Specifications:

  • Product Name: Troffer Transformer
  • Type: Volumetric (TTV) / Flat Panel (TTF)
  • Switch Between: 4 Watts & 3 Color Temperatures
  • Control Options: Multiple
  • Works on: 208V & 240V
  • Dimming: Yes
  • CRI: 80+
  • Beam Angle: N/A
  • Rated Life: 100,000 hours
  • Color Temperature Options: 3500K/4000K/5000K
  • UL Listed Fixture: Yes

Product Usage Instructions

Troffer Features:

  • Bracket design for universal troffer fit
  • Trim covers up air gap around frame
  • Fast 3-minute install design
  • Adjustable wattage or color
  • All-in-one can be installed either as a retrofit or a new fixture

Setting the Wattage and CCT:
Use the Flexwatt slide switch to set the wattage and the Flexcolor slide switch to set the color temperature.

Flexwatt Slide Switch Position:

  • 0: 16W (2000-2032LM)
  • 1: 20W (2500-2540LM)
  • 2: 24W (3072-3120LM)

Flexcolor Slide Switch Position:

  • Top (3500K): 28W (3584-3640LM)
  • Middle (4000K): 28W (3500-3556LM)
  • Bottom (5000K): 40W (5160-5300LM)

Flex control:
The fixture comes with 10V dimming and a dim-to-off driver with 12V DC aux power. It can be used with basic PIR fixture level control or advanced Bluetooth mesh sensor control system.

TROFFER TRANSFORMER

PART #
JOB NAME
TYPE

  • Install as a retrofit kit or as a new fixture.
  • 3 sizes to choose from 2×2, 2×4, 1×4.
  • Door style retrofit kit with just one piece, creating a seamless,no air gap look.
  • Choose from a volumetric or a flat panel design.
  • Sensor Ready (SR) for Occupancy and Network Lighting Controls (NLC) – see pages 9-16 for more information.

WATCH HOW EASY IT IS TO INSTALL THE TROFFER TRANSFORMER!

RP-Lighting-RP-TTV-G1-Troffer-Transformer-FIG- \(1\)

RP-Lighting-RP-TTV-G1-Troffer-Transformer-FIG- \(36\)

RP-Lighting-RP-TTV-G1-Troffer-Transformer-FIG- \(37\)

SETTING THE WATTAGE AND CCT W/ FLEXWATT + FLEXCOLOR

FLEXWATT SLIDE SWITCH POSITION

RP-Lighting-RP-TTV-G1-Troffer-Transformer-FIG- \(38\)

FLEXCOLOR SLIDE SWITCH POSITION

RP-Lighting-RP-TTV-G1-Troffer-Transformer-FIG- \(39\)

RP-Lighting-RP-TTV-G1-Troffer-Transformer-FIG- \(2\)

FLEXCONTROL

RP-Lighting-RP-TTV-G1-Troffer-Transformer-FIG- \(3\)

USE W/ BASIC PIR FIXTURE LEVEL CONTROL OR ADVANCED BLUETOOTH MESH SENSOR CONTROL SYSTEM

PART NUMBER BUILDER

RP-Lighting-RP-TTV-G1-Troffer-Transformer-FIG- \(43\)

RP-Lighting-RP-TTV-G1-Troffer-Transformer-FIG- \(44\)

PART NUMBER BUILDER

RP-Lighting-RP-TTV-G1-Troffer-Transformer-FIG- \(41\) RP-Lighting-RP-TTV-G1-Troffer-Transformer-FIG-
\(42\)

INSTALLATION GUIDE / RETROFIT

  1. SHUT OFF POWER TO THE FIXTURE
    Open the fixture lens and remove the existing fluorescent lamps, ballast cover and lens. Disconnect the ballast from the building’s line voltage.

  2. ATTACH SAFETY ANCHOR TO EXISTING FIXTURE

  3. ATTACH CARABINERS/SAFETY CABLES
    Use the (2) carabiners to connect to the Troffer Transformer safety cables to the anchor points. Now the fixture will be hanging in place to make the install easier. For install onto narrow T-Grid – install centering tabs to holes on trim for guarantee straight fit.

