EplusE EE600 Differential Pressure Sensor User Guide

June 9, 2024
EplusE

EplusE logo

QUICK GUIDE

EE600 – Differential Pressure Sensor

Find this document and further product information on our website atwww.epluse.com/ee600.

Installation

Pressure Connection

Installation Examples

Use a Ø7.5 mm drill for installing the pressure connection nipples into the duct.

User Interface – LED Indication

Green LED

Flashing (1s interval) = EE610 operates normally, the measured data is within the selected measuring range
One flash (2s) = Confirms adjustment or return to factory settings
Off = No power supply or electronics failure
Fast flashing (0.2 s interval) = Auto-zero is executed, first time 10 s after start/reset

Red LED

Flashing (1s interval) = The measured data is out of the selected range (overload or reversed pressure connection)
One flash (2s) = Indicates the failure of the attempt to adjust zero point or span point, or to return to factory adjustment

Connection Diagram

Important note:
The manufacturer cannot be held responsible for personal injuries or damage to property as a result of incorrect handling, installation, wiring, power supply and maintenance of the device.

Analogue Output

Digital Output

EE600 with Analogue Output

EplusE EE600 Differential Pressure Sensor

  1. Measuring range 2) Display backlight 3) These and further settings can be changed with PCS10 via USB configuration adapter (HA011066) while DIP switch S9 = 1. Only available with version with 10 DIP switches.

INFORMATION                     +43 7235 605 0 /info@epluse.com

E+E Elektronik Ges.m.b.H.
Langwiesen 7 • 4209 Engerwitzdorf • Austria
Tel: +43 7235 605-0 • Fax: +43 7235 605-8
info@epluse.comwww.epluse.com

LG Linz Fn 165761 t • VAT No. ATU44043101
Place of Jurisdiction: 4020 Linz • DVR0962759

QG_EE600 // v1.3 // Modification rights reserved // 350197

EE600 with RS485 Interface

The bus termination shall be realized with 120 Ω resistor (slide switch on board).

Electronics Board Layout

  1. Termination resistor 120 Ω slide switch: 1=ON, 0=OFF
  2. Status LED
  3. USB configuration adapter
  4. Display
  5. Supply and RS485 terminals
  6. Push buttons for span and zero point adjustment
  7. Address switch
Address Setting

Address setting via Software
All DIP switches at position 0 → address has to be set via Software (via PCS10 Product Configuration Software or via protocol BACnet/Modbus). Default address 43.
Example: Address is set via configuration software.

Address setting via Dip-Switch
Setting the DIP switches to any other address than 0, overrules the default address (43) or the address set via Software.
Example: Address set to 3 (0000 0011 binary).

Communication Settings

| BACnet| Modbus
---|---|---
| Factory settings| Selectable values| Factory settings| Selectable values
Baud rate| As ordered per type number | 9600, 19200, 38400, 57600, 76800| As ordered per type number| 9600, 19200, 38400
Data bits| 8| 8| 8| 8
Parity| None| None| Even| None, odd, even
Stop bits| 1| 1| 1| 1, 2
Address| 43| 0…127| 43| 1…247

BACnet Protocol

The EE600 PICS (Product Implementation Conformance Statement) is available on the website at www.epluse.com/ee600.
The recommended settings for multiple devices in a BACnet MS/TP network are 38400, 8, None, 1.
Address and Baud rate can be set via:

  1. PCS10, Product Configuration Software and the USB configuration adapter cable HA011066.
  2. BACnet protocol, see the PICS.
Modbus Protocol

The recommended settings for multiple devices in a Modbus RTU network are 9600, 8, even, 1.
Address, Baud rate, parity and stop bits can be set via:

  1. PCS10, Product Configuration Software and the USB configuration adapter cable HA011066.
  2. Modbus protocol in the register 60001 (0x00) and 60002 (0x01).
    See Application Note Modbus AN0103 (available on www.epluse.com/ee600).

The measured parameters are saved as a 32 bit floating point value and as 16 bit signed integer value, see the Modbus register map below.

Modbus Register Map

FLOAT32

Parameter| Unit| Register number 1) [DEC]| Protocol Address 2) [HEX]
Read register: function code 0x03 / 0x04
Differential pressure| mm H2O| 1211| 0x4BA
Differential pressure| mbar| 1213| 0x4BC
Differential pressure| Pa| 1215| 0x4BE
Differential pressure| kPa| 1217| 0x4C0
Differential pressure| inch WC| 1219| 0x4C2
Air velocity| m/s| 1041| 0x410
Air velocity| ft/min| 1043| 0x412
Volume flow| m³ /h| 1055| 0x41E
Volume flow| l/s| 1057| 0x420
Volume flow| m³ /s| 1059| 0x422
Volume flow| ft³ /min| 1181| 0x49C
Filter monitoring| %| 1075| 0x432
Level indicator | cm| 1077| 0x434
Level indicator | inch| 1079| 0x436

INT16

Parameter| Unit| Scale 3)| Register number 1) [DEC]| Protocol Address 2) [HEX]
Read register: function code 0x03 / 0x04
Differential pressure| mm H2O| 10| 4106| 0x1009
Differential pressure| mbar| 100| 4107| 0x100A
Differential pressure| Pa| 1| 4108| 0x100B
Differential pressure| kPa| 1000| 4109| 0x100C
Differential pressure| inch WC| 100| 4110| 0x100D
Air velocity| m/s| 100| 4021| 0xFB4
Air velocity| ft/min| 1| 4022| 0xFB5
Volume flow| m³ /h| 1| 4028| 0xFBB
Volume flow| l/s| 1| 4029| 0xFBC
Volume flow| m³ /s| 1000| 4030| 0xFBD
Volume flow| ft³ /min| 1| 4091| 0xFFA
Filter monitoring| %| 10| 4038| 0xFC5
Level indicator| cm| 10| 4039| 0xFC6
Level indicator| inch| 10| 4040| 0xFC7

  1. Register number starts from 1 2) Protocol address starts from 0 3) 1xx is scale. E.g. for 1:100, reading of 2550 is equivalent to 25.5

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals