TOSHIBA RAV-GM1601AT8P-E Air Conditioner Installation Guide

June 1, 2024
Toshiba

TOSHIBA-logo

TOSHIBA RAV-GM1601AT8P-E Air Conditioner

Specifications

  • Model: RAV-GM1601AT8P-E RAV-GM1601AT8JP-E
  • For commercial use
  • Refrigerant: R32
  • Compliance: IEC 61000-3-12
  • Center of gravity: 335mm x 150mm x 650mm

Product Usage Instructions

1. Installation of the Outdoor Unit:

Follow the Installation Manual provided for the outdoor unit carefully. Ensure proper spacing around the outdoor unit to prevent refrigerant leaks. Refer to the manual for detailed instructions on installation space requirements.

2. Connection to Power Supply:

Connect the appliance to the main power supply using a switch with a contact separation of at least 3mm. Do not use pressure washers to clean the air conditioner.

3. Required Tools/Equipment:

Prepare the tools and equipment listed in the manual before starting the installation work. Use exclusively newly prepared tools and equipment for the installation.

Frequently Asked Questions

  • Q: What refrigerant does this air conditioner use?
    • A: This air conditioner uses R32 refrigerant which is environmentally friendly and does not harm the ozone layer.
  • Q: Can I use existing piping for installation?
    • A: When using existing piping, refer to the manual’s Appendix for guidelines on using existing piping with the R32 refrigerant air conditioner.

“`

AIR CONDITIONER (SPLIT TYPE)
Installation Manual

Outdoor Unit
Model name:

RAV-GM1601AT8P-E RAV-GM1601AT8JP-E

For commercial use

Scan QR CODE to access installation and owner’s manual on website. https://www .toshiba-carrier.co.th/manuals/default.aspx
Manual are available in AR/BG/CZ/DA/DE/EL/EN/ES/ET/FI/FR/ HR/HU/IT/LT/LV/NL/NO/PL/PT/RO/RU/SK/SL/SV/TR.

English

Original instruction

Please read this Installation Manual carefully before installing the Air Conditioner. This Manual describes the installation method of the outdoor unit. For installation of the indoor unit, follow the Installation Manual attached to the indoor unit.
ADOPTION OF R32 REFRIGERANT
This air conditioner adopts the HFC refrigerant (R32) which does not destroy the ozone layer. This outdoor unit is designed exclusively for use with R32 refrigerant. Be sure to use in combination with a R32 refrigerant indoor unit.

This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to Ssc (1) at the interface point between the user’s supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit power Ssc greater than or equal to Ssc (1).

Ssc (*1)

Model RAV-GM1601AT8(J)P-E

Single system 1730

Ssc (KVA) Twin system
1730

Triple system 1730

2-EN

Center of gravity

(Unit: mm) Center of gravity
335

Center of gravity

150 650

Cautions for outdoor unit installation space In the event that the outdoor unit is installed in a small space
and refrigerant leaks, accumulation of highly concentrated
the installation space instructions in the Installation Manual, and provide open space on at least one of the four outdoor unit sides. In particular, when both the discharge and intake sides face walls and obstacles are also placed on both sides of the outdoor unit, take steps to provide space wide enough for a person to pass (600 mm or more) on one side to prevent leaked refrigerant from accumulating.
Building or wall

Obstacle

Outdoor unit

600 mm or more

Obstacle

Building or wall
To disconnect the appliance from main power supply This appliance must be connected to the main power supply by
means of a switch with a contact separation of at least 3 mm. Do not wash air conditioners with pressure washers.

3-EN

­ 2 ­

4-EN

Accessory parts

Part name

Q’ty

Shape

Usage

Installation Manual

1

Booklet

For hand this directly to the customer.

Drain nipple

1

Waterproof rubber cap

5

Protective bush

1

Guard material for passage part

1

Rub-Sheet

1

For protecting wires (pipe cover) For protecting passage part (pipe cover) For protecting small lizard.

Safety Manual

1

For hand over directly to the customer.

­ 3 ­

Installation of R32 refrigerant air conditioner

CAUTION
R32 refrigerant air conditioner installation y This air conditioner adopts the HFC refrigerant (R32) which does not destroy ozone layer. Therefore, during installation work, make sure that water, dust, former refrigerant, or refrigerant oil does not enter the R32 refrigerant air conditioner cycle. To prevent mixing of refrigerant or refrigerant oil, the sizes of connecting sections of charge port on the main unit and installation tools are different from those of the conventional refrigerant units. Accordingly, special tools are required for the R32 or R410A refrigerant units. For connecting pipes, use new and
only, so that water and/or dust does not enter. y When using existing piping, refer to “14 Appendix – [1] Existing piping”.

Required Tools/Equipment and Precautions for use
Prepare the tools and equipment listed in the following table before starting the installation work. Newly prepared tools and equipment must be used exclusively.
Legend
: Conventional tools (R32 or R410A) : Prepared newly (Use for R32 only)

Tools / equipment Gauge manifold Charging hose Charging cylinder Gas leak detector Vacuum pump
prevention function Flare tool

Use

How to use tools / equipment

Vacuuming / charging refrigerant and operation check

Conventional tools (R410A) Conventional tools (R410A)

Can not be used

Unusable (Use the electronic refrigerant charging scale)

Charging refrigerant

Conventional tools (R32 or R410A)

Vacuum drying

Conventional tools (R32 or R410A) installed.

Vacuum drying

Conventional tools (R32 or R410A)

Flare machining of pipes

Conventional tools (R410A)

5-EN

6-EN

Bender

Bending pipes

Refrigerant recovery equipment Refrigerant recovery

Torque wrench

Pipe cutter

Cutting pipes

Refrigerant cylinder

Charging refrigerant

Welding machine and nitrogen cylinder

Welding pipes

Electronic refrigerant charging scale

Charging refrigerant

Conventional tools (R410A) Conventional tools (R32 or R410A) Conventional tools (R410A) Conventional tools (R410A) Prepared newly (Use for R32 only) Conventional tools (R410A)
Conventional tools (R32 or R410A)

Refrigerant piping
R32 refrigerant
CAUTION
y y y
Use the following item for the refrigerant piping. Material : Seamless phosphorous deoxidized copper pipe. Ø6.35, Ø9.52, Ø12.7 Wall thickness 0.8 mm or more Ø15.88 Wall thickness 1.0 mm or more
REQUIREMENT
When the refrigerant pipe is long, provide support brackets at intervals of 2.5 to 3 m to clamp the refrigerant pipe. Otherwise, abnormal sound may be generated.

3 Installation conditions

Before installation

Be sure to prepare to the following items before installation.

Length of refrigerant pipe

Length of refrigerant Model pipe connected to
indoor / outdoor unit

Item

GM1601

5 to 50 m

Addition of refrigerant at the local site is unnecessary for refrigerant pipe length up to 30 m. If the refrigerant pipe length exceeds 30 m. Add refrigerant in the amount given in “Charging additional refrigerant”

  • Caution during addition of refrigerant. Charge the refrigerant accurately. Overcharging may cause serious trouble with the compressor.
    y Do not connect a refrigerant pipe that is shorter than 5 m. This may cause a malfunction of the compressor or other devices.

Airtight test
1. Before starting an airtight test, further tighten the spindle valves on the gas and liquid sides.
2. Pressurize the pipe with nitrogen gas charged from the service port to the design pressure (4.15 MPa) to conduct an airtight test.
3. After the airtight test is completed, evacuate the nitrogen gas.

Air purge
y To purge air, use a vacuum pump. y Do not use refrigerant charged in the outdoor unit to
purge air. (The air purge refrigerant is not contained in the outdoor unit.)

Electrical wiring
y interconnection wires with clamps so that they do not come into contact with the cabinet, etc.
Earthing
WARNING
Make sure that proper earthing is provided. Improper earthing may cause an electric shock. For details on how to check earthing, contact the dealer who installed the air conditioner or a professional installation company.
y Proper earthing can prevent charging of electricity on the outdoor unit surface due to the presence of a high frequency in the frequency converter (inverter) of the outdoor unit, as well as prevent electric shock. If the outdoor unit is not properly earthed, you may be exposed to an electric shock.
y Be sure to connect the earth wire. (grounding work) Incomplete grounding can cause an electric shock. Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone wires.
Test run
Turn on the leakage breaker at least 12 hours before starting a test run to protect the compressor during startup.
CAUTION
Incorrect installation work may result in a malfunction or complaints from customers.

7-EN

­ 4 ­

8-EN

­ 5 ­

Installation location

CAUTION

WARNING
Install the outdoor unit properly in a location that is durable enough to support the weight of the RXWGRRUXQLW ,QVXI¿FLHQWGXUDELOLWPDFDXVHWKHRXWGRRUXQLWWR fall, which may result in injury. Pay special attention when installing the unit onto a wall surface.
CAUTION
Do not install the outdoor unit in a location that LVVXEMHFWWRFRPEXVWLEOHJDVOHDNV Accumulation of combustible gas around the outdoor XQLWPDFDXVHD¿UH
Install the outdoor unit in a location that meets the IROORZLQJFRQGLWLRQVDIWHUWKHFXVWRPHU¶VFRQVHQW LVREWDLQHG y A well-ventilated location free from obstacles near
the air intakes and air discharge. y A location that is not exposed to rain or direct
sunlight. y A location that does not increase the operating noise
or vibration of the outdoor unit. y A location that does not produce any drainage
problems from discharged water.
Do not install the outdoor unit in the following ORFDWLRQV y A location with a saline atmosphere (coastal area)
RURQHWKDWLVIXOORIVXO¿GHJDVKRWVSULQJDUHD (Special maintenance is required). y A location subject to oil, vapor, oily smoke, or corrosive gases. y A location in which organic solvent is used. y Places where iron or other metal dust is present. ,Iiron or other metal dust adheres to or collects on WKHinterior of the air conditioner, it may spontaneously FRPEXVWDQGVWDUWD¿UH y A location where high-frequency equipment (including inverter equipment, private power generator, medical equipment, and communication equipment) is used (Installation in such a location may cause malfunction of the air conditioner, abnormal control or problems due to noise from such equipment). y A location in which the discharged air of the outdoor unit blows against the window of a neighboring house. y A location where the operating noise of the outdoor unit is transmitted. y When the outdoor unit is installed in an elevated position, be sure to secure its feet. y A location in which drain water poses any problems.
9-EN

1 Install the outdoor unit in a location where
WKHGLVFKDUJHDLULVQRWEORFNHG
2 When an outdoor unit is installed in a
location that is always exposed to strong winds like a coast or on the high stories of a building, secure normal fan operation by XVLQJDGXFWRUZLQGVKLHOG
3 When installing the outdoor unit in a
location that is constantly exposed to strong winds such as on the upper stairs or rooftop of a building, apply the ZLQGSURR¿QJPHDVXUHVUHIHUUHGWRLQWKH IROORZLQJH[DPSOHV

  1. Install the unit so that its discharge port faces the wall of the building. Keep a distance 500 mm or more between the unit and wall surface.
    500 mm

Wall

  1. Consider the wind direction during the operational season of the air conditioner, and install the unit so that the discharge port is set at a right angle relative to the wind direction.

Strong wind

Strong wind

y When using an air conditioner under low outside temperature conditions (Outside temp: -5°C or lower) in COOL mode, prepare a duct or wind shield so that it is not affected by the wind.

Snow hood Snow hood

Necessary space for installation (Unit: mm)
Single unit installation

When there is an obstacle on the back side (Front, sides, and top are free)

When there is an obstacle on the front side (Back, sides, and top are free)

When there are obstacles on the front and back sides (Sides and top are free)

150 or more

500 or more

150 or more 1000 or
more

When there are obstacles on the top and front sides (Back and sides are free)
1000 or more

When there are obstacles on the back and top sides (Front and sides are free)
500 or more

When there are obstacles on the back and sides (Front and top are free) * The height of the obstacle should
be lower than that of the outdoor unit.

1000 or more

150 or more

150 or more

300 or more

200 or more

10-EN

Serial unit installation

  • When the outdoor temperature is high, the cooling capability may be decreased because of an equipment protection operation.

When there is an obstacle on the back side (Front, sides, and top are free)

When there are obstacles on the back and top sides (Front and sides are free)

When there is an obstacle on the front side (Back, sides, and top are free)

500 or more

300 or more

300 or more

200 or more

300 or more

300 or more

200 or more

300 or more 300 or
more

When there are obstacles on the back and sides (Front and top are free) * The height of the obstacle should be
lower than that of the outdoor unit.

