KEYENCE LR-TB5000CL Photocell Detection Distance 5m Cable User Guide

June 12, 2024
KEYENCE

KEYENCE LR - logo LR-TB5000CL Photocell Detection Distance 5m Cable
User GuideKEYENCE LR TB5000CL Photocell Detection Distance 5m Cable -
Feager

Instructions for operating
Photocell LR-TB5000CL

About these instructions

This user information describes the default settings for the LR-TB5000CL photocell when it is connected to the SH 100 or SH 300 barrier. The specified setting values are valid for standard applications!

1 .1 Symbols used
Factory setting

1 .2 Further applicable documents

  • Original operating instructions for the photocell
  • Technical documents for the barrier

1 .3 Intended use
The functions and settings described in these instructions are intended for the following product:
– KEYENCE photocell LR-TB5000CL

Fitting and installation

Fitting and installation must be carried out by qualified specialized personnel
▶ Attach the photocell to the barrier. Follow the fitting instructions provided
▶ Connect the photocell to the barrier. Refer to the connection diagram.

Recommended procedure

Step 1: Check the basic settings. Section 4
Step 2: Set the light spot diameter. Section 4.4
Step 3: Make the settings for operation with barrier SH 100 / 300. Section

4.5
Step 4:| Determine and set the distance.| Section 4.6

Operation

4 .1 Control buttons

Button Display function:
MODE – Scroll down text

– Select input value
DISP| – Scroll up text
– Select input value
SET| – Open setting menu
– Save setting value

4 .2 Checking the basic settings
4 .3 Prerequisites

  • Fitting to the barrier is completed
  • The electrical connection between photocell and barrier has been made.
  • The photocell display shows Start Config

▶ Use the MODE button to scroll.

Menu| Required setting value|
---|---|---
Select I / O| OUT1+OUT2|
Select Output| NPN|

▶ Check the two menus and the setting values. When you have checked the setting values, End Config appears in the display.
▶ Press the SET button to complete the check and save the setting values.

Note
It is not possible to change saved basic settings afterwards. To do this, the photocell has to be returned to its factory settings. See section 6.
4 .4 Light spot diameter
Check the setting value for the light spot diameter.
▶ Set a setting value of 4. This setting value corresponds to a 6 mm light spot diameter.
▶ To do this, turn the adjusting screw on the back of the photocell.

4 .5 Settings for SH 100 / SH 300
Required setting values for the photocell when it is connected to barrier SH 100 or SH 300.
▶ Press the MODE button for approx. 3 seconds to open the Settings menu.

The photocell display shows Menu. The menu comprises 8 functions.
▶ To select the functions, press the MODE or DISP buttons.
▶ Press the SET button to open the Settings menu.
▶ To select the setting value, press the MODE or DISP buttons.
▶ Press the SET button to save the setting value.
For all 8 functions, the setting values must be checked and adjusted if necessary .
▶ Check the setting values.
▶ Change the setting values if necessary.

Response Time
Required setting value: 20 ms|
---|---
Output1 Logic
Required setting value: N.C.|
Output1 Mode
Required setting value: Default|
Output1 Timer
Required setting value: Off|
Output2 Logic
Required setting value: N.C.|
Output2 Mode
Required setting value: Default|
Output2 Timer
Required setting value: Off|
Adv . Settings
Required setting value: Off|

When you have made all the settings, the display shows End.
▶ To save all settings, press the SET button.
4 .6 Determining and setting the distance
Distance D is the length of the laser beam. This monitors the area below the barrier boom. The factory setting for the distance D is 500 (500 mm).
4 .6 .1 Determining the distance

KEYENCE LR TB5000CL Photocell Detection Distance 5m Cable -
distanceKEYENCE LR TB5000CL
Photocell Detection Distance 5m Cable - photocell

▶ To determine the distance, place an object approx. 150 mm behind the end of the barrier boom. The photocell calculates the distance automatically and the value appears in the display. In the example, the distance is 4500 mm.
4 .6 .2 Setting the distance for Out1
In order for the photocell to function correctly, the determined distance must be set for outputs Out1 and Out2.
▶ Set the distance for Out1 (example value 4500).

KEYENCE LR TB5000CL Photocell Detection Distance 5m Cable -
Timer4

4 .6 .3 Setting the distance for Out2

▶ Set the distance for Out2. The procedure is the same as for Out1.

Button lock

Activating the button lock| ▶ Press the MODE button and the DISP button at the same time for approx. 3 seconds.
---|---
Deactivating the button lock| ▶ Press the MODE button and the DISP button at the same time for approx. 3 seconds.

Factory setting

Returning the photocell to the factory setting| ▶ Press the MODE button and hold it down.
▶ Press the SET button 5 times in succession.
▶ Press the MODE button. Initialize? will appear. Select YES.
▶ Press the SET button. The photocell initializes and starts with the factory setting.
---|---