Product Information
Specifications
- Capacity: 60,000 Watts
- Battery Capacity: 60.1KWH
- Input Voltage: 480 Volts
- Phase: Three Phase
- Frequency: 60 HZ
- Efficiency: 95% at full load
- Harmonic Distortion: < 5% THD at Full Load
- Overload Capacity: 125% for 10 minutes, 150% for 1 minute
- Operating Temperature Range: 0C to 40C
- Cooling: Forced Air – Internal Fans
- Compliance and Certifications:
- Inspection: Onsite Special Certification – Per Client Request
- Batteries UL1973, UL9540, UL9540a
- Inverters: UL1741
- Communication Port: CAN2.0/RS485
Product Usage Instructions
Installation Requirements
- Connections: Provide proper electrical connections per manufacturer’s specifications.
- Clearances: Maintain a minimum 3′ clearance in front of all electrical panels and equipment access panels. Maintain a minimum 2′ clearance in front of all ventilation grates.
Testing and Commissioning
- Factory Testing: The system undergoes thorough factory testing to ensure compliance with performance standards, including relevant test results, certificates, and inspection reports.
Contact Information
- Manufacturer: Medicanix Inc – DBA Medi-Products
- Website: www.mediproducts.net
- Phone: 203-348-2886
Frequently Asked Questions (FAQ)
What is the warranty on the output fuse?
The output fuse has an 80 Amp rating and comes with a 10-year warranty.
What is the battery type used in the system?
The battery type used is Lithium Iron Phosphate.
What is the operating temperature range of the system?
The operating temperature range is from 0C to 40C.
UNIT WIRING
ELECTRICAL INFORMATION
Model Numbers| Wattage| Line Power| Load Power|
Conductors| Battery Type
---|---|---|---|---|---
MHW60KW60KWH-480V-3PH| 60,000| 480 Volts 100 Amps| 480 Volts 80 Amps| 3 Legs 1
Neutral 1 Ground| Lithium Iron Phosphate
SYSTEM SIZE
Model Numbers| Waveform| Width (A)| Depth (B)| Height
(C)| Weight (lbs)| Cabinets
---|---|---|---|---|---|---
MHW60KW60KWH-480V-3PH| Pure| 35.50”| 29.00”| 82.00”| 2270| 1
- Operating Temp: 40F – 110F
- Noise: 40 dBA
- Certification: Inverter: UL 1741
- Battery: UL1973, UL9540, UL9540a
- Notes: Unit Onsite Special Certification Inspection – per customer request.
- Output Fuse: 80 Amp
- Warranty: 10 Year Warranty
- Battery Monitor Communication Port: CAN2.0/RS485
UNIT DIMENSIONS
Technical Specifications
- Capacity: 60,000 Watts
- Battery Capacity: 60.1KWH
- Input Voltage: 480
- Phase: Three Phase
- Frequency: 60 HZ
- Efficiency: 95% at full load
- Harmonic Distortion: < 5% THD at Full Load
- Overload Capacity: 125% for 10 minutes 150% for 1 minute
- Operating Temperature Range: 0C to 40C
- Cooling: Forced Air – Internal Fans
Compliance and Certifications:
- Inspection: Onsite Special Certification – Per Client Request
- Batteries: UL1973, UL9540, UL9540a
- Inverters: UL1741
Comunication:
- Port: CAN2.0/RS485
Electrical:
- Line: 480 Volts 100 Amps
- Load: 480 Volts 80 Amps
- Conductors: 3 Legs 1 Neutral 1 Ground
- Battery Type Lithium Iron Phosphate
Installation Requirements:
- Connections: Provide proper electrical connections per manufacturer’s specifications
- Clearances: Maintain minimum 3′ clearance in front of all electrical panels and equipment access panels. Maintain minimum 2″ clearance in front of all ventilation grates
Testing and Commissioning:
- Factory Testing: System undergoes thorough factory testing to ensure compliance with performance standards, including relevant test results, certificates and inspection reports.
Contact Information: