KEYENCE LS20 Radar Type Level Sensor Instruction Manual
- June 1, 2024
- KEYENCE
Table of Contents
LS20 Radar Type Level Sensor
“`html
Specifications:
-
Model: FR Series
-
Type: Radar Type Level Sensor
-
Range: Long-range (FR-LM(H)20/LP(H)20/LS20)
-
Power Supply: Stabilized DC power supply with an isolating
transformer -
CE and UKCA Marking: Compliant with zRE Directive (CE) and
Radio Equipment Regulations (UKCA)
Product Usage Instructions:
Safety Precautions:
-
General Precautions: Follow all safety
instructions provided in the manual to prevent any accidents. -
Precautions on Media: Clean the bottom of the
main unit if conductive components adhere to it to avoid
measurement errors. -
Precautions on Handling: Handle the unit
carefully to prevent damage or malfunction. -
Precautions on Installation: Ensure proper
installation to improve noise immunity and prevent
malfunctions. -
Power Supply: Use a stabilized DC power supply
with an isolating transformer and ground the frame ground
terminal.
Regulations and Standards:
-
CE and UKCA Marking: Complies with essential
requirements of the applicable EU Directive(s) and UK
regulations. -
CSA Certificate: Ensure proper screen
brightness settings to meet certification requirements. -
Precautions on Radio Communication: Follow
guidelines to prevent interference and ensure proper
communication.
Frequently Asked Questions (FAQ):
Q: Where can I find the FR Series User’s Manual?
A: The FR Series User’s Manual can be downloaded from the
KEYENCE website or obtained through a local KEYENCE
representative.
Q: What should I do if the measured values exceed the upper
limit?
A: If conductive components adhere to the bottom of the main
unit causing measurement errors, clean the bottom of the main unit
to remove the substances.
Q: How should I handle the product during installation?
A: When installing the unit, consider factors like noise
immunity and avoid placing it near high electric or magnetic fields
to prevent malfunctions.
“`
96Mxxxxx
Radar Type Level Sensor
FR Series
Long-range (FR-LM(H)20/LP(H)20/LS20)
Instruction Manual
1IPUP
Details about the FR Series functions and how to use the unit can be found in
the “FR Series User’s Manual.” A copy of the “FR Series User’s Manual” can be
downloaded off of the KEYENCE website. Alternatively, contact a local KEYENCE
representative. KEYENCE website: http://www.keyence.com
Read this manual before using the product in order to achieve maximum
performance. Keep this manual in a safe place after reading it so that it can
be used at any time.
Symbols
The following symbols alert you to important messages. Be sure to read these
messages carefully.
Indicates a hazardous situation which, if not avoided, will result in DANGER
death or serious injury.
Indicates a hazardous situation which, if not avoided, could result in WARNING
death or serious injury.
Indicates a hazardous situation which, if not avoided, could result in CAUTION
minor or moderate injury.
Indicates a situation which, if not avoided, could result in product NOTICE
damage as well as property damage.
Important Indicates cautions and limitations that must be followed during
operation.
Point Indicates additional information on proper operation.
Reference Indicates tips for better understanding or useful information.
Safety Precautions
General precautions
· Do not use this product for the purpose of protecting a human body or a part
of a human body.
· This product is not intended for use as an explosion-proof product. Do not
use this product in a hazardous location and/or potentially explosive
atmosphere.
DANGER · Do not use this product in an application that may cause death,
serious injury, or serious property damage due to a failure with this product
occurring, such as in nuclear power plants; on aircraft, trains, ships, or
vehicles; used within medical equipment, playground equipment, roller
coasters, and other rides.
· Do not use the FR-SH01(C) for applications such as beverages, food, and
medical services. Also, if using the FR-LP(H)20(L) for applications such as
beverages, food, and medical services, be sure to use a ferrule mounting
bracket (OP-88888).
· If the equipment is used in a manner not specified by the manufacturer,
WARNING the protection provided by the equipment may be impaired.
· You must perform a sufficient risk assessment for the machine where this
product is to be installed prior to installing this product. Provide
appropriate protective fail-safe measures on the machine independent from this
product in case a failure with this product should occur.
· Before starting operation and during operation, verify the functions and
performance of the product.
CAUTION · In case any failure occurs with the product, take sufficient safety
measures to prevent further damage.
· The sanitary model (FR-LS20(L)) needs to be cleaned prior to use. · If the
product is used in combination with other equipment, the functions
and performance may not meet expectations depending on the operating
condition, environment, and other conditions. Consider these points NOTICE
before using this product. · If this product is used for an acid or alkaline
medium, or for an application within sanitary environments and electroplating,
check the resistance of the sensor materials to the target medium or
application beforehand.
Precautions on media
Measured values may exceed the upper limit if conductive components NOTICE in
the target medium adhere to the bottom of the main unit. In this case,
clean the bottom of the main unit to remove the adhered substances.
Precautions on handling
· When detecting a high-temperature liquid, the temperatures of the metal
components of the sensor will also rise, which may cause burns. Do not
CAUTION touch these metal components during operation. · Do not touch the
thread component of the main unit because it is sharp.
Precautions on installation
Do not install the sensor in the following locations, as this may result in an
accident: · A location where the main unit is subject to vibrations or impact
greater
than its environmental resistance · A location whose ambient temperature does
not fall within the ambient CAUTION operating temperature range · A location
where the humidity surrounding the main unit is not between
35%RH and 85%RH (no condensation) · A location subject to sudden changes in
temperature · A location with any volatile combustibles, solvents, or
corrosive gases · A location with a strong magnetic or electric field
During installation, take the following into account to improve the noise
immunity. Otherwise, a malfunction may occur.
· When using IO-Link, do not use a power cable whose length exceeds
20 m.
· Mount the sensor as far away as possible from any power lines.
· Mount the sensor as far away as possible from any equipment generating
a high electric or magnetic field (such as solenoids and choppers).
· Wire input/output signal lines separately from power and high-tension
NOTICE
lines.
Power supply
· Noise superimposed on the power supply may result in malfunction. Be
sure to use a stabilized DC power supply with an isolating transformer.
· When using a commercially available switching regulator, be sure to
ground the frame ground terminal.
· Failing to abide by the recommended installation conditions in this
manual may lead to unstable detection.
Precautions on Regulations and Standards
CE and UKCA marking
Keyence Corporation has confirmed that this product complies with the
essential requirements of the applicable EU Directive(s) and UK regulations,
based on the following specifications. Be sure to consider the following
specifications when using this product in the Member States of European Union
and in the United Kingdom.
zRE Directive (CE) and Radio Equipment Regulations (UKCA)
· Operating frequency: 58 to 63 GHz · Maximum radio output:
FR-S(H)01(C): -12.81 dBm (0.05 mW) FR-LM(H)20/LP(H)20/LS20: -5.89 dBm (0.26
mW) FR-LM(H)20L/LP(H)20L/LS20L: -17.36 dBm (0.02 mW) Remarks: These
specifications do not give any guarantee that the end-product with this
product incorporated complies with the essential requirements of RE Directive
and Radio Equipment Regulations. The manufacturer of the end-product is solely
responsible for the compliance of the end-product itself according to RE
Directive and Radio Equipment Regulations.
CSA certificate
This product complies with the following CSA and UL standards and has been
certificated by CSA. · Applicable standard CAN/CSA C22.2 No.61010-1
UL61010-1 Be sure to consider the following specifications when using this
product as a product certified by CSA. · Overvoltage category I · Pollution
degree 3 (FR-S(H)01(C)/SA1/SA2/SA1C/SA0/LS20(L)) · Pollution degree 4 (FR-
LM(H)20(L)/LP(H)20(L)) · Use this product at an altitude of 5000 m or less. ·
Use a CSA/UL certified power supply that provides Class 2 output as defined in
the
CEC (Canadian Electrical Code) and NEC (National Electrical Code). · The FR-
LM20/LP20 can also be used outdoors. In that situation, use the FR-LMP1
protection cover. · When using the FR-LM20 outdoors, ensure the ambient
temperature is 40°C or lower
and select [Turns off when no op.] for “Screen brightness.”
Precautions on radio communication
· The FR Series uses the 60 GHz band. · Radio frequency interference slowing
or even preventing measurement may occur if
this product is used in the vicinity of equipment that uses the same frequency
band such as wireless LAN equipment, microwaves, factory-use heaters, and
highfrequency medical equipment. Industrial, scientific, and medical equipment
as well as on-site radio stations (requiring a license) used on factory
production lines to identify moving bodies, specified low-power radio stations
(not requiring a license), and amateur radio stations (requiring a license)
operate in the frequency band used by this device. · KEYENCE declares that the
FR-S(H)01(C)/LS20(L)/LM(H)20(L)/LP(H)20(L) complies with Radio Equipment
Directive 2014/53/EU. · The entirety of this declaration of conformity with
this EU directive is available at the following Internet address.
