epluse EE610 Low Differential Pressure Sensor User Guide

June 1, 2024
EplusE

epluse EE610 Low Differential Pressure Sensor

Specifications

  • Model: EE610 – Low Differential Pressure Sensor
  • Power Supply: 15-35 V DC
  • Analogue Output: 0-10 V / 4-20 mA
  • Digital Output: RS485

Product Usage Instructions

Electrical Connection

Ensure correct cabling of the device by following the wiring diagram for the product version being used. The power supply should be within the range of 15-35 V DC to avoid overheating and potential hazards.

Installation
Properly connect the pressure to the sensor and ensure a secure installation to prevent any leaks or malfunctions.

User Interface – LED Indication
The LED indicators provide important information about the status of the sensor:

  • Green LED:
    • Flashing (1 s interval): Normal operation within the measuring range.
    • One flash (2 s): Adjustment confirmation or return to factory settings.
    • Off: No power supply or electronics failure.
  • Red LED:
    • Flashing (1 s interval): Measured data is out of the selected range.
    • One flash (2 s): Failure indication during adjustment.

Communication Settings
The sensor can communicate via RS485 interface with configurable settings such as Baud rate, Data bits, Parity, Stop bits, and Modbus address. These settings can be adjusted using the PCS10 software. Default settings are provided but can be customized based on user requirements.

FAQ

  • Q: How can I change the communication settings of the EE610 sensor?
    A: The communication settings can be changed using the PCS10 software for user-selectable values such as Baud rate, Data bits, Parity, Stop bits, and Modbus address. Ensure to follow the provided guidelines for proper configuration.

  • Q: What should I do if the LED indicators show a failure during adjustment?
    A: If the LED indicators show a failure during adjustment, refer to the user manual for troubleshooting steps or contact customer support for assistance. It is important to address any issues promptly to ensure accurate sensor readings.

Quick Guide
EE610 – Low Differential Pressure Sensor

PLEASE NOTE
Find this document and further product information on our website at www.epluse.com/ee610.

Electrical Connection

WARNING

  • Incorrect installation, wiring or power supply may cause overheating and therefore personal injuries or damage to property.
  • For correct cabling of the device, always observe the presented wiring diagram for the product version used.
  • The manufacturer cannot be held responsible for personal injuries or damage to property as a result of incorrect handling,
    installation, wiring, power supply and maintenance of the device.

Analogue Output

epluse-EE610-Low-Differential-Pressure-Sensor- \(1\)

Use a Ø7.5 mm drill for installing the pressure connection nipples into the duct.

Digital Output

epluse-EE610-Low-Differential-Pressure-Sensor- \(2\)

User Interface – LED Indication

Green LED| | | Red LED|
---|---|---|---|---
Flashing (1 s interval)| EE610 operates normally, the measured data is within the selected measuring range| | Flashing (1 s interval)| The measured data is out of the selected range (overload or reversed pressure connection)
One flash (2 s)| Confirms adjustment or return to factory settings| One flash (2 s)| Indicates the failure of the attempt to adjust zero point or span point, or to return to factory adjustment
Off| No power supply or electronics failure
Fast flashing (0.2 s interval)| Auto-zero is executed, first time 10 s after start / reset|

EE610 with Analogue Output

S1| S2| MR 1)| S3| S4| Time| S5| S6| Unit| S7| DPB 2)| S8| Output| S9| Setting 3)
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
0| 0| ±100 Pa| 0| 0| 50 ms| 0| 0| Pa| 0| on| 0| 0 – 10 V/ 4 – 20 mA| 0| DIP switches
1| 0| ±50 Pa| 1| 0| 500 ms| 1| 0| mbar| 1| off| 1| 0 – 5 V / 0 – 20 mA| 1| PCS10
0| 1| ±25 Pa| 0| 1| 2 s| 0| 1| inch WC|
1| 1| 0-100 Pa| 1| 1| 4 s| 1| 1| mm H2O

  1. Measuring range
  2. Display backlight
  3. These and further settings can be changed with PCS10 via USB configuration adapter (HA011066) while DIP switch S9 = 1. Only available with version with 10 DIP switches.

EE610 with RS485 Interface Electronics Board Layout

The bus termination shall be realized with the 120 Ω resistor (slide switch on board).

epluse-EE610-Low-Differential-Pressure-Sensor- \(3\)

Address Setting

  • Address setting via Software
    • All DIP switches at position 0 → address has to be set via Software (via PCS10 Product Configuration Software or via protocol BACnet / Modbus). Defa lt address 44.
    • Example: Address is set via configuration software.
  • Address setting via Dip-Switch
    • Setting the DIP switches to any other address than 0, overrules the default address (44) or the address set via Software.
    • Example: Address set to 3 (0000 0011 binary).

Communication Settings

| BACnet| Modbus
---|---|---
| Factory settings| User selectable values (via PCS10)| Factory settings| User selectable values (via PCS10)
Baud rate| As specified in the order code| 9 600, 19 200, 38 400, 57 600, 76 800, 115 200| As specified in the order code| 9 600, 19 200, 38 400 57 600, 76 800, 115 200
Data bits| 8| 8| 8| 8
Parity| None| None| Even| None, odd, even
Stop bits| 1| 1| 1| 1, 2
Modbus address| 44| 0…127| 44| 1…247

BACnet Protocol
The EE610 PICS (Product Implementation Conformance Statement) is available on the website at www.epluse.com/ee610. The recommended settings for multiple devices in a BACnet MS/TP network are 38400, 8, none, 1.
Address and Baud rate can be set via:

  • PCS10, Product Configuration Software and the USB configuration adapter HA011066.
  • BACnet protocol, see the PICS.

Modbus Protocol
The recommended settings for multiple devices in a Modbus RTU network are 9600, 8, even, 1.
Address, Baud rate, parity and stop bits can be set via:

  • PCS10, Product Configuration Software and the USB configuration adapter HA011066.
  • Modbus protocol in the register 1 (0x00) and 2 (0x01).
  • Refer to Application Note Modbus AN0103 (available on www.epluse.com/ee610).
  • The measured values are saved as 32 bit floating point value and as 16 bit signed integer value, see Modbus register map below.

Modbus Register Map

| FLOAT 32| INT16
---|---|---
Parameter| Unit| Register number 1) [DEC]| Register address 2) [HEX]| Scale 3)| Register number 1) [DEC]| Register address 2) [HEX]
Read register: function code 0x03 / 0x04
Differential pressure| mm H2O| 1211| 4BA| 10| 4106| 1009
Differential pressure| mbar| 1213| 4BC| 100| 4107| 100A
Differential pressure| Pa| 1215| 4BE| 1| 4108| 100B
Differential pressure| kPa| 1217| 4C0| 1000| 4109| 100C
Differential pressure| inch WC| 1219| 4C2| 100| 4110| 100D

  1. Register number starts from 1
  2. Register address starts from 0
  3. 1xx is scale. E.g. for 1:100, reading of 2550 is equivalent to 25.5

E+E Elektronik Ges.m.b.H. Langwiesen 7

  • 4209 Engerwitzdorf | Austria T +43 7235 605-0
  • F +43 7235 605-8
  • info@epluse.com
  • www.epluse.comepluse-EE610-Low-Differential-Pressure-Sensor- \(6\)
  • QG_EE610
  • Version v1.3
  • 04-2024
  • All rights reserved
  • 350203