When there are obstacles on the front and back sides (Sides and top are free)

1000 or more

150 or more

300 or more

300 or more 300 or
more

200 or more

300 or more 300 or more

200 or more 1000 or more

Single unit multiple-row installation (Top and both sides are free) * The height of the obstacle should be
lower than that of the outdoor unit.
1500 or more

300 or 1000 or more more

200 or more
2000 or more

Multiple unit multiple-row installation (Top, both sides, and front are free)

300 or more

300 or more 300 or more
300 or more

300 or more 300 or more

200 or more
1500 or more 300 or more 1000 or more

11-EN

Installation of outdoor unit
y Before installation, check the strength and horizontalness of the base so that abnormal sounds do not emanate.
y

(Anchor bolt, nut: M10 × 4 pairs)

Drain hole 525

150

600

(Unit: mm) 150

Set the out margin of the anchor bolt to 15 mm or less.
15 mm or less
y When water is to be drained through the drain hose, attach the following drain nipple and waterproof rubber cap, and use the drain hose (Inner dia.: 16 mm) sold on the market. Also seal knockout hole and the screws securely with silicone material, etc., to prevent water from leaking. Some conditions may cause dewing or dripping of water.
y When collectively draining discharged water completely, use a drain pan.

400 365
45

Drain hole Drain nipple mounting hole
y and vibration-proof rubber pads to directly support

with and underneath the bottom plate of the outdoor unit. * When installing the foundation for an outdoor unit with downward piping, consider the piping work.

Correct

Fixing leg

Absorb vibration with vibration-proof
rubber pads

Foundation

Correct

Bottom plate of outdoor unit

Foundation
leg that is in contact with and underneath the bottom plate of the outdoor unit.

If only the end of
supported, it may deform.

Incorrect
Do not support the outdoor unit only

Foundation
­ 6 ­

Drain nipple

Waterproof rubber cap (5 pcs.)

Knockout hole

Drain nipple Waterproof rubber cap

For reference
If a heating operation is to be continuously performed for a long time under the condition that the outdoor temperature is 0°C or lower, draining defrosted water
resulting in trouble with the cabinet or fan. It is recommended to procure an anti-freeze heater locally in order to safely install the air conditioner. For details, contact the dealer.

WARNING
y Be sure to install the outdoor unit in a place able to bear its weight.

resulting in human injury.

y Perform

installation work to protect

against strong wind and earthquakes.

EN

If the outdoor unit is imperfectly installed, an

accident by falling or dropping may be caused.

12-EN

Refrigerant piping

Refrigerant Piping
1. Use the following items for the refrigerant piping. Material : Seamless phosphorous deoxidized copper pipe. Ø9.52 Wall thickness 0.8 mm or more Ø15.88 Wall thickness 1.0 mm or more Do not use any copper pipes with a wall thickness less than these thicknesses.
Knockout of pipe cover
Knockout procedure

  • Be sure to wear heavy work gloves while working. Supplied protective bush

Rear direction

Supplied passage hole guard material * Attach the guard material
securely so that it does not come loose.
Sticking RUBBER SHEET
PIPE-CONNECT follow as the picture.

Side direction

Front direction Bottom direction
y The indoor / outdoor connecting pipes can be connected in 4 directions. Take off the knockout part of the pipe cover through which pipes or wires will pass through the base plate.
y Detach the pipe cover and tap on the knockout section a few times with the shank of a screwdriver. A knockout hole can easily be punched.
y After punching out the knockout hole, remove burrs from the hole and then install the supplied protective bush and guard material around the passage hole to protect wires and pipes. Be sure to attach the pipe covers after pipes have been connected. Cut the slits under the pipe covers to facilitate the installation. After connecting the pipes, be sure to mount the pipe cover. The pipe cover is easily mounted by cutting off the slit at the lower part of the pipe cover.

RUBBER SHEET

Optional installation parts (Locally procured)

Parts name

Refrigerant piping A Liquid side: Ø9.5 mm
Gas side: Ø15.9 mm

B

Pipe insulating material (polyethylene foam, 10 mm thick)

C Putty, PVC tape

Q’ty One each
1 One each

­ 7 ­

Refrigerant piping connection

CAUTION
IMPORTANT 4 POINTS FOR PIPING WORK 1.
joints are not allowed indoors. When mechanical connectors are reused indoors, sealing parts shall be renewed.
part shall be refabricated. 2. Tight connection (between pipes and unit) 3. Evacuate the air in the connecting pipes by using
VACUUM PUMP. 4. Check the gas leakage. (Connected points)

Piping connection Liquid side
Outer diameter Ø9.5 mm

Thickness 0.8 mm

Gas side Outer diameter
Ø15.9 mm

Thickness 1.0 mm

Flaring
1. Cut the pipe with a pipe cutter. Be sure to remove burrs that may cause a gas leak.
2. pipe.

or those for R32.

However, the conventional tools can be used by adjusting the projection margin of the copper pipe.

Projection margin in

B (Unit: mm)

B

RIDGID (Clutch type)

Outer dia. of copper pipe
9.5 15.9

R32/R410A tool used
0 to 0.5

Conventional tool used
1.0 to 1.5

Flaring dia. size: A (Unit: mm) A

Outer dia. of copper pipe 9.5 15.9

A

+0 ­0.4

13.2

19.7

CAUTION
y when removing burrs.
y Flare processing under the condition of scratches
cause refrigerant gas leak. y

processing. y
surface.

Tightening of connecting part

1 Align the centers of the connecting pipes

and fully tighten the

nut with your

Then the nut with a wrench as

shown in the

and tighten it with a

torque wrench.

Half union or packed valve

Flare nut

Externally threaded side

Internally threaded side

Fix with wrench.

Tighten with torque wrench.

2 As shown in the

be sure to use two

wrenches to loosen or tighten the

nut

of the valve on the gas side. If you use a

single crescent, the

nut cannot be

tightened to the required tightening torque.

On the other hand, use a single crescent to

the liquid side.

13-EN

14-EN

2XWHUGLDRIFRSSHUSLSH 9.5 mm (dia.) 15.9 mm (dia.)

(Unit: N·m) Tightening torque 34 to 42 (3.4 to 4.2 kgf·m) 68 to 82 (6.8 to 8.2 kgf·m)

Cover

Cap Loosened

Piping valve Tightened

Flare nut 9DOYHDWJDVVLGH

CAUTION
y Do not put the crescent wrench on the cap or cover. The valve may break.
y If applying excessive torque, the nut may break according to some installation conditions.

Incorrect

Cover

Cap

· After the installation work, be sure to check for gas leaks of the pipe connections with nitrogen.
7KHUHIRUHXVLQJDWRUTXHZUHQFKWLJKWHQWKHÀDUH pipe connecting sections that connect the indoor/ RXWGRRUXQLWVDWWKHVSHFL¿HGWLJKWHQLQJWRUTXH Incomplete connections may cause not only a gas leak, but also trouble with the refrigeration cycle.
Do not apply refrigerating machine oil to the ÀDUHGVXUIDFH
15-EN

Refrigerant pipe length

Single

Allowable pipe length (m) Total length L 50

Height difference (Indoor-outdoor H) (m)

Indoor unit: Upper

Outdoor unit: Lower

30

30

Gas side Ø15.9

Pipe diameter (mm)

Liquid side Ø9.5

Number of bent portions 10 or less

Simultaneous twin, triple

System
TWIN TRIPLE

Allowable pipe length (m)

Total length y12 y13 y14 Maximum

Distributed
pipes y2 y3 y4 Maximum

Distributed
pipes y3±2 y4±2 y4±3 Maximum

50

15

10

50

15

10

Height difference (m) (Indoor-outdoor H)

Indoor unit: Upper

Indoor-Indoor

Outdoor unit:

¨K

Lower

30

30

0.5

30

30

0.5

System
TWIN TRIPLE

Pipe diameter (mm)

Main pipe

Branching pipe

Gas side

Liquid side

Gas side

Liquid side

Ø15.9

Ø9.5

Ø15.9

Ø9.5

Ø15.9

Ø9.5

Ø12.7

Ø6.4

Number of bent portions
10 or less 10 or less

Figure of Single Indoor unit

Figure of simultaneous twin

Indoor unit

Indoor unit

Figure of Simultaneous triple

Indoor unit Indoor unit

Indoor unit

Outdoor unit

Outdoor unit

Distributor

2

3

1

Outdoor unit

4

2

3

Distributor
1

L H H H

­ 8 ­

EN
16-EN

5 Air purging

Airtight test

After completing the refrigerant piping work, perform an airtight test. Connect a nitrogen gas cylinder and pressurize the pipes with nitrogen gas as follows to conduct the airtight test.

Low pressure gauge

High pressure gauge

Charge port

VL VH Gauge manifold

CAUTION
or noxious gas for the airtight test.

Pressure reducing valve

Nitrogen gas

Gas leak check

Step 1….Pressurize to 0.5 MPa (5 kg/cm²G) for 5 minutes or longer. Step 2….Pressurize to 1.5 MPa (15 kg/cm²G) for 5 minutes or longer.

Major leaks can be discovered.

Step 3….Pressurize to 4.15 MPa (42 kg/cm²G) for 24 hours. ……………. Micro leaks can be discovered.

(However, note that when the ambient temperature differs during pressurization and after 24 hours, the pressure will change by approximately 0.01 MPa (0.1 kg/cm²G) per 1°C, so this should be compensated.)

If the pressure drops in steps 1 through 3, check the connections for leakage.

  • After the airtight test is completed, evacuate the nitrogen gas.

­ 9 ­

Air purge
With respect to the preservation of the terrestrial environment, adopt “Vacuum pump” to purge air (Evacuate air in the connecting pipes) when installing the unit. y Do not discharge the refrigerant gas to the
atmosphere to preserve the terrestrial environment. y Use a vacuum pump to discharge the air (nitrogen,
etc.) that remains in the set. If air remains, the capacity may decrease. For the vacuum pump, be sure to use one with a

pump stops. (If oil in the vacuum pump is put in an air conditioner including R32, it may cause trouble with the refrigeration cycle.)

Compound pressure gauge
­101 kPa (­76 cmHg)

Pressure gauge Gauge manifold valve

Handle Low
Charge hose (For R32/R410A)

Handle High (Keep fully closed)
Charge hose (For R32/R410A)
Vacuum pump adapter

prevention (For R32/R410A)

Charge port (Valve core (Setting pin))

Vacuum pump
Packed valve at gas side

Vacuum pump
the manifold valve is closed completely.
Attach the connecting port of the charge hose with a projection to push the valve core (setting pin) to the
charge port of the set.
Open Handle Low fully.
Turn ON the vacuum pump. (1)
a little to check that the air passes through. (
2)
Execute vacuuming until the compound pressure gauge
indicates ­101 kPa (­76 cmHg). (1)
Close Handle Low completely.
Turn OFF the vacuum pump.
Leave the vacuum pump as it is for 1 or 2 minutes, and check that the indicator of the compound pressure gauge
does not return.
Open the valve stem or valve handle fully. (First, at liquid side, then gas side)
Disconnect the charge hose from the charge port.
Tighten the valve and caps of the charge port securely.
1: Use the vacuum pump, vacuum pump adapter, and gauge manifold correctly referring to the manuals supplied with each tool before using them.
line of the oil gauge. *2: When air is not charged, check again whether the
connecting port of the discharge hose, which has a
charge port.

17-EN

18-EN

+RZWRRSHQWKHYDOYH
Fully open the valves of the outdoor unit. (First fully open the valve on the liquid side, and then fully open the valve on the gas side.) * Do not open or close the valves when the ambient
temperature is -20°C or less. Doing so may damage the valve O-rings and result in refrigerant leakage.
6HUYLFHYDOYH Open the valve with hexagon wrench. Hexagon wrench size : 5 mm
Valve unit

Charge port

Using a minus screwdriver, turn it counterclockwise by 90° until it hits the stopper. (Full open)

Replenishing refrigerant
This model is a 30 m chargeless type that does not need to have its refrigerant replenished for refrigerant pipes up to 30 m. When a refrigerant pipe longer than PLVXVHGDGGWKHVSHFL¿HGDPRXQWRIUHIULJHUDQW
Refrigerant replenishing procedure
1. After vacuuming the refrigerant pipe, close the valves and then charge the refrigerant while the air conditioner is not working.
2. When the refrigerant cannot be charged to the VSHFL¿HGDPRXQWFKDUJHWKHUHTXLUHGDPRXQWRI refrigerant from the charge port of the valve on the gas side during cooling.
Requirement for replenishing refrigerant
Replenish liquid refrigerant. When gaseous refrigerant is replenished, the refrigerant composition varies, which disables normal operation.

Flare nut

Handle position Groove position

Groove to insert a screwdriver

Closed completely

Opened fully

9DOYHKDQGOLQJSUHFDXWLRQV y Open the valve stem until it strikes the stopper.
It is unnecessary to apply further force. y Securely tighten the cap with a torque wrench.

Cap tightening torque

9DOYHVL]H

Ø9.5 mm Ø15.9 mm

Charge port

14 to 18 N·m (1.4 to 1.8 kgf·m)
33 to 42 N·m (3.3 to 4.2 kgf·m)
14 to 18 N·m (1.4 to 1.8 kgf·m)

Charging additional refrigerant

Figure of Single Indoor unit
Outdoor unit

Figure of simultaneous twin

Indoor unit
Outdoor unit

Indoor unit

2

3

1

Figure of Simultaneous triple

Indoor unit

Indoor unit Indoor unit

Outdoor unit

4

2

3

Distributor
1

Formula for calculating the amount of additional refrigerant (Formula will differ depending on the diameter of the liquid connecting side pipe.) * R1 to R3DUHWKHOHQJWKVRIWKHSLSHVVKRZQLQWKH¿JXUHVDERYH8QLWP

Single

Diameter of connecting pipe (liquid side) R
Ø9.5

Amount of additional refrigerant per meter (g/m)
35

Amount of additional refrigerant (g) = Amount of refrigerant charged for main pipe
îRí

Simultaneous twin

Outdoor unit
GM160

Diameter of connecting pipe (liquid side)

R1 Ø9.5

R2 Ø9.5

R3 Ø9.5

Amount of additional refrigerant per meter (g/m)

35

35

Amount of additional refrigerant (g) = Amount of refrigerant charged for main pipe + amount of refrigerant charged for branch piping
îR1±îR2 + R3 ­ 4)

Triple
Outdoor unit
GM160

Diameter of connecting pipe (liquid side)

R1 Ø9.5

R2 Ø6.4

R3 Ø6.4

R4 Ø6.4

Amount of additional refrigerant per meter (g/m)

35

20

Amount of additional refrigerant (g) = Amount of refrigerant charged for main pipe + amount of refrigerant charged for branch piping
îR1±îR2 + R3 + R4 ­ 6)

EN

19-EN

­ 10 ­

20-EN

Gas leak inspection
Use a leak detector manufactured specially for HFC refrigerant (R32, R410A, R134a, etc.) to perform the R32 gas leak inspection.

  • Leak detectors for conventional HCFC refrigerant (R22, etc.) cannot be used, as the sensitivity drops to approximately 1/40 when used for HFC refrigerant.
    y R32 has a high working pressure, so failure to perform the installation work properly may result in gas leaks such as when the pressure rises during operation. Be sure to perform leak tests on the piping connections.

Indoor unit inspection locations (piping connections) Refrigerant piping
Indoor unit side piping

Outdoor unit inspection locations

Insulating the Pipes
y The temperatures at both the liquid side and gas side will be low during cooling so in order to prevent condensation, be sure to insulate the pipes at both of these sides.
y Insulate the pipes separately for the liquid side and gas side.
y Insulate the branch pipes by following the instructions in the installation manual provided with the branch pipe kit.

REQUIREMENT
Be sure to use an insulating material which can withstand temperatures above 120°C for the gas side pipe since this pipe will become very hot during heating operations.

21-EN

­ 11 ­

Electrical work

WARNING

1 Using the

wires, ensure that the

wires are connected, and wires securely

so that the external tension to the wires

does not affect the connecting part of the

terminals.

2 Be sure to connect the earth wire.
(grounding work) Incomplete grounding may lead to electric shock. Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone wires.
3 The appliance shall be installed in
accordance with national wiring regulations. Capacity shortages of the power circuit or an incomplete installation may cause an electric

y Remove the service panel, and you can see electric parts on the front side.
y A conduit pipe can be installed through the hole for
be used, drill the hole again to an appropriate size. y Be sure to clamp the power wires and indoor/outdoor
connecting wires with a banding band along the connecting pipe so that the wires do not touch the compressor or discharge pipe. (The compressor and the discharge pipe become hot.) Furthermore, be sure to secure these wires with the
electric parts box.
Electrical control box cover
Service panel
Cord clamp

CAUTION
y An installation fuse must be used for the power supply line of this air conditioner.
y Incorrect / incomplete wiring may lead to an
y Prepare an exclusive power supply for the air conditioner.
y This product can be connected to the mains power. Fixed wire connections: A switch that disconnects all poles and has a contact separation of at least 3 mm must be
y Be sure to use the cord clamps attached to the product.
y Do not damage or scratch the conductive core or inner insulator of the power and system interconnection wires when peeling them.
y Use the power and system interconnection wires
protective devices required.

Wire hole

Wiring between indoor unit and outdoor unit

The dashed lines show on-site wiring.

Input power 380­415V 3N~, 50Hz Outdoor unit
380V 3N~, 60Hz

Indoor unit

Wired remote controller

Circuit breaker
y Connect the indoor/outdoor connecting wires to the identical terminal number on the terminal block of each unit. Incorrect connection may cause a failure.

22-EN

For the air conditioner, connect a power wire with the

Model RAV-
Power supply
Maximum running current Installation fuse rating
Power supply wire
System interconnection wires

GM160 380-415 V 3N ~, 50 Hz
380 V 3N ~, 60 Hz
16.1 A
20 A (all types can be used) H07 RN-F or 60245 IEC 66
(5 × 2.5 mm² or more) H07 RN-F or 60245 IEC 66
(4 × 1.5 mm² or more)

How to wire
1. Connect the power supply wires and system interconnection wires to the terminal block of the electrical control box.
2. Tighten the screws of the terminal block, connect the wires matching the terminal numbers (Do not apply tension to the connecting section of the terminal block.)
y Insulate the unsheathed cords (conductors) with electrical insulation tape. Process them so that they do not touch any electrical or metal parts.
y For system interconnection wires, do not use a wire joined to another on the way. Use wires long enough to cover the entire length.

