Specifications
- Brand: VIZULO
- Model: Orris Basic LED luminaire
- Mounting Instruction: Montzas instrukcija M
- IP Rating: IP65
- Voltage: 198 – 264 V AC
- Manufacture Date: 24.03.2022
- Weight: 7.51 kg (ORB 1), 7.59 kg (ORB 2)
- Dimensions: SCd = 0.09 m, 427 x 825 x 427 mm, Min 60 mm
Product Usage Instructions
Mounting the Luminaire
- Ensure the mounting surface is secure and suitable for installation.
- Follow the provided mounting instructions carefully to position the luminaire correctly.
- Use appropriate tools to securely mount the luminaire as per the specified dimensions.
Direction of Light
The luminaire should be positioned according to the direction of light indicated by removable stickers with arrows.
Caution and Maintenance
Avoid prolonged staring into the luminaire from a distance closer than 3.25 m to prevent discomfort.
Only allow the manufacturer, service agent, or qualified personnel to replace the light source in the luminaire.
Energy Efficiency Class and Light Source Replacement
The luminaire contains light sources with different energy efficiency classes and color rendering index (CRI).
FAQ
Q: Can I replace the light source myself?
A: No, the light source should only be replaced by the manufacturer, service agent, or qualified personnel.
Q: What should I do if I encounter an electrical shock risk?
A: Exercise caution and avoid contact with the electrical components. Seek professional assistance if needed.
Dimensions
Netto Weight
INSTALLTION
Direction of light for asymmetric lens
The luminaire should be positioned so that prolonged staring into the luminaire at a distance closer than 3.25 m is not expected.
The light source contained in this luminaire shall only be replaced by the manufacturer or his service agent or a similar qualified person.
Caution, risk of electrical shock
WARNING!
- Do not touch LED modules!
- Do not put any tools or other items on LED modules!
- In case any LED is physically damaged (example shown below) the warranty is void.
Energy efficiency class of contained light source(s)
MCB/Inrush current table
Tridonic LED driver (No dim/ Midnight dimming/ DALI)
Standard/High density| In-rush current
(peak/duration)
| B10A| B13A| B16A| B20A| B25A| B32A| B40A| C10A| C13A| C16A| C20A| C25A|
C32A| C40A
6-12 LED, 8-26W| 15 A (226 μs)| 19| 25| 30| 37| 46| 59| 74| 31| 41| 50| 61|
76| 97| 122
12-20 LED, 20-43W| 25 A (236 μs)| 12| 16| 20| 26| 32| 41| 52| 20| 26| 33| 43|
53| 68| 86
20-28 LED, 30-64W| 32 A (335 µs)| 6| 8| 10| 13| 16| 20| 26| 10| 13| 16| 21|
26| 33| 42
28-48 LED, 45-96W| 42 A (238 µs)| 6| 8| 10| 13| 16| 20| 26| 10| 13| 17| 22|
27| 35| 44
48-64 LED, 70-144W| 65 A (268 µs)| 3| 4| 5| 6| 7| 9| 12| 5| 7| 8| 10| 12| 16|
20
64-108 LED, 100-211W| 80 A (225 µs)| 4| 6| 8| 10| 12| 16| 20| 6| 10| 13| 16|
20| 25| 32
108-128 LED, 135-288W| 130 A (268 µs)| 1| 2| 2| 3| 3| 4| 6| 2| 3| 4| 5| 6| 8|
10
128-160 LED, 200-380W| 160 A (225 µs)| 2| 3| 4| 5| 6| 8| 10| 3| 5| 6| 8| 10|
12| 16
Eco| | B10A| B13A| B16A| B20A| B25A| B32A| B40A| C10A| C13A| C16A| C20A|
C25A| C32A| C40A
4-4 LED, 9-20W| 15 A (226 μs)| 19| 25| 30| 37| 46| 59| 74| 31| 41| 50| 61| 76|
97| 122
4-8 LED, 20-38W| 25 A (236 μs)| 12| 16| 20| 26| 32| 41| 52| 20| 26| 33| 43|
53| 68| 86
8-12 LED, 30-57W| 32 A (335 µs)| 6| 8| 10| 13| 16| 20| 26| 10| 13| 16| 21| 26|
33| 42
12-24 LED, 45-96W| 42 A (238 µs)| 6| 8| 10| 13| 16| 20| 26| 10| 13| 17| 22|
27| 35| 44
24-32 LED, 70-144W| 65 A (268 µs)| 3| 4| 5| 6| 7| 9| 12| 5| 7| 8| 10| 12| 16|
20
32-52 LED, 100-211W| 80 A (225 µs)| 4| 6| 8| 10| 12| 16| 20| 6| 10| 13| 16|
20| 25| 32
52-64 LED, 135-288W| 130 A (268 µs)| 1| 2| 2| 3| 3| 4| 6| 2| 3| 4| 5| 6| 8| 10
64-96 LED, 200-380W| 160 A (225 µs)| 2| 3| 4| 5| 6| 8| 10| 3| 5| 6| 8| 10| 12|
16
Tridonic LED driver (Zhaga)
Standard/High density| In-rush current
(peak/duration)
| B10A| B13A| B16A| B20A| B25A| B32A| B40A| C10A| C13A| C16A| C20A| C25A|
C32A| C40A
6-12 LED, 8-26W| 15 A (316 μs)| 16| 21| 25| 33| 41| 52| 66| 26| 35| 41| 55|
68| 88| 110
12-20 LED, 20-43W| 20 A (346 μs)| 11| 14| 17| 22| 27| 35| 44| 18| 23| 28| 36|
45| 57| 72
20-28 LED, 30-64W| 28 A (270 µs)| 10| 13| 16| 20| 25| 32| 40| 16| 21| 26| 33|
41| 52| 66
28-48 LED, 45-96W| 38 A (280 µs)| 6| 8| 10| 13| 16| 20| 26| 10| 13| 16| 21|
26| 33| 42
48-64 LED, 70-144W| 56 A (277 µs)| 3| 4| 5| 6| 7| 9| 12| 5| 6| 8| 10| 12| 16|
20
64-108 LED, 100-211W| 85 A (215 µs)| 3| 4| 5| 6| 7| 9| 12| 5| 6| 8| 10| 12|
16| 20
108-128 LED, 135-288W| 112 A (277 µs)| 1| 2| 2| 3| 3| 4| 6| 2| 3| 4| 5| 6| 8|
10
128-160 LED, 200-380W| 170 A (215 µs)| 1| 2| 2| 3| 3| 4| 6| 2| 3| 4| 5| 6| 8|
10
| | | | | | | | | | | | | | |
Eco| | B10A| B13A| B16A| B20A| B25A| B32A| B40A| C10A| C13A| C16A| C20A|
C25A| C32A| C40A
4-4 LED, 9-20W| 15 A (316 μs)| 16| 21| 25| 33| 41| 52| 66| 26| 35| 41| 55| 68|
88| 110
4-8 LED, 20-39W| 20 A (346 μs)| 11| 14| 17| 22| 27| 35| 44| 18| 23| 28| 36|
45| 57| 72
8-12 LED, 30-57W| 28 A (270 µs)| 10| 13| 16| 20| 25| 32| 40| 16| 21| 26| 33|
41| 52| 66
12-24 LED, 45-96W| 38 A (280 µs)| 6| 8| 10| 13| 16| 20| 26| 10| 13| 16| 21|
26| 33| 42
24-32 LED, 70-144W| 56 A (277 µs)| 3| 4| 5| 6| 7| 9| 12| 5| 6| 8| 10| 12| 16|
20
32-52 LED, 100-211W| 85 A (215 µs)| 3| 4| 5| 6| 7| 9| 12| 5| 6| 8| 10| 12| 16|
20
52-64 LED, 135-288W| 112 A (277 µs)| 1| 2| 2| 3| 3| 4| 6| 2| 3| 4| 5| 6| 8| 10
64-96 LED, 200-380W| 170 A (215 µs)| 1| 2| 2| 3| 3| 4| 6| 2| 3| 4| 5| 6| 8| 10
Terms of use and maintenance
Before luminaire is turned on, it should be mounted according with this
mounting instruction or any other applicable regulations.
Mounting instructions
Mounting of luminaire must be performed by a qualified person according with following instructions:
- The warranty of luminaire does not apply, if the mounting of luminaire has been performed in precipitation (rain, snow, hail).
- The warranty of luminaire does not apply, if a control system unauthorized by VIZULO or an inapplicable LED driver has been used to drive the luminaire.
- The warranty of luminaire does not apply, if it has been used in an unsuitable ambient temperature or has been supplied by voltage outside of the specified range.
- The warranty of luminaire does not apply, if the LED driver program has been changed in any way.
- The warranty of the luminaire does not apply, if the logged history data of the LED driver has been deleted without the permission of VIZULO.
- The warranty of luminaire does not apply, if it has been mounted in unspecified angles or upside down (luminaire glass directed up), or it has been completely submerged under water.
Safety instructions
Any actions with the luminaire must be performed by a qualified person, who is
certified according with national regulations and requirements.
To prevent any accidents person installing the luminaire must follow national
safety requirements and following instructions:
- The label containing technical parameters of the luminaire has to be studied before the work on it has begun.
- Any luminaire build or design changes are prohibited.
- The luminaire must be used in good technical condition and according with this instruction.
- Only VIZULO authorized spare parts and accessories can be used to repair the luminaire.
- The repair of luminaire has to be performed by a qualified and certified person.
Maintenance and repair
Luminaire has to be disconnected from electrical grid before it is opened and/or repaired!
- The person working with the luminaire must follow national regulations and legislations that apply to maintenance and testing of electrical or electronic appliances.
- The luminaire may need to be cleaned depending on its environment. Only a damp cloth or a sponge may be used to clean the luminaire. Use only household detergents diluted by water.
- Only VIZULO authorized spare parts may be used for the luminaire.
- Instruction for changing spare parts must be requested from VIZULO and studied before the repair is attempted.
- LED modules, lens and LED drivers can be changed on an installed luminaire, but it is advised to perform this task indoor to avoid water entering the luminaire.
- Spare parts (lens, LED modules and drivers) should be ordered from the information available on the luminaire label.
References