jetec JDA-500 Smart Gas Detector Transmitter built-in LCD and explosion proof Instruction Manual
- June 3, 2024
- JETEC
Table of Contents
SMART Gas Detector/Transmitter(4~20mA)
with built-in LCD & explosion proof
JDA-500
Introduction
JDA-500 detects various combustible & toxic gases leaked from industrial areas for gas producers, gas users, gas reservoirs, gas by-producers, and so on, in order to prevent any accidents in advance. JDA-500 converts digital signal into the 4-20mA standard current output signal which can be transmitted to various devices such as PLC, DDC, or recorder to build comprehensive gas monitoring system. Also, JDA-500 provides RS-485 communication signal and alarm relay contact. DC 4-20mA standard output signal realizes max 2500m long distance output signal transmission and RS-485 communication signal realizes max 1000m long distance signal transmission.
Features
-
Digital process
Digital processr based on built-in micro processor realizes various artificial intelligent functions which result in convenient gas monitoring environment. -
Self diagnosis
Digital process automatically diagnoses the sensor signal and sends 2mA error signal output on the malfunction in the sensor. -
Auto-calibration without opening cover
You don’t need to open front cover for calibration. You only have to touch cover window using magnetic bar. It is quite useful for the corrective work in the explosive area. -
LCD display with back light
LCD offers real-time display of gas density and back light offers easy reading even in dark area. -
User programming
User programming calibration density and detection rage offers user’s own operating functions. -
Built-in HD(high dissolution) A/D converter for accurate output signal.
-
Multi signal output
Various output signals – DC 4-20mA, 2 step-relay contact, & RS-485(option) — provides best networking with all kinds of devices & equipments. -
4-20mA transmitter
4-20mA output enables stable and long distance (maximum 2.5km) signal transmission. -
RS-485
RS-485 enables stables stable and long distance (maximum 1.2km) signal communication. -
Alarm output
SPST 2 step relay contacts (AL1/AL2).
Specification
Detection principle | Catalytic , Electro-Chemical, TCD or NDIR |
---|---|
Built – in display | 2-ines x 8-characters LCD with back light |
Gas sampling | Diffusion type |
Target gas | Please refer to the target gas list. |
Measurement range | 0~ 100 %LEL, 0~10,000ppm. 0~100% VOL |
Response time | Within 30 sec., 90% / full scale |
Accuracy | ≤±2% / full scale |
Sensor displacement | Zero – ≤±2%LEL/ 6 month, span -≤±2%LEL / 6 month |
Input power | DC 20 ~ 30V |
Output power | 4 ~ 20mA/Full Scale – 2.5km transmission |
Operating temp.& humidity | -30’C~ 60°C, 5 ~ 95% RH (Non-condensing) |
Signal cable | CVVS & CVVSB -1.5 sq x 3 wire – shield type |
Wire conduit | 1/2″ or 3/4″ PF, NPT |
Installation type | Wall or Pipe Mounting |
Exterior material | Cast Aluminum Alloy |
Explosion-proof | Ex dllC TS |
Output | 2 step- relay contact (ALARM-1/ALARM-2) |
Communication output | RS-485 communication output(option) |
Sensor operation period | 5 years (in air) |
Sensor warranty period | 1 year |
Parts & Description
1. Amp & Power Board
2 . Transmitter Board
3. Parts’ Name and Description
1. DETECTOR HOSING BODY | 2. DETECTOR HOSING COVER |
---|---|
3. SENSOR HOUSING | 4. M4 HEADLESS BOLT |
5. CALIBRATION NIPPLE INSERT | 6. SENSOR CAP |
7. GAS SENSOR | 8. M4 HEADLESS BOLT |
9. MOUNT HOLES | 10, CONDUIT CONNECTION |
11. CALIBRATION KEY | 12. MODE KEY |
13. UP KEY | 14. DOWN KEY |
15. ENT KEY | 16. M3 HEADLESS BOLT |
Sensor Calibration
Please carry out calibration periodically in order to keep optimum sensor
condition at least once a year.
1. Zero Calibration
Please follow below procedure:
- Please touch CAL key through the window of cover using magnetic bar. And then, LCD shows below:
- Please touch ENT key through the window using magnetic bar. And then, LCD shows below:
- Please infuse standard gas such as clean air or nitrogen gas for one minute.
- When the measured value becomes stable, please touch ENT key using magnetic bar.
- When the zero calibration finishes, [OK] will be shown on LCD:
▲Caution: Zero calibration should be processed with clean air or 99%
nitrogen gas. (For O2 gas, you must use nitrogen gas 99.8% or more.)
2. Span Calibration
Please follow below procedure:
- Please fix the calibration nipple on the sensor cap.
- Please touch CAL key through the window of cover using magnetic bar.
- Please touch MODE key through the window using magnetic bar to move into CAL menu. And then, LCD shows below:
- Please touch ENT key though the widow using magnetic bar. And then, LCD shows below:
- Please touch UP & DOWN key through the window to input the calibration gas density. And then, please touch ENT key to confirm it. And then, LCD shows below:
- Please infuse the standard gas for one minute until the density value becomes stable. And then, please touch ENT key.
- Please stop calibration gas and remove the calibration nipple. And then, LCD shows below as gas density value goes down.
- When the density value goes down 10%LEL or below, measuring mode starts automatically.
▲Caution: The standard gas should be within the designated density range.
If you use it out of the designated density range, the calibration is not
possible and the sensor may be damaged or lifetime may be reduced extremely. (
Default: gas density = 50%LEL & measuring range 0 ~ 100%LEL)
▲ Caution: Please start calibration after 4 minutes from power on after
sensor replacement.
Sensor Replacement
Please follow below procedure:
- Please turn off the power.
- Please open the front cover.
- Please dissemble the display board.
- Please disassemble the three line connector between sensor and sensor board.
- Please pull out the headless boltto disassemble the sensor cap.
- Please assemble new sensor cap and tighten the headless bolt.
- Please assemble three line connector between sensor and sensor board.
- Pease push and insert the guide bar into the bushing of power board accurately to fix the display board.
- Please assemble the front cover.
- Please turn on the power.
- Please proceed with sensor calibration.
▲ Caution
Before replacing sensor, please make sure that power should be off.
Please make sure whether the direction of connector’s socket is correct.
****Please fully tighten the sensor cap and front cover to secure water
proof.
Wiring
1. Terminals
2 . Cable Specification
- Cable Type: Shield Cable
- Transmission distance and required cable specification
Transmission distance | 0~ 500m | 501 ~ 1,500m | Over 1,500m |
---|---|---|---|
Required cable specification | 0.75 sq | 1.25sq | 2.0sq |
Installation
1. Front view
2 . Side view
3. Cable conduit and installation position
- Cable Conduit: 1/2’, 3/4” PF/NPT.
- In open area, please install JDA-500 as close as possible to the potential gas leakage place suchas gasvalve and pipe connection.
- I n closed area,
- Light gas (specific gravity < 1): Please install JDA-500 20 ~ 30cm from ceiling.
- Heavy gas (specific gravity > 1): Please install JDA-500 20 ~ 30cm from the floor.
4 .Cautions
- Please avoid any potential electrical troubles such as rain drops.
- Please avoid any vibration or physical impact which can affect the output signal value.
- Please avoid high temperature or humidity.
- Please avoid any electrical noise such as motor, pump, or high voltage power line.
- Please choose the place where you can do repair & maintenance job easily. If itis not available, we recommend suction type detectors.
Setting Menu
|
---|---
< 1> Measuring mode
Please push MODE key for 2 seconds to start setting mode.
< 2> HI-SCALE
Set 4 ~ 20mA output signal for full scale.
(ex) If you set SCALE to 100, 4mA output signal displays ‘0’ and 20mA output
signal displays ‘100’.
< 3 > ALARM-1
According to ‘AL TYPE’, alarm #1 on.
< 4 > ALARM-2
According to ‘ A L TYPE’, alarm #2 on.
< 5 > AL-TYPE(ALARM-TYPE)
It has four(4) alarm types: L&L, L&H, H&L, and H&H
You can use two alarm relay —relay 1 & relay 2.
(ex) If you set ‘ AL TYPE’ to H&L:
⇒ Relay 1 set high: when the measured value is higher than set value, alarm
on.
⇒ Relay 2 set low: when the measured value is lower than set value, alarm on.
< 6> AL-RESET(ALARM RESET)
Select release method on alarm relay contact or buzzer.
Select’AUTO’ ⇔ ‘MANUAL’
Sensor Calibration Menu
< 1> Calibration mode
Please touch CAL key on the window using magnetic bar to start calibration
mode.
< 2> Zero calibration
At ‘CAL [ZERO], please touch ENT key on the window using magnetic bar. When
‘ZERO GAS <0.0 %LEL>’ shows on LCD, please infuse clean air or 100% nitrogen
gas until the measured value becomes stable. And then, please touch ENT key on
the window to confirm it. If the zero calibration is successful, ‘ZERO GAS
[OK] will be displayed. If calibration is not successful, “ZERO GAS [FAIL]’
will be displayed during 2 seconds.
< 3> SPAN CALIBRATION
(ex) Target gas: H2
Standard gas: H2(50 %LEL)+Air Balance
- At the CAL[SPAN], please touch the ENT key on the window using magnetic bar.
- Please input the density value of standard H2 gas, 50%LEL, using UP and DOWN key on the window using magnetic bar. And then, please touch ENT key to confirm it. LCD shows below: (2) Please infuse the standard H2 gas until the displayed value becomes stable as LCD shows below picture. And please touch ENT key to confirm it.
- Ifthe SPAN calibration is successful, LCD shows below:
- Measuring mode will start automatically when the density value goes down under 10%LEL.
TEL:+886-4-23729418
sales@jetec.com.tw
www.jetec.com.tw
Documents / Resources
|
jetec JDA-500 Smart Gas Detector Transmitter built-in LCD and explosion
proof
[pdf] Instruction Manual
JDA-500 Smart Gas Detector Transmitter built-in LCD and explosion proof,
JDA-500, Smart Gas Detector Transmitter built-in LCD and explosion proof,
Detector Transmitter built-in LCD and explosion proof, built-in LCD and
explosion proof, LCD and explosion proof, explosion proof, proof
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>