To Indoor unit terminal block

Power supply terminal block

Earth screw

Pipe valve

Earth screw

System interconnection wire

Power supply wire

Stripping length power cord and connecting wire

10
60 (mm)
Earth wire

10

10

40

40

(mm) Connecting line

10 60
Earth wire Power supply

Wiring diagram

  • For details on the remote controller wiring / installation, refer to the Installation Manual enclosed with the remote controller.

Single system Remote controller Remote controller wiring
Indoor side
System interconnection wires Outdoor side

AB 1 23
1 23 N L1(R) L2(Y) L3(B)
Power supply

Simultaneous twin system
Remote controller Remote controller wiring

Remote controller inter-unit wiring

AB
Indoor side

System interconnection wires
Outdoor side

1 23 1 23

N L1(R) L2(Y) L3(B)

Power supply

Indoor side

AB 123

Indoor power inter-unit wiring

Simultaneous triple system

Remote controller
Remote controller wiring

Remote controller inter-unit wiring

Indoor side
Indoor/Outdoor connecting wires
Outdoor side

AB 123

Indoor side

AB 123

123 L1 L2 L3 N

Indoor power inter-unit wiring

Power supply

Remote controller inter-unit wiring

Indoor side

AB 123

Indoor power inter-unit wiring

  • Use 2-core shield wire (MVVS 0.5 to 2.0 mm² or more) for the remote controller wiring in the simultaneous system to prevent noise problems. Be sure to connect both ends of the shield wire to earth leads.
  • Connect earth wires for each indoor unit in the simultaneous system.

23-EN

­ 12 ­

24-EN

­ 13 ­

7 Earthing

12 Functions to be implemented locally

WARNING
Be sure to connect the earth wire. (grounding work) Incomplete grounding may cause an electric shock.
Connect the earth wire properly following applicable technical standards. Connecting the earth wire is essential to preventing electric shock and to reducing noise and electrical charges on the outdoor unit surface due to the high-frequency wave generated by the frequency converter (inverter) in the outdoor unit. If you touch the charged outdoor unit without an earth wire, you may experience an electric shock.

8 Finishing

clamp them to the wall with off-the-shelf support brackets or their equivalent. Keep the power wires and system interconnection wires off the valve on the gas side or pipes that have no heat insulator.

9 Test run

y Turn on the leakage breaker at least 12 hours before starting a test run to protect the compressor during

startup.

To protect the compressor, power is supplied from the 380-415 VAC input to the unit to preheat the compressor.

y Check the following before starting a test run:

y That all pipes are connected securely without leaks.

y That the valve is open.

If the compressor is operated with the valve closed, the outdoor unit will become overpressurized, which may

damage the compressor or other components.

If there is a leak at a connection, air can be sucked in and the internal pressure further increases, which may

cause a burst or injury. y

‘s Manual.

Annual maintenance

For an air conditioning system that is operated on a regular basis, cleaning and maintenance of the indoor / outdoor units are strongly recommended. As a general rule, if an indoor unit is operated for about 8 hours daily, the indoor / outdoor units will need to be
person. Failure to clean the indoor / outdoor units regularly will result in poor performance, icing, water leaking and even compressor failure.

J806 J805 J804 J803 J802 J801 J800
J806 J805 J804 J803 J802 J801 J800

Handling existing pipe

When using the existing pipe, carefully check for the following: y y Scratches and dents y Water, oil, dirt, or dust in the pipe y Flare looseness and leakage from welds y Deterioration of copper pipe and heat insulator
Cautions for using existing pipe
y

y Blow nitrogen gas or use an appropriate means to keep the inside of the pipe clean. If discolored oil or much
residue is discharged, wash the pipe. y Check welds, if any, on the pipe for gas leaks.

When the pipe corresponds to any of the following, do not use it. Install a new pipe instead. y The pipe has been opened (disconnected from indoor unit or outdoor unit) for a long period. y The pipe has been connected to an outdoor unit that does not use refrigerant R32, R410A. y The existing pipe must have a wall thickness equal to or larger than the following thicknesses.

Reference outside diameter (mm) Ø9.5 Ø15.9

Wall thickness (mm)
0.8 1.0

y

.

Existing piping
The following settings are required when using a pipe Ø19.1 mm as the existing piping at the gas pipe side.
Steps taken to support existing piping
1. Cut J805 (Jumper). 2. Set the circuit breaker to the ON position to turn on the power.
Jumper wires

11 Air conditioner operating conditions
For proper performance, operate the air conditioner under the following temperature conditions:

Cooling operation Heating operation

Dry bulb temp. Wet bulb temp.

­15°C to 46°C ­15°C to 15°C

If air conditioner is used outside of the above conditions, safety protection may work.

25-EN

26-EN

Refrigerant recovery
WARNING
y Don’t admit air into refrigerant during recovery. Otherwise, the pressure in the freezing cycle might increase abnormally. Serious injury could occur if it bursts.
[Recovering the refrigerant] y You need to recover the refrigerant when moving or repairing the indoor and/or outdoor units. You cannot do this while the air conditioner is running in cooling mode because a protective device will be tripped. Be sure to recover the refrigerant in test run mode.
y Use a refrigerant recovery device when the amount of refrigerant to be recovered exceeds the initial amount of 2.4 kg.
Instructions (Recovery to the Air Conditioner)
1. Power on the air conditioner. 2. To set the air conditioner to test run mode, hold down the Temporary button for more than 10 seconds.
Then, you will hear a “Pi” sound, and the light (green), light (green) and light (orange) lamps will blink quickly to indicate that the air conditioner has gone into a test run mode. 3. Wait for one minute to elapse, and then close the valve of liquid side. 4. It is recommended to attach a pressure gauge at the service port so that you can determine when refrigerant recovery has been completed. 5. Upon completion, close the valve of gas side. 6. Stop the air conditioner. 7. Power off the air conditioner. y Complete Steps 2 to 6
unit to stop. y If the recovery operation has been interrupted by the protective device, turn off the air conditioner. In this
case, use a refrigerant recovery device.