[www.keyence.com/cedoc] ·
E1
Precautions on radio communication (FR-S(H)01(C)/LS20L/
LM(H)20L/LP(H)20L)
· This device complies with part 15 of the FCC Rules. · Operation is subject
to the following two conditions:
(1) This device may not cause harmful interference, and (2) this device must
accept any interference received, including interference that
may cause undesired operation. · FCC CAUTION Changes or modifications not
expressly approved by the party
responsible for compliance could void the user’s authority to operate the
equipment. Note: This equipment has been tested and found to comply with the
limits for a Class A
digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference when
the equipment is operated in a commercial environment. · This equipment
generates, uses, and can radiate radio frequency energy and, if not installed
and used in accordance with the instruction manual, may cause harmful
interference to radio communications. · Operation of this equipment in a
residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his own expense. · This
equipment complies with FCC radiation exposure limits set forth for an
uncontrolled environment and meets the FCC radio frequency (RF) Exposure
Guidelines. · This equipment should be installed and operated keeping the
radiator at least 20cm or more away from person’s body. · This device contains
licence-exempt transmitter(s)/receiver(s) that comply with Innovation, Science
and Economic Development Canada’s licence-exempt RSS(s). Operation is subject
to the following two conditions: 1. This device may not cause interference. 2.
This device must accept any interference, including interference that may
cause undesired operation of the device. · L’émetteur/récepteur exempt de
licence contenu dans le présent appareil est conforme aux CNR d’Innovation,
Sciences et Développement économique Canada applicables aux appareils radio
exempts de licence. L’exploitation est autorisée aux deux conditions suivantes
: 1. L’appareil ne doit pas produire de brouillage; 2. L’appareil doit
accepter tout brouillage radioélectrique subi, même si le brouillage est
susceptible d’en compromettre le fonctionnement. · This equipment complies
with ISED radiation exposure limits set forth for an uncontrolled environment
and meets RSS-102 of the ISED radio frequency (RF) Exposure rules. · This
equipment should be installed and operated keeping the radiator at least 20cm
or more away from person’s body. · Cet équipement est conforme aux limites
d’exposition aux rayonnements énoncées pour un environnement non contrôlé et
respecte les règles d’exposition aux fréquences radioélectriques (RF) CNR-102
de l’ISDE. · Cet équipement doit être installé et utilisé en gardant une
distance de 20 cm ou plus entre le radiateur et le corps humain. · dde ef id
df df ef
Packaged Items
· Main unit · Instruction Manual · Precautions (FR-LP20 only)
System Configuration Example and Name of Each Component Standard model; chemical model
Power cable connector (M12 male)
Display
When used with separated display
Sensor head
Display
MENU key Select key Arrow keys
Ring indicator1
Case Can be rotated up to 330°
Mounting thread (G1-1/2)
1 Lights in red, yellow, or green depending on the indicator pattern setting.
Sanitary model
Display
MENU key Select key Arrow keys Ring indicator*1
Mounting screw (G1-1/2)
Cover
Power cable connector (M12 male)
*1 Lights in red, yellow, or green depending on the indicator pattern setting.
Product Overview
The FR Series allows you to specify the following values. (1) The distance
from the reference surface of the sensor to the bottom of the tank (0%) (2)
The distance from the reference surface of the sensor to the top surface of
the tank (100%)
With these values specified, the sensor displays the level of the
liquid/powder from the bottom of the tank.
Example) The FR Series is mounted 100 mm above the top surface of a tank whose height (the position at which the tank is filled to 100% capacity) is 1000 mm.
(2) Distance to top surface (100%): 100 mm
Tank top surface (100%)
Tank view
Curdreisnptlvaaylue % display Analogoutput
1000 mm
100%
20 mA
Tank bottom (0%)
400 mm Current value
40% 10.4 mA
(1) Distance to bottom (0%): 1100 mm
0 mm
0%
4 mA
When using an oil-based liquid (low specific conductive capacity)
You can select [Oily Liquid] for “Detection target” to automatically mask the
area close to the bottom of the tank, preventing false detections of the
bottom of the tank. The current value display shows “- – -” in the masked
area. For details on the masking function, see the user’s manual.
Tank view
Curdreisnptlvaaylue % display Analogoutput
1000 mm
100%
20 mA
E2
100 mm (0 mm)
10% (0%)
5.6 mA (4 mA)
Installation and Mounting Mounting the sensor Mounting on the flange nozzle
1 Fit a gasket (included with the flange mounting bracket)1 on the flange
mounting bracket, and then mount the sensor or sensor head on the flange
mounting bracket. Recommended tightening torque: 30 N·m for the FR-LM20 and
1.5 N·m for the FR-LP20
2 Insert a flange gasket1 between the parts, and then use nuts and bolts
to mount the flange mounting bracket on the flange nozzle. 1 Rubber packing is
not required if an airtight seal is not required.
Bolts: not included Sensor or sensor head
Gasket (OP-88891): included with the flange mounting bracket
Flange mounting bracket (equivalent to JIS5K/10K 50A, DIN PN10 DN50, ANSI
class 150 2″): OP-88880 (SUS304)/OP-88885 (PVC)
Flange gasket: not included
Flange: not included
Nuts: not included
Mounting directly on a top panel (using a mounting bracket, not a nut)
1 Insert the threads of the sensor or sensor head into a general
mounting bracket. Recommended tightening torque: 30 N·m for the FR-LM20 and
1.5 N·m for the FR-LP20
2 In the top panel, drill a hole with a diameter of 49 mm and four screw
holes for securing the general mounting bracket, and then use screws to secure
the general mounting bracket on this panel.
Sensor or sensor head
M5 screws: not included
General mounting bracket: OP-88881 (SUS304)/OP-88919 (PPS)
Top panel (thickness: 10 mm or less)
Mounting directly on a top panel (screwing in the device)
1 Drill a G1-1/2 screw hole in the top panel. 2 Fit a gasket1 on the threads
of the sensor or sensor head, and then
screw this device into the top panel. Recommended tightening torque: 30 N·m
for the FR-LM20 and 1.5 N·m for the FR-LP20 1 A gasket is not required if an
airtight seal is not required
Sensor or sensor head
Gasket: OP-88890 (inorganic fiber + oil-resistant rubber)/OP-88891 (FKM)
Mounting on a ferrule
1 Attach the OP-88920 aligned with the sides of the lens unit at the
bottom of the sensor.
2 Mount the gasket included with the ferrule mounting bracket on the
top of this bracket.
3 Mount the ferrule mounting bracket on the sensor or sensor head.
Recommended tightening torque: 30 N·m for the FR-LM20/LS20 and 1.5 N·m for the
FR-LP20
4 Mount the ferrule gasket on the ferrule, and then mount this assembly
on the sensor using a clamp.
Sensor or sensor head Gasket: OP-88920 (EPDM)
Gasket: included with the ferrule mounting bracket Ferrule mounting bracket
(2S): OP-88888/ OP-88889 (with leakage port)
- Mount on a ferrule that meets the following dimensions. LD L must not exceed 127 mm.
%
Recommended installation conditions
The FR Series beam widens as follows. Ensure there are no metal obstacles in the following range.
0
Mounting with separated display (standard model/chemical model)
1 Remove the two screws (M3
screws for the FR-LM20 and M4 screws for the FR-LP20) from the back, and then
pull the display away from the sensor head.
2 Connect the display and the
sensor head with a dedicated cable (FR-LMS5 or FR-LPS5), and then tighten the
screws in two locations on the display and sensor head to secure the cable.
Recommended tightening torque: 6.3 N·m (FR-LMS5)/0.2 N·m (FR-LP20)
Point Applying more than the recommended tightening torque may damage the
screws.
3 Secure the display with the Panel Mounting Bracket FR-LB1 or Rear
Mounting Bracket FR-LB2.
Measuring distance: m –
Mounting directly on a top panel (mounting with a nut)
1 Drill a hole with a diameter of 49 mm in the top panel. 2 Fit a gasket1 on
the threads of the sensor or sensor head, and then
insert the threads in the hole in the top panel.
3 Attach a nut from the bottom of the top panel.
Recommended tightening torque: 30 N·m for the FR-LM20 and 1.5 N·m for the FR-
LP20 1 A gasket is not required if an airtight seal is not required.
Sensor or sensor head
Gasket: OP-88890 (inorganic fiber + oil-resistant rubber)/OP-88891 (FKM)
Top panel (thickness: up to 16 mm)
Nut: OP-88883 (SUS304)/OP-88887 (PPS)
Top panel (thickness: 24 mm or less)
Mounting on an inner wall
1 Mount a side mounting bracket on a wall with M6 screws. 2 Insert the sensor
or sensor head into the bracket, and then attach a
nut from the bottom of the bracket. Recommended tightening torque: 30 N·m for
the FR-LM20 and 1.5 N·m for the FR-LP20
Sensor or sensor head
Wall surface
Side mounting bracket: OP-88882 (SUS304)/ OP-88886 (PPS) M6 screws: not
included (eight for the OP-88882 and four for the OP-88886) Nut: included with
the side mounting bracket (the OP-88883 for the OP-88882 and the OP-88887 for
the OP-88886)
5 Oil-based liquid or powder
Water-soluble liquid 10
15
20
-10
-5
0
5
10
Beam widening: m
1 In the case of a metal wall with a smooth surface (having depressions and protrusions shorter than 2.5 mm), there are no problems if the wall is within the range.
Detection may be unstable at close distances. Install the sensor or sensor head at the following recommended distances from the expected upper limit of the liquid level.
Reference surface of the sensor
Highest expected liquid level
Water-soluble liquid: 30 mm Oil-based liquid (specific conductive capacity less than 10): 120 mm Powder (specific conductive capacity of 2.2): 170 mm
Adjusting the orientation of an installed sensor
The case can be rotated up to approximately 340°. After securing the sensor to
a mounting bracket or something similar, rotate the case while holding the
hexagon part in place with a wrench to orient the display as desired.
Point The case of the sanitary model (FR-LS20) does not rotate. Adjust its
orientation when mounting the sensor on a ferrule.
E3
E4
Attaching/removing the cover (sanitary model)
· Removing the cover Turn the cover counterclockwise, and then remove it.
· Attaching the cover Align the indentation on the cover with the entrance to the groove, and then turn the cover clockwise.
Wiring Pin layout
· Power cable connector pin layout
2
1
8
3
7
Pin # 1 2
Color White Brown
Description Analog output Power supply (24 VDC)
4
6
5
3
Green OUT3
4
Yellow OUT4
5
Gray OUT1
6
Pink OUT2*
7
Blue 0 V
8
Red OUT5
*IO-Link-compatible wire when connecting an IO-Link device
Independently insulate any unused input/output wires.
Load (input device)
(1) Control output wiring · NPN
Brown OUT Blue (2) Analog output wiring Brown White
24 V 0 V 24 V
Analog current input device
· PNP
Brown
24 V
OUT
Blue 0 V
Blue
0 V * It is possible to switch between 4-20 mA and 0-20 mA using settings.
Connecting the Power Cable
1 Plug the power cable into the power cable connector.
When connecting the connector, plug it in straight and fix it firmly. NOTICE
If the tightening is not sufficient, the connector may loosen, which may
lead to contact failures.
Initial Setting at First Startup
When the sensor is turned on for the first time, configure the following
initial settings. · Select parameters with the U and V keys and use the z Set
key to confirm entries. · To return to the previous screen, press the Y key.
I/O settings
PNP / NPN PNP
Number of control outputs 2
External input OFF
Set and continue
Back
Set
Underlined items are initial values
Language PNP/NPN
ENGLISH, , , DEUTSCH PNP, NPN
Number of control outputs 0, 1, 2, 3, 4, 5
Detection target
Water-soluble liquid, Oily Liquid, Powder
Distance unit
mm (millimeters), m (meters)
Display value scaling Display value unit1 Decimal point position1
OFF, ON No unit, mL, L, hL, m3, g, kg, t, mm, m, % 99999, 9999.9, 999.99, 99.999, 9.9999
Tank shape*1
Straight tank, Spherical tank, Cylindrical tank (horizontal placement), Cone base tank, Quadrangular pyramid base tank, Sloped base tank, Multipoint correction
Distance to bottom
0 to 25000 mm
Distance to top surface Height of base1, 2
Tank capacity1
0 to 25000 mm 0 to 25000 mm 0 to 99999
Number of multipoint correction points1, 3
Point 1_Height1, 3, 4
2 to 32 0 to 99999
Point 1_Current value
*1, 3, 4
0 to 99999
Set value 1*5
0 to 99999
Output logic 1*5
N.O., N.C.
Indicator pattern*6
Pattern 1, Pattern 2, Pattern 3, Only green, Always Off
1 This item is only displayed when [ON] is selected for “Display value selection.” 2 This item is only displayed when [Cone base tank], [Quadrangular pyramid base
tank], or [Sloped base tank] is selected for “Tank shape.” 3 This item is
only displayed when [Multipoint correction] is selected for “Tank
shape.” 4 Points 2 to 32 are displayed depending on the value selected with
Number of
multipoint correction points. 5 Numbers 1 to 5 are displayed depending on the
value selected with Control
outputs. Nothing is displayed if “0” is selected with Control outputs. 6 The
selectable number of patterns varies depending on the set judgment output
count.
· Number of control outputs
At most, there are five outputs, one external input, and one analog output. ·
Set the number of control outputs to use.
The set number of control outputs are assigned in order from OUT1. You can
only use up to four control outputs when you select [ON] for “External input.”
· Other functions can be assigned to outputs to which control outputs are not
assigned. For details on these functions, see the user’s manual. · Each
control output can also be changed to area mode. For details on area mode, see
the user’s manual.
Pin #
5 6 3 4 8 1
Color
Name
Auxiliary output Control
External input
output
Error
Stability Period alarm change
Reset period change
Gray OUT1 3
3
3
3
–
Pink OUT2 3
3
3
3
–
Green OUT3 3
3
3
3
–
Yellow OUT4 3
3
3
3
–
Red OUT5/IN 3
3
3
3
3
White
Analog output
–
–
–
–
–
Analog output
3
IO-Link
- –
· Detection target Select [Water-soluble liquid] if the specific conductive
capacity of the measurement target is 10 or higher, [Oil-based liquid] if the
specific conductive capacity of the target is less than 10, and [Powder] if
the target is a powder. If you select [Oil-based liquid], the area from the
base to 10% of the height of the tank on the side far from the sensor is
masked. For details, see the user’s manual.
Point Selecting an incorrect detection target may prevent accurate detection
of the liquid surface.
· Distance to bottom Enter the distance from the reference surface of the
sensor to the bottom of the tank. For the position of the reference surface of
the sensor when using a mounting bracket, see the dimensions provided in, for
example, the catalog. The height of the liquid surface from the bottom of the
tank is displayed as the current value with the position indicated by this
distance used as the zero point (0%).
Reference surface of the sensor
Distance to bottom
Liquid level
Current value
Tank bottom (zero point)
Reference surface of the sensor
· Distance to top surface
Enter the distance from the reference surface of the sensor to the top surface
of the tank. This position is 100% in the % display.
Distance to top surface
Reference surface of the sensor 100%
0% · Display value selection
OFF: The height of the liquid level is displayed. ON : The display value is
scaled and converted to volume or weight. For scaling, you can select the tank
shape or enter a conversion table with up to 32 multipoint correction points.
For details on multipoint correction, see the user’s manual.
· Output logic 1 N.O.: Control output turns on when the current value exceeds
one of the set values. N.C.: Control output turns on when the current value
drops below one of the set values.
· Indicator pattern You can select the lighting order of the ring indicator
according to the liquid surface position. The indicator color is also linked
to the color bar on the current value screen.
Set value 1
Set value 2
Set value 3
Set value 4
The number of selectable indicator orders varies depending on the number of control outputs. Select the indicator pattern from those shown below. To use a different pattern, select Custom. For details on how to set custom order, see the user’s manual.
Number of control outputs
Order 1
Order 2
Order 3 Only green Always Off
0
Green
Red
Green
1
Green
Red
Green Green
Red
Green
Red
Green
2
Yellow
Yellow
Green
Green
Green
Red
Red
Green
Red
Red
Red
Green
Yellow
Green
Green
Green
3
Green
Yellow
Green
Green
Red
Red
Green
Green
Red
Red
Yellow
Green
4
Green
Green
Yellow
Green
Red
Red
Red
Red
Yellow
Green
5
Green Green
Green Green
Yellow
Green
Red
Red
Green Green Green Green Green
Green Green Green Green Green Green
Basic Operation Current value screen
2134 mm
% display
42.7 %
Set value confirmation
2134 mm
4500 4000 1000
500
Flow conversion value display*
2134 mm
0
mm/min
Output indicators: The numbers of the on outputs light in orange.
Color bar: The color here is linked to the ring indicator.
Tank view: Indicates the current liquid level.
Set values: Show set values 1 to 5.
- This item is only displayed when “ON” is selected for Flow conversion mode.
Changing set values
Press the MENU key on the current value display to enter the menu, and then
select Change set value. Use the S and T keys to adjust the set value, and
then confirm the change with the z Set key.
Menu screen Menu
Current Value Basic installation settings Change set value Settings
Set value
4500 mm
2134
[mm]
5000
4000
Diagnosis function
Select
Set
1000 500
Back
0 Set
E5
E6
Key lock
This function prevents operation mistakes by locking/disabling key operations
to prevent the settings from being easily changed. To require a password when
canceling the key lock, set “Key lock method” to “With password.”
Enabling/disabling the key lock: Hold down the MENU key and the T key for 3
seconds or more. When “Key lock method” is set to “With password,” the
password is required when unlocking the keys.
Reference If the password entered is incorrect, an error will occur, and the
normal screen will appear with the key lock still enabled.
Initializing settings
Press the MODE key on the current value screen to display the menu screen, and
then select “Settings” > “Initialize.”
Maintenance
· Clean deposits and foreign substances on the mounting bracket and the bottom
of the sensor or sensor head as necessary.
· If using the FR-LS20, it is recommended to replace the gasket (OP-88920)
inside the ferrule mounting bracket once a year. At that time, also wipe away
any dirt inside the ferrule mounting bracket with a soft cloth.
Specifications
Item
Measurement range1 Displayable range1
Standard model FR-LM(H)20(L)
Chemical model FR-LP(H)20(L) Max. 20 m 65.6 ft Max. 25 m 82.0 ft
Sanitary model FR-LS20(L)
Specific conductive capacity of target media*2
2 or more
Resolution Accuracy*3
1 mm 0 to 0.5 m: ±5 mm 0.5 to 10 m: ±1 mm 10 m to 20 m: ±2 mm
Control output response time
0.4 s, 1.5 s, 4 s (default), 10 s
Tank pressure
-0.1 to 1 MPa
-0.1 to 0.1 MPa
-0.1 to 1 MPa
Material
Inside the tank
Lens: PTFE Internal packing: FKM entering part: SUS304
Lens: PTFE Internal packing: FKM
entering part: PPS
Lens: PTFE Ferrule internal packing: EPDM
(when using the OP-88920) Ferrule: SUS316L
(when using the OP-88888/88889)
Case
PPS PET PAR
PPS PPSU
SUS304
Connection port
G1-1/2 (40A)
G1-1/2 (40A)
2S ferrule (when using the OP-88888/88889)
Number of control outputs
Max. 5
Output
Contro output/ alarm output
NPN/PNP open collector (switchable), 30 VDC max., 50 mA max. for each output,
residual voltage: 1.4 V max. (50 mA max.),
N.O./N.C. switchable, IO2 also used for IO-Link, IO5 also used for external
input
Analog output
0-20mA/4 to 20 mA, maximum load resistance: 260 (Response time: 0.2 s after comparator output determined [90% response])
Network compatibility
IO-Link v1.1/COM2
Resolution
Analog output accuracy
Zero accuracy
F.S. accuracy
1 mm ±0.1 mA (zero = 4 mA) ±0.2 mA (F.S. = 20 mA)
Ambient temperature
Environmental Ambient humidity resistance Operating coupling
temperature4, 5 Vibration resistance Shock resistance
Built-in and separated display: -20 to +50°C (no freezing)4, 5
Separated head: -20 to +60°C (no freezing)4, 5
Built-in and separated display: -10 to +50°C (no freezing)4, 5
Separated head: -10 to +60°C (no freezing)4, 5
Max. 85%RH (no condensation)
-20 to +60°C (no freezing)4, 5
-20 to +85°C (no freezing)4, 5
-10 to +85°C (no freezing)4, 5
-20 to +100°C (no freezing)4, 5
10 to 500 Hz; Power spectral density: 0.816 G2/Hz; X, Y and Z directions 100 m/s2 (approx. 10 G), 16 ms pulses, 1000 times each for X, Y and Z axes
Enclosure rating
IP67(IEC60529), Enclosure Type 4X(NEMA250)
IP67(IEC60529), IP69K(ISO20653)
Protection circuit
Protection against reverse power connection, output overcurrent, output surge, and reverse output connection
Power voltage
24 VDC+25%/-20% including ripple, Class 2/LPS
Current consumption
56 mA max. (at 20 V)/ 48 mA max. (at 30 V) (excluding load)
75 mA max. (at 20 V)/ 67 mA max. (at 30 V) (excluding load)
56 mA max. (at 20 V)/ 48 mA max. (at 30 V) (excluding load)
Corresponding cable/connector
8-pin M12 connector
1 Value guaranteed with water and the recommended mounting method. With water and the recommended mounting method, measurement is possible right up to the lens surface. An undetectable area on the near side occurs due to the relationship between the environment and the measurement medium. Additionally, the maximum measuring distance decreases.
2 The target shape or the environment may make measurement impossible. 3 This value is guaranteed by KEYENCE inspection facilities. Errors may occur due to your environment. 4 The operating temperature range for each model is as follows.
Ambient temperature Ambient temperature
FR-LM(H)20(L)/LP(H)20(L) 80
70
Separated display
60 50
Built-in display
40
Protection cover attached
30
with built-in display
20
10
0
-10
-20
-20
0
20
40
60 80 100 120
Coupling temperature
FR-LS20(L) 80
70
60
50
40
30
20
10
0
-10
-20
-20
0
20
40
60 80 100 120
Coupling temperature
On the FR-LM20/LP20, selecting [Turns off when no op.] for “Screen brightness”
can alleviate the ambient temperature regulation by 10°C. *5 When performing
SIP with the FR-LM(H)20(L)/LP(H)20(L)/LS20(L), turn the power supply off, and
then perform this operation for 1 hour or less with an ambient temperature of
40°C or less and an internal system temperature of 130°C. Also, be sure to
attach a ferrule mounting bracket and an internal gasket, which are optional
KEYENCE products.
E7
WARRANTIES AND DISCLAIMERS
(1) KEYENCE warrants the Products to be free of defects in materials and
workmanship for a period of one (1) year from the date of shipment. If any
models or samples were shown to Buyer, such models or samples were used merely
to illustrate the general type and quality of the Products and not to
represent that the Products would necessarily conform to said models or
samples. Any Products found to be defective must be shipped to KEYENCE with
all shipping costs paid by Buyer or offered to KEYENCE for inspection and
examination. Upon examination by KEYENCE, KEYENCE, at its sole option, will
refund the purchase price of, or repair or replace at no charge any Products
found to be defective. This warranty does not apply to any defects resulting
from any action of Buyer, including but not limited to improper installation,
improper interfacing, improper repair, unauthorized modification,
misapplication and mishandling, such as exposure to excessive current, heat,
coldness, moisture, vibration or outdoors air. Components which wear are not
warranted.
(2) KEYENCE is pleased to offer suggestions on the use of its various
Products. They are only suggestions, and it is Buyer’s responsibility to
ascertain the fitness of the Products for Buyer’s intended use. KEYENCE will
not be responsible for any damages that may result from the use of the
Products.
(3) The Products and any samples (“Products/Samples”) supplied to Buyer are
not to be used internally in humans, for human transportation, as safety
devices or fail-safe systems, unless their written specifications state
otherwise. Should any Products/ Samples be used in such a manner or misused in
any way, KEYENCE assumes no responsibility, and additionally Buyer will
indemnify KEYENCE and hold KEYENCE harmless from any liability or damage
whatsoever arising out of any misuse of the Products/Samples.
(4) OTHER THAN AS STATED HEREIN, THE PRODUCTS/SAMPLES ARE PROVIDED WITH NO
OTHER WARRANTIES WHATSOEVER. ALL EXPRESS, IMPLIED, AND STATUTORY WARRANTIES,
INCLUDING, WITHOUT LIMITATION, THE WARRANTIES OF MERCHANTABILITY, FITNESS FOR
A PARTICULAR PURPOSE, AND NON-INFRINGEMENT OF PROPRIETARY RIGHTS, ARE
EXPRESSLY DISCLAIMED. IN NO EVENT SHALL KEYENCE AND ITS AFFILIATED ENTITIES BE
LIABLE TO ANY PERSON OR ENTITY FOR ANY DIRECT, INDIRECT, INCIDENTAL, PUNITIVE,
SPECIAL OR CONSEQUENTIAL DAMAGES (INCLUDING, WITHOUT LIMITATION, ANY DAMAGES
RESULTING FROM LOSS OF USE, BUSINESS INTERRUPTION, LOSS OF INFORMATION, LOSS
OR INACCURACY OF DATA, LOSS OF PROFITS, LOSS OF SAVINGS, THE COST OF
PROCUREMENT OF SUBSTITUTED GOODS, SERVICES OR TECHNOLOGIES, OR FOR ANY MATTER
ARISING OUT OF OR IN CONNECTION WITH THE USE OR INABILITY TO USE THE PRODUCTS,
EVEN IF KEYENCE OR ONE OF ITS AFFILIATED ENTITIES WAS ADVISED OF A POSSIBLE
THIRD PARTY’S CLAIM FOR DAMAGES OR ANY OTHER CLAIM AGAINST BUYER. In some
jurisdictions, some of the foregoing warranty disclaimers or damage
limitations may not apply.
BUYER’S TRANSFER OBLIGATIONS: If the Products/Samples purchased by Buyer are
to be resold or delivered to a third party, Buyer must provide such third
party with a copy of this document, all specifications, manuals, catalogs,
leaflets and written information provided to Buyer pertaining to the
Products/Samples.
E 1101-3