RITTAL RIPM-04-00-0523 19-Inch Floor Cabinet Enclosure Instruction Manual

June 1, 2024
RITTAL

RITTAL RIPM-04-00-0523 19-Inch Floor Cabinet Enclosure

Product Information

Specifications

  • Enclosure Protection Degree: IP66
  • Material: Stainless Steel (SS304 or SS316 L)
  • Dimensions: Various sizes available from 600W x 1600H x 400D mm to 1000W x 2200H x 1000D mm
  • Compliance: ISO 9001:2015, EN ISO IEC 80079-34:2020, ATEX Directive 2014/34/EU

Product Usage Instructions

Use
The empty enclosures are designed for the installation of Ex components and terminals.

Installation

  • For explosion-protected enclosure variants, follow EN 60079-14 for configuration and selection, and EN 60079-17 for testing and maintenance.
  • Choose an installation location that prevents damage from industrial trucks. Enclosures on support frameworks must be secured against tipping.

Cable and Wire Entries
Use metal cable and wire entries with sealing plugs. Ensure all entries have an EU prototype test certificate. Install entries with metal counter nuts to maintain stability.

Frequently Asked Questions (FAQ)

  • Q: What is the maximum protection degree of the enclosures?
    A: The enclosures have an IP66 protection rating according to EN 60529, protecting contact, foreign bodies, and water.

  • Q: Can special dimensions be requested for the enclosures?
    A: Yes, special dimensions between 600W x 1600H x 400D mm to 1000W x 2200H x 1000D mm can be manufactured upon request with SS304 or SS316 L material.

  • Q: What standards do the enclosures comply with?
    A: The enclosures conform to ISO 9001:2015, EN ISO IEC 80079-34:2020, and ATEX Directive 2014/34/EU.

Use

The empty enclosures/terminal enclosures/ Junction Box/Remote I/O Enclosure made of stainless steel are designed for the installation of Ex components and terminals.

Purpose of these instructions

  • When work is done in areas where there is a risk of explosion, the safety of persons and equipment depends on adherence to the relevant safety regulations. Consequently, the installation and maintenance personnel who work on such systems have a special responsibility. The prerequisite here is the exact knowledge of the applicable regulations and standards.
  • These instructions present a brief summary of the most important safety measures. It is intended as an enhancement to the appropriate regulations with which the responsible persons must comply.
  • The instructions and other objects may not remain in the enclosure during operation.

Safety information

  • The empty enclosures/terminal enclosure/ Remote I/O enclosures are designed for permanent installation in explosion-endangered areas of zones 1 and 2 in accordance with IEC 60079-10-1:2020 or in zones 21 and 22 in accordance with IEC 60079-10-2 :2015. The above-mentioned enclosures are not to be used in zones 0 and 20.
  • The enclosures may not be operated in conditions subject to dust accumulations ≥ 5 mm thickness in accordance with IEC 60079-10-2:2015.
  • Inappropriate or unauthorized use or failure to comply with the information contained in these instructions voids any warranty on our part.
  • Modifications or changes to the empty enclosure / terminal enclosure Remote I/O enclosures that impair explosion protection are not allowed.
  • The empty enclosure / terminal enclosure must be clean and undamaged when it is installed.

In particular, the following must be observed:

  • national safety regulations
  • national workplace health and safety regulations
  • national installation and set-up regulations
  • generally accepted engineering standards
  • the safety information contained in these operating instructions
  • the data and rated operating conditions on the nameplate and rating plate
  • the EU prototype testing certificate

Non-compliance with these instructions will invalidate the warranty!

Conformance to standards

  • The empty enclosures/terminal enclosures /Remote I/O enclosures conform to the requirements of IEC 60079-0 Ed 7.0: 2017 Explosive atmospheres- Part 0: Equipment – General requirements. IEC 60079-7 Ed 5.1: 2017 Explosive atmospheres – part 7: Equipment protection by increased safety “e”, IEC 60079 -31 Ed 3: 2022 Explosive atmospheres -Part 31: Equipment dust ignition protection by enclosure “t”.
  • IEC 60529 Ed 2.2: 2013 Degrees of protection provided by the enclosure.
  • The enclosures are state-of-the-art at the time of manufacturing and conform to ISO 9001:2015, EN ISO IEC 80079-34:2020 and as per ATEX Directive 2014/34/EU.

Technical data

Enclosure protection degree:
Protection category as per EN 60529: Contact, foreign body, and water protection IP66RITTAL-RIPM-04-00-0523-19-Inch-Floor-Cabinet-Enclosure-FIG-
\(1\)

Dimensions

SS large enclosures


Article number for enclosure in 2 mm thick

| Article number for enclosure in 1.5 mm

thick

| ****


Description

---|---|---
9792111| 9792131| EX – SS ENCL 600Wx1600Hx600D
9792112| 9792132| EX – SS ENCL 600Wx1800Hx400D
9792113| 9792133| EX – SS ENCL 600Wx1800Hx600D
9792115| 9792135| EX – SS ENCL 800Wx1800Hx600D
9792114| 9792134| EX – SS ENCL 600Wx2000Hx600D
9792116| 9792136| EX – SS ENCL 800Wx2000Hx600D
9792117| 9792137| EX – SS ENCL 800Wx2000Hx800D
9792118| 9792138| EX – SS ENCL 800Wx2200Hx600D
9792120| 9792140| EX – SS ENCL 1000Wx2200Hx1000D
9792148| 9792144| EX – SS ENCL 800Wx900Hx600D
9792119| Ex – SS Large Enclosure – Special dimensions can be manufactured between 600W x 1600 H x 400D mm to 1000W x 2200 H x 1000D mm In SS304 or SS316 L, with/without gland plates, and with/without gland holes.

Note : 9792119 is Generic article for special dimensions. The special request for quotation will be reviewed by technical department (Ex representative) and Product Management.

Service temperature
Permitted service temperature -50°C to +180°C. The permitted operational temperature range must be considered for internal components.

Attention:
Empty enclosures with component certificates require an examination certificate of a notified body for overall approval.

Installation

For the installation and operation of explosion-protected enclosure variants, the recognized rules of technology in accordance with EN 60079-14 “Configuring and selection”, and EN 60079-17 “Test and maintenance”, and the accompanying installation and operating instructions must be observed.

Installation location
The installation location for explosion-protected enclosure variants must be chosen to prevent any damage caused by industrial trucks or forklift trucks.
Explosion-protected enclosure variants installed on support frameworks must be protected from falling over.

Service temperature
To maintain the determined surface temperature, the environment temperature limit values may not be undershot or overshot (-50°C to +180°C) .
Any present external heat sources or solar radiation may cause additional heating of the enclosure. Appropriate measures should be considered during the installation

Cable and wire entries

  • Cable and wire entries as well as sealing plugs made of metal can be used. All cable and wire entries must have a separate EU prototype test certificate.
  • The maximum number of entries listed in the table for each side of the enclosure has been defined to avoid weakening of the side panels or degrading the stability of the enclosure.
  • All cable and wire entries must be installed using a metal counter nut.
  • The number of possible standard cable glands decreases if strain relief or cable guards are used.
  • Unused openings for cable and wire entries must be closed with metal plugs that have a separate EU prototype test certificate,
  • The cable and wire entries must be installed so that a self-loose ending is prevented, and the permanent sealing of the cable and wire entry locations can be guaranteed.
  • The distances between the cable entries should be chosen so that a torque wrench can be used to tighten the cable and wire entries and the box nuts.
  • The tightening torques must be observed for the installation of the cable and wire entries.

Maximum number of cable and wire entries

The maximum number of cable/wires entries on the Ex-enclosures isss as follows
THE INFORMATION CONTAINED IN THE OPERATING INSTRUCTIONS PROVIDED BY THE MANUFACTURERS OF CABLE AND WIRE ENTRIES MUST BE OBSERVED. RITTAL-
RIPM-04-00-0523-19-Inch-Floor-Cabinet-Enclosure-FIG-
\(6\) RITTAL-
RIPM-04-00-0523-19-Inch-Floor-Cabinet-Enclosure-FIG-
\(7\)

Enclosure attachment

RITTAL-RIPM-04-00-0523-19-Inch-Floor-Cabinet-Enclosure-FIG-
\(3\) RITTAL-
RIPM-04-00-0523-19-Inch-Floor-Cabinet-Enclosure-FIG-
\(4\) RITTAL-
RIPM-04-00-0523-19-Inch-Floor-Cabinet-Enclosure-FIG-
\(8\) RITTAL-
RIPM-04-00-0523-19-Inch-Floor-Cabinet-Enclosure-FIG-
\(9\)

Ex large Enclosure: Instruction Manual – Ex Large Enclosure

PE conductor / equipotential bonding conductor (PA) connection.

  • As a general rule, the outer protective conductor or an equipotential bonding conductor must be connected.
  • An internal and external connection point located at the empty enclosure is provided for this purpose. The connection must be performed in agreement with EN 60079-0, Section 15.
  • Connect the PE / equipotential bonding conductor as described on drawing NO. N131348 00 EX A3 sheet 3/5, using the stainless-steel screws, nuts, plain washers, and split washers that accompany the empty enclosure. Attach a standard cable lug with the appropriate cross-section and ring diameter to the PE / equipotential bonding conductor which is fed in from the outside. The cable lug you select should fulfill the requirements for ring cable lugs defined in the DIN 46234 standard or for spade-type cable lugs defined in the DIN 46235 standard.
  • The terminals for the protective earth and equipotential bonding conductor are designed to accept at least one conductor. The cross-sections must be selected as follows:
    Cross-sectional area of phase conductors, S mm2| Minimum cross-sectional area of the corresponding PE protective conductor Sp mm2
    ---|---
    S≤ 16 16 <S≤35

s >35 mm2

| S 16

0.5 S

The PE / equipotential bonding conductor terminal fittings are designed for a minimum cross-section of 4 mm².
When you are installing the outer conductor / equipotential bonding conductor, be sure that you route the conductor properly in a fixed position near the enclosure main body to ensure that the conductor will not rotate or become loose. Torque the screwed connection to 10 Nm to provide sufficient contact pressure using the split washer provided.
The SL / PA connection between the enclosure’s main body and the door must be achieved with a flexible connector marked in green/yellow. Select the cross- section to match the heaviest installed gauge outer conductor but not less than 4 mm² if the cross-section table above does not apply.
Select materials for the protective conductor terminal that are not likely to be susceptible to electrochemical corrosion. Appropriate measures must be taken to protect protective earth conductors against mechanical, electro- dynamic, and thermodynamic stress. Mechanical protective earth connections must be accessible for inspection and testing.

Note:

  • Earthing for (E1 & E2) top cover
  • Etarthing for (E1 & E2) bottom cover
  • Etarthing for (E1 & E2) rear cover
  • Earthing for E1 & E2, door
  • Earthing for (E1 & E2) side panel-LH&RH
  • Earthing for (E1 & E4) mounting plate
  • External earthing for (E3) side panel LH & RH

Commissioning

Before you apply power for the first time, you must check the following items:

  • the enclosure must be properly installed.
  • the enclosure must not be damaged; this applies in particular to the seals.
  • there must not be any foreign objects in the enclosure.
  • the wiring space must be clean.
  • mounting and device screws must be securely fastened.
  • cable and wire entries must be securely fastened.
  • all cables and wires must be installed in the lead-throughs as required for the protection category.
  • unused cable and wire entries must be closed with certified plugs.
  • unused holes must be sealed with certified plugs.
  • the outer protective earth connection must be properly installed near the enclosure.

Repair, maintenance, and servicing

Repair and maintenance work on the enclosures listed above may be performed only by authorized personnel with the appropriate training. Maintenance and servicing is performed based on EN 60079-17. As part of the maintenance, in particular, parts that depend on ignition safety must be inspected.
This includes, in particular, the seals, the fastening system, cable, and wire entries.
The maintenance intervals must be chosen depending on the operating conditions and the operating time. When maintenance work is performed on the enclosure, care must be taken to ensure that no circuit-dependent dangerous remote effects can occur.
Warning – “Enclosures must be cleaned with Damp Cloth only”
APPLICABLE NATIONAL REGULATIONS MUST BE ADHERED TO DURING THE OPERATION OF THE ENCLOSURES LISTED ABOVE.

Schedule of Limitations

  1. The service temperature range is -50°C to +180°C.
  2. Installation of electrical components inside the empty enclosures requires further assessment by an ExCB.
  3. Enclosure backside cover and earthing screws need to be tightened with a suitable torque w.r.t to Bolt size.
  4. The empty enclosure with painting (Coating thickness up to 0.18mm) must not be used in areas affected by charge-producing processes, mechanical friction and separation processes, electron emission (e.g., in the vicinity of electrostatic coating equipment), and pneumatically conveyed dust.
  5. All unused entry openings must be fitted with a suitable cable entry device of protection type Ex “eb” and Ex “tb” and must have a minimum IP66 rating.
  6. Entry holes shall be perpendicular to the equipment face to ensure the correct sealing arrangement of an accessory. Plain holes shall be no larger than 0.7mm above the major diameter of the accessory thread.

Disposal
Please observe your national disposal regulations.

For queries pls contact

RITTAL Private Limited, Nos. 23 & 24,
KIADB Industrial Area, Veerapura,
Doddaballapur – 561203
Bangalore , India Phone: +91 80 6141 3924
info@rittal-india.com,
Ex-large Enclosure: Instruction Manual – Ex Large Enclosure