General Aire 4400A Fan Assist Evaporative Humidifier Instruction Manual

June 1, 2024
General Aire

Model 4400A

Installation Manual

Fan-Assist Evaporative Humidifier

Automatic


Please Read And Save These Instructions


USA Model                      Canadian Model
4400A (GFI #5961)                    GF-4400A

Patent Pending


Supply Plenum Installation Location: The model 4400A fan-assist evaporative humidifier must be installed on the supply plenum (ONLY) of a forced air handling system. Select a location for the humidifier that allows for service and maintenance.

  1. Return
  2. Supply
  3. Vertical Installation
  4. Drain Line

  CAUTION!
This symbol and the word “CAUTION” indicates:
IMPORTANT INSTRUCTIONS!

  WARNING!
This symbol and the word “WARNING” indicates:
IMPORTANT INSTRUCTIONS!


Failure to heed CAUTION! or WARNING! can result in serious injury or death.


Inside The Box

  • GA35 Vapor Pad® (GFI #7902)
  • Solenoid Valve Assembly
  • GFX4 Digital Automatic Humidistat (GFI #7170)
  • Installation Hardware
  • Push-to-Connect Valve for 1/2 copper or PEX
  • 1/4″ Diameter plastic supply tubing for cold water applications
  • Electrical wire and wire nuts
  • (6) #8 x 1/2” Long self-piercing sheet metal screws

CAUTION! 24V Transformer is Factory Installed. Do NOT Connect Any Power Supply Source to the External Yellow & Red Wires.


WARNING: DISCONNECT ELECTRICAL POWER BEFORE BEGINNING INSTALLATION.

Off


IMPORTANT: To ensure your safety and the longevity of your unit, we recommend:

  • Contacting a licensed contractor to perform maintenance or repairs.

  • Changing your Vapor Pad® at the start of each heating season.

WARNING: Do not install where ambient temperatures fall below 32°F / 0°C or where plenum temperatures exceed 200°F / 93°C. For maximum evaporative capacity, install this humidifier on the warm air supply plenum.


Form No. 4400-18 REV B

General Aire logo


INSTALLATION – SUPPLY (ONLY)

1 Prepare Duct
  1. Cut a rectangular hole using the manufacturer-supplied mounting template.

For serviceability, please allow an obstruction-free zone of at least 4″ (101.6mm) on the right side and bottom of the humidifier.

2 Affix Chassis
  1. Install the humidifier chassis, making sure the drain spout is pointing downward, as shown.
  2. Level the chassis and install using the six mounting screws included.
3 Install the Push-to-Connect Valve

1. Select desired valve location.

2. Remove 0.6in (15mm) of pipe to account for valve width (Fig. A).
Make sure both pipe ends are square, deburred and clean.

Fig. A

3. Mark both pipes at the insertion depth, 0.95″ (24mm) (Fig. B).

Fig. B

4. Firmly insert both pipes into fitting until at full depth.
Verify each pipe is fully inserted. The depth mark will be within 0.005″ (0.13mm) of the release collar (Fig. C).

Fig. C

4 Configure Water Supply Tubing
  1. Utilizing copper tubing requires a brass compression nut and brass sleeve.
  2. Utilizing plastic tubing requires a plastic sleeve on the outside with a brass compression nut.

HOT WATER – COPPER TUBING 1/4″

COLD WATER – PLASTIC TUBING 1/4″

  1. Brass Sleeve P-102
  2. Plastic Sleeve P-190
  3. Compression Nut P-101
5 Connect Water Supply
  1. Connect 1/4″ water supply tube to brass inlet of solenoid.
  2. Turn on water supply and check for leaks.

CAUTION: Do not use plastic tubing in contact with any hot plenum surface or duct.

  1. Solenoid Assy 4400-05
  2. 1/4″ Water Supply Tube
  3. Compression Nut P-101
  4. Compression Sleeve P-190
6 Connect Drain Hose
  1. Connect the 1/2″ ID drain hose to the spout on the humidifier cabinet using the provided flat spring clip.

  2. Run the drain hose to a suitable drain such as floor drain, laundry sink or to a condensate pump (sold separately). Be sure the hose has continuous slope and is not kinked at any point.

  3. 1/2″ Spout

  4. Flat Spring Clip

  5. 1/2″ Drain Hose


CONNECTING THE GFX4 TO THE 4400A

7 Wiring the GFX4 Without Relay or Air Proving Switch

Option 1: Interlocked with call for heat and with use of field-supplied jumper between AC-C and HUM1

General Aire 4400A Fan Assist Evaporative Humidifier -
c2

  1. GeneralAire® GFX4 Humidistat

  2. Thermostat

  3. Furnace

  4. 3-wire Cable
    Field Supplied

  5. JUMPER

  6. 2-wire Cable
    Field Supplied

  7. Wire Splices

  8. Blue Wires

  9. GeneralAire® GF-4400A Fan-Assist Humidifier

  10. Yellow Wires

  11. Cap each wire separately.
    Do not touch together.

  12. Red Wires

  13. 115v Power Supply Cord

Option 2: Blower activation on humidity call and with use of field- supplied jumper between AC-L and HUM1

General Aire 4400A Fan Assist Evaporative Humidifier -
c3

  1. GeneralAire® GFX4 Humidistat

  2. Thermostat

  3. Furnace

  4. 3-wire Cable
    Field Supplied

  5. JUMPER

  6. 2-wire Cable
    Field Supplied

  7. Wire Splices

  8. Blue Wires

  9. GeneralAire® GF-4400A Fan-Assist Humidifier

  10. Yellow Wires

  11. Cap each wire separately.
    Do not touch together.

  12. Red Wires

  13. 115v Power Supply Cord


CONNECTING THE GFX4 TO THE 4400A & TESTING THE UNIT

7 Utilizing Traditional Wiring to Connect the GFX4

Option 3: Interlocked with call for heat and with use of field-supplied 24V isolation relay

General Aire 4400A Fan Assist Evaporative Humidifier -
c4

  1. GeneralAire® GFX4 Humidistat

  2. 2-wire Cable
    Field Supplied

  3. Isolation Relay, 24vac coil
    Field Supplied

  4. Furnace

  5. Thermostat

  6. 4-wire Cable
    Field Supplied

  7. Yellow Wires

  8. GeneralAire® GF-4400A Fan-Assist Humidifier

  9. Red Wires

  10. Wire Splices

  11. 115v Power Supply Cord

Option 4: Interlocked with blower and with use of field-supplied GA50 sensing relay or 12502 air pressure switch

General Aire 4400A Fan Assist Evaporative Humidifier -
c5

  1. GeneralAire® GFX4 Humidistat

  2. GA50 Current Sensing Relay
    Field Supplied

  3. MULTI SPEED BLOWER MOTOR

  4. COMMON LEAD

  5. 12502 Air Proving Switch
    Field Supplied

  6. 4-wire Cable
    Field Supplied

  7. Yellow Wires

  8. GeneralAire® GF-4400A Fan-Assist Humidifier

  9. Red Wires

  10. Wire Splices

  11. 115v Power Supply Cord

8 Test the Operation of the Unit
  1. Turn on the water supply.
  2. Turn the humidistat RH% to 75%.
  3. Turn the furnace on; heat cycle. Make sure the furnace blower motor is on.
  4. Once the solenoid valve is energized the valve should open.
  5. Check flow of water through distributor trough and Vapor Pad® (3.5 GPH of water at a line water pressure of 60PSI).
  6. Check fan operation (ON).
  7. Reduce RH% to desired setting after test completion.

General Aire logo


4400A FAN-ASSIST EVAPORATIVE PARTS ASSEMBLY

General Aire 4400A Fan Assist Evaporative Humidifier -
d1

  1. 4400-05
    SOLENOID ASSEMBLY

  2. 4200-21
    SS DISTRIBUTION TUBE ASSEMBLY

  3. 4400-22
    PIVOT PIN

  4. GA35
    VAPOR PAD

  5. 4200-15
    DISTRIBUTION TROUGH

  6. 4400-09
    MOTOR MOUNT

  7. 4400-08
    AIR FLOW ADAPTER

  8. 4400-06
    CROSSFLOW FAN

  9. 4400-07
    FAN MOTOR COVER

  10. 4400-13
    COVER

  11. 1137-61
    RELAY ASSEMBLY

  12. 4400-12
    FAN MOTOR SHEILD

  13. 4400-11
    WIRE HARNESS

  14. 4200-14
    DRAIN PAN

  15. 4400-22
    PIVOT PIN

  16. 4200-10
    SPOUT

  17. 4400-01
    CHASSIS


MAINTENANCE

Replace your GA35 Vapor Pad® at the beginning of each heating season.

  • Remove Cover

  • Release & Open Door

  • Remove Vapor Pad Assembly

  • Remove & Discard Used Vapor Pad

  • Remove Scale Buildup On Frame, If Present

  • Reinsert Vapor Pad Assembly

  • Close Door

  • Reinstall Cover

WARRANTY

Your new humidifier carries a 5-year limited warranty. For our complete warranty policy visit www.generalfilters.com.


CONTACT

General Filters, Inc. 43800 Grand River Avenue Novi, Michigan 48375
Toll Free: 866-476-5101 www.generalaire.com

Canadian General Filters, Ltd. 400 Midwest Rd Toronto, ON M1P3A9
Toll Free: 888-216-9184 www.generalaireiaq.ca