Troubleshooting

You can perform fault diagnosis of the outdoor unit with the LEDs on the P.C. board of the outdoor unit in addition to using the check codes displayed on the wired remote controller of the indoor unit. Use the LEDs and check codes for various checks. Details of the check codes displayed on the wired remote controller of the indoor unit are described in the Installation Manual of the indoor unit.
LED displays and check codes

No.

Error

1 Normal 2 Discharge temperature sensor (TD) error 3 Heat exchanger temperature sensor (TE) error 4 Heat exchanger temperature senser (TL) error 5 Outside air temperature sensor (TO) error 6 Suction temperature sensor (TS) error 7 Heat sink temperature sensor (TH) error 8 Mis-mounting of temperature sensor (TE, TS) 9 EEPROM error 10 Compressor breakdown 11 Compressor lock 12 Current detection circuit error 13 Thermostat for compressor activated 14 Model data not set 15 MCU-MCU commumication error 16 Discharge temperature error 17 High pressure SW error 18 Power supply voltage error 19 Heat sink overheating error 20 Gas leak detected 21 4-way valve reverse error 22 High pressure protective operation 23 DC outdoor Fan motor error (Upper side) 24 DC outdoor Fan motor error (Lower side) 25 Compressor drive device shot circuit 26 Position detection circuit error 27 28 Power supply error
: ON, : OFF,

Display D800 D801 D802 D803 D804 D805

  • The LEDs are located at the top right of the P.C. below.

Electric parts cover

D800 (Yellow) D801 (Yellow) D802 (Yellow) D803 (Yellow) D804 (Yellow) D805 (Green)

27-EN

­ 14 ­

Push on arrow head and slide.

Inspection window through which to check the LED displays

EN
28-EN

­ 15 ­

14 Appendix

[1] Existing piping

Work instructions
The existing R22 and R410A piping can be reused for our digital inverter R32 product installations.

WARNING

the existence of scratches or dents on

the existing pipes and

the reliability of

the pipe strength are conventionally referred to the

local site.

If the

conditions can be cleared, it is

possible to update existing R22 and R410A pipes

to those for R32 models.

Basic conditions needed to reuse existing pipes
Check and observe the presence of three conditions in the refrigerant piping works. 1. Dry (There is no moisture inside of the pipes.) 2. Clean (There is no dust inside of the pipes.) 3. Tight (There are no refrigerant leaks.)

Restrictions for use of existing pipes
In the following cases, the existing pipes should not be reused as they are. Clean the existing pipes or exchange them with new pipes. 1. When a scratch or dent is heavy, be sure to use
new pipes for the refrigerant piping works. 2. When the existing pipe thickness is thinner than the

use new pipes for the refrigerant piping works. y The operating pressure of R32 is high. If there is
a scratch or dent on the pipe or a thinner pipe is used, the pressure strength may be inadequate, which may cause the pipe to break in the worst case. * Pipe diameter and thickness (mm)

Pipe outer diameter Ø6.4 Ø9.5 Ø12.7 Ø15.9 Ø19.0

R32/R410A

Thickness

0.8 0.8 0.8 1.0 1.0

R22

y In case the pipe diameter is Ø12.7 mm or less and the thickness is less than 0.7 mm, be sure to use new pipes for the refrigerant piping works.
3. When the outdoor unit was left with the pipes disconnected, or the gas leaked from the pipes and

y There is the possibility of rain water or air, including moisture, entering the pipe.

4. When refrigerant cannot be recovered using a refrigerant recovery unit. y There is the possibility that a large quantity of dirty oil or moisture remains inside the pipes.
5. When a commercially available dryer is attached to the existing pipes. y There is the possibility that copper green rust has been generated.
6. When the existing air conditioner is removed after refrigerant has been recovered. Check if the oil is judged to be clearly different from normal oil. y The refrigerator oil is copper rust green in color: There is the possibility that moisture has mixed with the oil and rust has been generated inside the pipe. y There is discolored oil, a large quantity of residue, or a bad smell. y A large quantity of shiny metal dust or other wear residue can be seen in the refrigerant oil.
7. When the air conditioner has a history of the compressor failing and being replaced. y When discolored oil, a large quantity of residue, shiny metal dust, or other wear residue or mixture of foreign matter is observed, trouble will occur.
8. When temporary installation and removal of the air conditioner are repeated such as when leased etc.
9. If the type of refrigerator oil of the existing air conditioner is other than the following oil (Mineral oil), Suniso, Freol-S, MS (Synthetic oil), alkyl benzene (HAB, Barrel-freeze), ester series, PVE only of ether series. y The winding-insulation of the compressor may deteriorate.
NOTE
The above descriptions are results have been
our air conditioners, but do not guarantee the use of the existing pipes of air conditioners that have adopted R32 in other companies.

Branching pipe for simultaneous operation system
In the concurrent twin system, when TOSHIBA has

reused. Branching pipe model name: RBC-TWP30E2, RBC-TWP50E2, RBC-TRP100E On the existing air conditioner for simultaneous operation system (twin, triple system), there are cases

compressive strength. In such case, please change the piping to a branch pipe for R32/R410A.

Curing of pipes
When removing and opening the indoor or outdoor unit for a long time, cure the pipes as follows: y Otherwise rust may be generated when moisture or
foreign matter due to condensation enters the pipes. y The rust cannot be removed by cleaning, and new
pipes are necessary.

Placement location
Outdoors
Indoors

Term

Curing manner

1 month or more Less than 1 month
Every time

Pinching Pinching or taping

29-EN

30-EN

Are there scratches or dents on the existing pipes?
NO
Is it possible to operate the existing air conditioner?
YES
y After the existing air conditioner is operated in cooling mode for approx. 30 minutes or longer, * recover the refrigerant.
y Refer to “12 Refrigerant recovery” y For cleaning the pipes and recovering oil

  • Refrigerant recovery: Pump down method

YES NO

Existing pipes: Cannot be used. y Use new pipes.