  4. MAKE ELECTRICAL CONNECTIONS
    Connect input power via the included quick disconnect

  5. INSTALL KNIFE-EDGE
    Align the knife-edge of the Troffer Transformer with the T-bar grid and push. The knife will be sandwiched between the T-bar and the old fixture.

  6. COMPLETE THE INSTALL
    Push the other side of the Troffer Transformer up into the existing fixture. With a TORX T30 screwdriver rotate corner screws ½ turn (180°) to secure the Troffer-Transformer in place with expanding latch. (2×4 center latch is ¼ turn – 90°) Install adhesive cover to T30 latch for smooth look. Turn power ON and install is complete!

DIMENSIONS / TTV

AIR
Use the Troffer Transformer Air Return Option (…-AIR) on flat panel or volumetric versions to include air return slots in the fixture trim.

RP-Lighting-RP-TTV-G1-Troffer-Transformer-FIG- \(10\)

TTV DIMENSIONS

RP-Lighting-RP-TTV-G1-Troffer-Transformer-FIG- \(11\)

RP-Lighting-RP-TTV-G1-Troffer-Transformer-FIG- \(12\)

RP-Lighting-RP-TTV-G1-Troffer-Transformer-FIG- \(13\)

RP-Lighting-RP-TTV-G1-Troffer-Transformer-FIG- \(14\)

AIR
Use the Troffer Transformer Air Return Option (…-AIR) on flat panel or volumetric versions to include air return slots in the fixture trim.

RP-Lighting-RP-TTV-G1-Troffer-Transformer-FIG- \(15\)

TTF DIMENSIONS

RP-Lighting-RP-TTV-G1-Troffer-Transformer-FIG- \(16\)

RP-Lighting-RP-TTV-G1-Troffer-Transformer-FIG- \(17\)

RP-Lighting-RP-TTV-G1-Troffer-Transformer-FIG- \(18\)

IR11 REMOTE

REMOTE CONTROL SETTINGS

If satisfied with default settings, remote control is not needed. If settings need to be changed, optional remote control (RP-OC2-REMOTE-IR11), is required.

PERMANENT ON FUNCTION
Press ‘ON’ button, fixture goes to permanent on mode, sensor is disabled. With memory function against power failure.

  • Press ‘Auto’ or ‘Reset’ to quit this mode.

PERMANENT OFF FUNCTION
Press ‘OFF’ button, fixture goes to permanent off mode, sensor is disabled.
With memory function against power failure

  • Press ‘Auto’ or ‘Reset’ learn’ to quit this mode.

SENSOR MODE
Press ‘Auto’ button, the sensor starts to work and all settings remain the same as the latest status before the light was switched on/off.

RESET FUNCTION
Press ‘Reset’ button, all settings go back to factory default settings.

FACTORY DEFAULT SETTINGS – REMOTE REQUIRED TO CHANGE SETTINGS
Daylight sensor=disable
Hold time=5min
Twilight time=+∞
Twilight level=30%
NOTE daylight harvest function is disabled in factory default mode. Choose the appropriate lux threshold first to activate the daylight harvest function.

DISABLE DAYLIGHT SENSOR
Press ‘Disable’ button, the daylight sensor will be disabled, the motion sensor will work always, even in daytime.

TEST MODE
Test mode’ is used for testing purpose only, for users to check the detec-tion range.
**Quit test mode by pressing any other button of ‘Hold time’. The sensor settings are changed accordingly.

TEST MODE SETTINGS
Daylight sensor=disable
Hold time=3s
Twilight time=N/A
Twilight level=N/A

RP-Lighting-RP-TTV-G1-Troffer-Transformer-FIG- \(25\)

  • THE LIGHT WILL BLINK (~0.5S) ONCE WHEN SENSOR SUCCESSFULLY RECEIVES RC SIGNAL AFTER PRESSING ANY VALID BUTTON.
  • WHEN“TWILIGHT LEVEL”SET AT 0%, IT BE-COMES ON/OFF CONTROL.

MOTION SENSOR W/ DAYLIGHT HARVESTING

SMART PHOTOCELL DAYLIGHT HARVESTING SENSOR

  • Occupancy & daylight sensor.
  • Lighting control scenarios adjusts the light based on occupancy, daylight and or manual control.
  • Powered by 0-10V/12V AUX connections.
  • Passive infrared (PIR) occupancy sensor.
  • Uses less than 0.1W in standby mode.
  • Bluetooth mesh compliant.
  • Bluetooth operation frequency – 2.4GHz – 2.483 GHz.
  • Bluetooth transmission range – 10-30m (typical indoor).
  • Input current – ≥20mA.
  • Individual/group addressing.
  • Decentralized control (no single point of failure).
  • Compact & flexible ready to be integrated into any suitable luminaire.
  • Detection range – Max 5m.

PIR MOTION SENSOR

RP-Lighting-RP-TTV-G1-Troffer-Transformer-FIG- \(27\)

RP-Lighting-RP-TTV-G1-Troffer-Transformer-FIG- \(45\)

TROFFER TRANSFORMER

PROVISIONING / CONFIGURATIONS
The Bluetooth Mesh sensor is in the Unprovisioned Mode until it is provisioned by a “Provisioner”,which typically is a smart phone with a Bluetooth Mesh compatible app. It is highly recommended to use the Silvair iOS app (https://silvair.com/en/) to make the Bluetooth Mesh sensor fully work. Please contact Silvair at business@silvair.com about how to get and use the app.

BLUETOOTH MESH FACTORY RESET
This device can be easily reset by pressing the “Reset” button for 5 seconds. Once the factory reset is done successfully, the luminaire flashes and then permanent on, then the device is being able to be re-commissioned by SILVAIR app

ACCESSING THE SILVAIR APP

RP-Lighting-RP-TTV-G1-Troffer-Transformer-FIG- \(28\)

NETWORK STATUS INDICATION (BY GREEN LED)

SIZE 120V 208V
UNPROVISIONED 30ms ON 300ms OFF
--- --- ---
PROVISIONED 30ms ON 2000ms OFF
FACTORY RESET 100ms ON 1000ms OFF
MESH PACKAGE RECEIVED 30ms ON 50ms OFF
ATTENTION (FROM NETWORK) 500ms ON 500ms OFF

LIGHTING CONTROL SCENARIOS

Multiple lighting control scenarios are available once the Bluetooth mesh sensor is provisioned. At each scenario, duration, fade time and target brightness can be configured at any time with the iOS app.

EXAMPLE OCCUPANCY SENARIO

RP-Lighting-RP-TTV-G1-Troffer-Transformer-FIG- \(29\)

EXAMPLE OCCUPANCY SENARIO W/ DAYLIGHT HARVESTING

RP-Lighting-RP-TTV-G1-Troffer-Transformer-FIG- \(30\)

EXAMPLE VACANCY SENARIO

RP-Lighting-RP-TTV-G1-Troffer-Transformer-FIG- \(31\)

EXAMPLE OCCUPANCY SENARIO W/ MANUAL OVERRIDE

RP-Lighting-RP-TTV-G1-Troffer-Transformer-FIG- \(32\)

WIRING DIAGRAM

RP-Lighting-RP-TTV-G1-Troffer-Transformer-FIG- \(33\)

DETECTION PATTERN

RP-Lighting-RP-TTV-G1-Troffer-Transformer-FIG- \(34\) RP-Lighting-RP-TTV-G1-Troffer-Transformer-FIG-
\(35\)

HEADQUARTERS & TRAINING CENTER • Cary, IL
INNOVATION & MANUFACTURING CENTER • Middleton, MA
847.380.3540 • led-lIc.com • sales@led-lIc.com
04.01.24 Information is subject to change without notice.

FAQ

How do I install the Troffer Transformer?

The Troffer Transformer is designed for easy installation.Follow the provided instructions to mount and connect the transformer to your existing electrical system.

Can I use the Troffer Transformer as a retrofit?

Yes, the Troffer Transformer can be installed either as a retrofit or as a new fixture, offering flexibility in upgrading your lighting setup.

What are the available control options for the Troffer Transformer?

The Troffer Transformer offers multiple control options,including dimming, PIR occupancy sensor, wireless grouping sensor,low energy network options, and emergency battery backup.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals