EplusE EE600 Differential Pressure Sensor User Guide
- June 9, 2024
- EplusE
Table of Contents
QUICK GUIDE
EE600 – Differential Pressure Sensor
Find this document and further product information on our website atwww.epluse.com/ee600.
Installation
Pressure Connection
Installation Examples
Use a Ø7.5 mm drill for installing the pressure connection nipples into the duct.
User Interface – LED Indication
Green LED
Flashing (1s interval) = EE610 operates normally, the measured data is within
the selected measuring range
One flash (2s) = Confirms adjustment or return to factory settings
Off = No power supply or electronics failure
Fast flashing (0.2 s interval) = Auto-zero is executed, first time 10 s after
start/reset
Red LED
Flashing (1s interval) = The measured data is out of the selected range
(overload or reversed pressure connection)
One flash (2s) = Indicates the failure of the attempt to adjust zero point or
span point, or to return to factory adjustment
Connection Diagram
Important note:
The manufacturer cannot be held responsible for personal injuries or damage to
property as a result of incorrect handling, installation, wiring, power supply
and maintenance of the device.
Analogue Output
Digital Output
EE600 with Analogue Output
- Measuring range 2) Display backlight 3) These and further settings can be changed with PCS10 via USB configuration adapter (HA011066) while DIP switch S9 = 1. Only available with version with 10 DIP switches.
INFORMATION +43 7235 605 0 /info@epluse.com
E+E Elektronik Ges.m.b.H.
Langwiesen 7 • 4209 Engerwitzdorf • Austria
Tel: +43 7235 605-0 • Fax: +43 7235 605-8
info@epluse.com • www.epluse.com
LG Linz Fn 165761 t • VAT No. ATU44043101
Place of Jurisdiction: 4020 Linz • DVR0962759
QG_EE600 // v1.3 // Modification rights reserved // 350197
EE600 with RS485 Interface
The bus termination shall be realized with 120 Ω resistor (slide switch on board).
Electronics Board Layout
- Termination resistor 120 Ω slide switch: 1=ON, 0=OFF
- Status LED
- USB configuration adapter
- Display
- Supply and RS485 terminals
- Push buttons for span and zero point adjustment
- Address switch
Address Setting
Address setting via Software
All DIP switches at position 0 → address has to be set via Software (via PCS10
Product Configuration Software or via protocol BACnet/Modbus). Default address
43.
Example: Address is set via configuration software.
Address setting via Dip-Switch
Setting the DIP switches to any other address than 0, overrules the default
address (43) or the address set via Software.
Example: Address set to 3 (0000 0011 binary).
Communication Settings
| BACnet| Modbus
---|---|---
| Factory settings| Selectable values| Factory settings|
Selectable values
Baud rate| As ordered per type number | 9600, 19200, 38400, 57600, 76800| As
ordered per type number| 9600, 19200, 38400
Data bits| 8| 8| 8| 8
Parity| None| None| Even| None, odd, even
Stop bits| 1| 1| 1| 1, 2
Address| 43| 0…127| 43| 1…247
BACnet Protocol
The EE600 PICS (Product Implementation Conformance Statement) is available on
the website at www.epluse.com/ee600.
The recommended settings for multiple devices in a BACnet MS/TP network are
38400, 8, None, 1.
Address and Baud rate can be set via:
- PCS10, Product Configuration Software and the USB configuration adapter cable HA011066.
- BACnet protocol, see the PICS.
Modbus Protocol
The recommended settings for multiple devices in a Modbus RTU network are
9600, 8, even, 1.
Address, Baud rate, parity and stop bits can be set via:
- PCS10, Product Configuration Software and the USB configuration adapter cable HA011066.
- Modbus protocol in the register 60001 (0x00) and 60002 (0x01).
See Application Note Modbus AN0103 (available on www.epluse.com/ee600).
The measured parameters are saved as a 32 bit floating point value and as 16 bit signed integer value, see the Modbus register map below.
Modbus Register Map
FLOAT32
Parameter| Unit| Register number 1) [DEC]| Protocol Address
2) [HEX]
Read register: function code 0x03 / 0x04
Differential pressure| mm H2O| 1211| 0x4BA
Differential pressure| mbar| 1213| 0x4BC
Differential pressure| Pa| 1215| 0x4BE
Differential pressure| kPa| 1217| 0x4C0
Differential pressure| inch WC| 1219| 0x4C2
Air velocity| m/s| 1041| 0x410
Air velocity| ft/min| 1043| 0x412
Volume flow| m³ /h| 1055| 0x41E
Volume flow| l/s| 1057| 0x420
Volume flow| m³ /s| 1059| 0x422
Volume flow| ft³ /min| 1181| 0x49C
Filter monitoring| %| 1075| 0x432
Level indicator | cm| 1077| 0x434
Level indicator | inch| 1079| 0x436
INT16
Parameter| Unit| Scale 3)| Register number 1) [DEC]|
Protocol Address 2) [HEX]
Read register: function code 0x03 / 0x04
Differential pressure| mm H2O| 10| 4106| 0x1009
Differential pressure| mbar| 100| 4107| 0x100A
Differential pressure| Pa| 1| 4108| 0x100B
Differential pressure| kPa| 1000| 4109| 0x100C
Differential pressure| inch WC| 100| 4110| 0x100D
Air velocity| m/s| 100| 4021| 0xFB4
Air velocity| ft/min| 1| 4022| 0xFB5
Volume flow| m³ /h| 1| 4028| 0xFBB
Volume flow| l/s| 1| 4029| 0xFBC
Volume flow| m³ /s| 1000| 4030| 0xFBD
Volume flow| ft³ /min| 1| 4091| 0xFFA
Filter monitoring| %| 10| 4038| 0xFC5
Level indicator| cm| 10| 4039| 0xFC6
Level indicator| inch| 10| 4040| 0xFC7
- Register number starts from 1 2) Protocol address starts from 0 3) 1xx is scale. E.g. for 1:100, reading of 2550 is equivalent to 25.5
References
- Sensor Technology: Humidity, CO2, Flow & Temperature Measurement
- Multi-range differential pressure sensor
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>