Nitrogen gas pressure 0.5 MPa

y Remove the existing air conditioner from the piping
to remove any remains inside of the pipe. Note: In case of twin and triple pipes, also be sure to

Was largely discolored oil or a large quantity of remains discharged? (When the oil deteriorates,
the color of the oil changes to a muddy or black color.) NO
Connect the indoor / outdoor units to the existing pipe. y
the existing pipe.) y
R32.
In case that the gas pipe Ø19 mm is used for the outdoor unit of GM110 (4 HP) or higher : (Our R32 model 4 to 6 HP gas pipe size is Ø15.9 mm)
6HHSDJH³([LVWLQJSLSLQJ´
y (Airtight test), Vacuum dry, Refrigerant charge, Gas leak check
Test run

(If there is discharge of remains, it is judged that a large quantity of remains are present.)

YES

Clean the pipes or use new pipes.

Piping necessary to change the

nut / machining

size due to pipe compression

  1. Flare nut width: H

Copper pipe outer Ø6.4 Ø9.5 diameter

For R32, R410A

17

22

H

For R22

Same as above

Ø12.7 26 24

Ø15.9 29 27

(mm)
Ø19.0
36 Same
as above

  1. Flare machining size: A

Copper

pipe outer Ø6.4 Ø9.5 Ø12.7 Ø15.9

A

diameter

For R32, R410A

9.1 13.2 16.6

19.7

For R22 9.0 13.0 16.2 19.4

Becomes a little larger for R32/R410A

(mm) Ø19.0
24.0 23.3

[2] Minimum

area : Amin (m²)

Total refrigerant quantity*

Floor standing Wall mounted

unit

unit

Ceiling mounted
unit

h0 M (kg)

2.400

2.435

2.470

2.505

2.540

2.575

2.610

2.645

2.680

2.715

6HP

2.750

2.785

2.820

2.855

2.890

2.925

2.960

2.995

3.030

3.065

Max. 3.100

0.6
49.424 50.876 52.349 53.843 55.358 56.894 58.451 60.030 61.629 63.249 64.890 66.552 68.236 69.940 71.665 73.412 75.179 76.968 78.777 80.607 82.459

1.8
Amin(m²) 5.492 5.653 5.817 5.983 6.151 6.322 6.495 6.670 6.848 7.028 7.210 7.395 7.582 7.771 7.963 8.157 8.353 8.552 8.753 8.956 9.162

2.2
3.676 3.784 3.894 4.005 4.118 4.232 4.348 4.465 4.584 4.704 4.827 4.950 5.075 5.202 5.330 5.460 5.592 5.725 5.859 5.996 6.133

  • Total refrigerant quantity: Refrigerant quantity precharged at factory + Additional refrigerant quantity charged during installation

EN

31-EN

­ 16 ­

32-EN

Amin (m²) 90 80 70
60

Floor-standing unit

­ 17 ­
15

Model
RAV-GM1601AT8P-E RAV-GM1601AT8JP-E

Sound power level (dBA)

Cooling

Heating

70

72

70

72

Product information of ecodesign requirements, (Regulation (EU) 2016/2281) http://ecodesign.toshiba-airconditioning.eu/en

Weight (kg)
94 94

50

40

30

20

10

Wall-mounted unit

Ceiling-mounted unit

0

2.3

2.4

2.5

2.6

2.7

2.8

2.9

3.0

3.1

3.2

M (kg)

33-EN

34-EN

Declaration of conformity

Manufacturer:

Toshiba Carrier (Thailand) Co., Ltd. 144 / 9 Moo 5, Bangkadi Industrial Park, Tivanon Road, Tambol Bangkadi, Amphur Muang, Pathumthani 12000, Thailand

TCF holder:

TOSHIBA CARRIER EUROPE S.A.S Route de Thil 01120 Montluel FRANCE

Hereby declares that the machinery described below:

Generic Denomination: Air Conditioner

Model / type:

RAV-GM1601AT8P-E, RAV-GM1601AT8JP-E

Commercial name: Digital Inverter Series Air Conditioner

Complies with the provisions of the Machinery Directive (Directive 2006/42/EC) and the regulations transposing into national law

NOTE manufacturer’s consent.

To Fix the Fluorinated Greenhouse Gases Label

Fill in the label as follows:

Do not vent gases into the atmosphere.

Contains

greenhouse gases

Chemical Name of Gas

R32

Global Warming Potential (GWP) of Gas

675

CAUTION
1. Stick the enclosed refrigerant label adjacent to the service ports for charging or recovering location and where possible adjacent to existing nameplates or product information label.
2. Clearly write the charged refrigerant quantity on the refrigerant label using indelible ink. Then, place the included transparent protective sheet over the label to prevent the writing from rubbing off.
3.
greenhouse gas is never vented to the atmosphere during installation, service or disposal. When any
gas is detected, the leak shall be stopped and repaired as soon as possible. 4. access and service this product. 5. in this product, such as when moving the product or recharging the gas, shall comply under (EU)
greenhouse gases and any relevant local legislation. 6. Periodical inspections for refrigerant leaks may be required depending on European or local legislation. 7. Contact dealers, installers, etc., for any questions.

Pre-charged refrigerant in the nameplate
Additional charge on installation site [kg] GWP × kg 1000

35-EN

­ 18 ­

36-EN

Warnings on refrigerant leakage
Check of concentration limit
7KHURRPLQZKLFKWKHDLUFRQGLWLRQHULVWREHLQVWDOOHGUHTXLUHVDGHVLJQWKDWLQWKHHYHQWRIUHIULJHUDQW JDVOHDNLQJRXWLWVFRQFHQWUDWLRQZLOOQRWH[FHHGDVHWOLPLW The refrigerant R32 which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws to be imposed which protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its concentration should rise excessively. Suffocation from leakage of R32 is almost non-existent. If a conditioner system is to be installed in a small room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its concentration does not reach the limit (and in the event of an emergency, measures can be made before injury can occur). In a room where the concentration may exceed the limit, create an opening with adjacent rooms, or install mechanical ventilation combined with a gas leak detection device. The concentration is as given below.
Total amount of refrigerant (kg) &RQFHQWUDWLRQOLPLWNJP³)
Min. volume of the indoor unit installed room (m³)
Refrigerant Concentration Limit shall be in accordance with local regulations.

­ 19 ­

37-EN

38-EN

144 / 9 Moo 5, Bangkadi Industrial Park, Tivanon Road, Tambol Bangkadi, Amphur Muang, Pathumthani 12000, Thailand

1128501002A

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals