCS
□ ISO 8859-1
□ ISO 10646 (UCS-2)
□ ISO 10646 (UCS-4)
□ JIS C 6226
If this product is a communication gateway, describe the types of non- BACnet equipment/networks(s) that the gateway supports:
TABLE 1 – Standard Object Types Supported (GTC108e)
Object| Create Object Service| Delete Object Service|
Optional Properties Supported| Writeable Properties| Proprietary
Properties| Property Range Restrictions| Special Requirements
Device – GTC108e| No| No|
- Description
- Location
- Active COV Subscriptions
|
- Object Identifier
- Object Name
- Description
- Location
- APDU Timeout
|
- BBMD Remote Address
- BBMD Remote Port
- Time To Live
- Service Tag
| None| None
Analog Input 1 – AMD Airflow| No| No|
- Description
- Reliability
- COV Increment
|
- Units
- Out of Service
- COV Increment
- Present Value
| None| Units: FPM, CFM, MPS, LPS| None
Analog Input 2 – AMD Temperature| No| No|
- Description
- Reliability
- COV Increment
|
- Units
- Out of Service
- COV Increment
- Present Value
| None| Units: °C or °F| None
Analog Input 4 – AMD Alarm Status| No| No|
- Description
- Reliability
- COV Increment
|
- Out of Service
- Present Value
| None| None| None
Analog Input 5 – AMD Fan Alarm Status| No| No|
- Description
- Reliability
- COV Increment
|
- Out of Service
- Present Value
| None| None| Fan Array
Analog Value 1 – AMD Area| No| No|
- Description
- Reliability
| | None| Units: sq ft or sq m| Fan Array
Analog Value 2 – Fan 1 Area| No| No|
- Description
| | None| Units: sq ft or sq m| Fan Array
Analog Value 3 – Fan 2 Area| No| No|
- Description
| | None| Units: sq ft or sq m| Fan Array
Analog Value 4 – Fan 3 Area| No| No|
- Description
| | None| Units: sq ft or sq m| Fan Array
Analog Value 5 – Fan 4 Area| No| No|
- Description
| | None| Units: sq ft or sq m| Fan Array
Analog Value 6 – Fan 5 Area| No| No|
- Description
| | None| Units: sq ft or sq m| Fan Array
Analog Value 7 – Fan 6 Area| No| No|
- Description
| | None| Units: sq ft or sq m| Fan Array
Analog Value 8 – Fan 7 Area| No| No|
- Description
| | None| Units: sq ft or sq m| Fan Array
Object| Create Object Service| Delete Object Service|
Optional Properties Supported| Writeable Properties|
Proprietary Properties| Property Range Restrictions| Special
Requirements
---|---|---|---|---|---|---|---
Analog Value 9 – Fan 8 Area| No| No|
- Description
| | None| Units: sq ft or sq m| Fan Array
Analog Value 10 – Traverse Status| No| No|
- Description
- Reliability
| Present Value| None| Only write 0 – 3| None
Analog Value 21 – Node 1 Velocity| No| No|
- Description
- Reliability
| | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 22 – Node 2 Velocity| No| No|
- Description
- Reliability
| | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 23 – Node 3 Velocity| No| No|
- Description
- Reliability
| | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 24 – Node 4 Velocity| No| No|
- Description
- Reliability
| | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 25 – Node 5 Velocity| No| No|
- Description
- Reliability
| | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 26 – Node 6 Velocity| No| No|
- Description
- Reliability
| | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 27 – Node 7 Velocity| No| No|
- Description
- Reliability
| | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 28 – Node 8 Velocity| No| No|
- Description
- Reliability
| | None| Units: FPM, MPS| Enabled in AV 10
Analog Value 41 – Node 1 Temperature| No| No|
- Description
- Reliability
| | None| Units: °C or °F| Enabled in AV 10
Analog Value 42 – Node 2 Temperature| No| No|
- Description
- Reliability
| | None| Units: °C or °F| Enabled in AV 10
Analog Value 43 – Node 3 Temperature| No| No|
- Description
- Reliability
| | None| Units: °C or °F| Enabled in AV 10
Analog Value 44 – Node 4 Temperature| No| No|
- Description
- Reliability
| | None| Units: °C or °F| Enabled in AV 10
Analog Value 45 – Node 5 Temperature| No| No|
- Description
- Reliability
| | None| Units: °C or °F| Enabled in AV 10
Analog Value 46 – Node 6 Temperature| No| No|
- Description
- Reliability
| | None| Units: °C or °F| Enabled in AV 10
Analog Value 47 – Node 7 Temperature| No| No|
- Description
- Reliability
| | None| Units: °C or °F| Enabled in AV 10
Analog Value 48 – Node 8 Temperature| No| No|
- Description
- Reliability
| | None| Units: °C or °F| Enabled in AV 10
Analog Value 101 – Fan 1 Flow| No| No|
- Description
- Reliability
| | None| Units: FPM, CFM, MPS, LPS| Fan Array
Analog Value 102 – Fan 2 Flow| No| No|
-
Description
-
Reliability
| | None| Units: FPM, CFM, MPS, LPS| Fan Array
Analog Value 103 – Fan 3 Flow| No| No|
- Description
- Reliability
| | None| Units: FPM, CFM, MPS, LPS| Fan Array
Analog Value 104 – Fan 4 Flow| No| No|
- Description
- Reliability
| | None| Units: FPM, CFM, MPS, LPS| Fan Array
Analog Value 105 – Fan 5 Flow| No| No|
- Description
- Reliability
| | None| Units: FPM, CFM, MPS, LPS| Fan Array
Object| Create Object Service| Delete Object Service|
Optional Properties Supported| Writeable Properties| Proprietary
Properties| Property Range Restrictions| Special Requirements
---|---|---|---|---|---|---|---
Analog Value 106 – Fan 6 Flow| No| No|
- Description
- Reliability
| | None| Units: FPM, CFM, MPS, LPS| Fan Array
Analog Value 107 – Fan 7 Flow| No| No|
- Description
- Reliability
| | None| Units: FPM, CFM, MPS, LPS| Fan Array
Analog Value 108 – Fan 8 Flow| No| No|
- Description
- Reliability
| | None| Units: FPM, CFM, MPS, LPS| Fan Array
Analog Value 111 – Fan 1 Temperature| No| No|
- Description
- Reliability
| | None| Units: °C or °F| Fan Array
Analog Value 112 – Fan 2 Temperature| No| No|
- Description
- Reliability
| | None| Units: °C or °F| Fan Array
Analog Value 113 – Fan 3 Temperature| No| No|
- Description
- Reliability
| | None| Units: °C or °F| Fan Array
Analog Value 114 – Fan 4 Temperature| No| No|
- Description
- Reliability
| | None| Units: °C or °F| Fan Array
Analog Value 115 – Fan 5 Temperature| No| No|
- Description
- Reliability
| | None| Units: °C or °F| Fan Array
Analog Value 116 – Fan 6 Temperature| No| No|
- Description
- Reliability
| | None| Units: °C or °F| Fan Array
Analog Value 117 – Fan 7 Temperature| No| No|
- Description
- Reliability
| | None| Units: °C or °F| Fan Array
Analog Value 118 – Fan 8 Temperature| No| No|
- Description
- Reliability
| | None| Units: °C or °F| Fan Array
Network Port 1| No| No|
- Description
- Network Number
- Network Number Quality
- Mac Address
- APDU Length
- Max Master
- Max Info Frames
|
- Max Master
- Max Info Frames
| None| None| None