Honeywell DR65A3000 Ducted Whole House Dehumidifier Installation Guide
- June 1, 2024
- Honeywell
Table of Contents
- INCLUDED IN THIS BOX
- Installation Checklist
- Benefits
- Maintaining Ideal Humidity
- Setting the Controls
- Control Options
- Specifications
- Install to Fit Your Application
- Terminal Description
- Wiring
- Checkout
- Cleaning
- Technical Description
- Troubleshooting
- Parts List
- 5-Year Limited Warranty
- CUSTOMER SUPPORT
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Honeywell DR65A3000 Ducted Whole House Dehumidifier
INCLUDED IN THIS BOX
OPTIONAL CONTROLS SOLD SEPARATELY
Note: If IAQ thermostat such as Prestige™ IAQ kit is used, a separate dehumidify control is not needed.
Tools required to install DR65A3000 dehumidifier
-
3/8” hex drive
-
Drill or duct cutting tool
-
Wire stripper/cutter
-
Standard screwdriver
-
T20 Torx screwdriver
-
Duct tape
-
8” round duct and starter collar
-
18-22 gauge, 5 conductor thermostat wire
-
1/2” diameter drain line (8’)
-
1/2” drain clamps (2)
-
3/4” male NPT drain outlet
Options -
1/2” drain p-trap (may be required by local code)
-
Drain pan
-
Float switch or water sensor (normally closed)
A: DR65A3000 (1)
B: MERV 11 Filter (1)
C: Installation Guide
D: Prestige IAQ Kit
D1: Prestige IAQ Kit
D2: Vision PRO™ Smart or Vision PRO Red LINK®
D3: H6062 Humidi PRO Digital Humidity Control (HVAC fan wired to DR65,
not H6062)
D4: T10 or T10+ Pro Smart Thermostat
Installation Checklist
Included in This Box
A DR65A3000 (1)
B MERV 11 Filter (1)
C Installation Guide
Control Options (Sold separately)
D1 Prestige IAQ Kit
D2 Vision PRO Smart or Vision PRO Red LINK
D3 H6062 digital control
D4 T10 or T10+ Pro Smart Thermostat
Tools Required (Not Supplied)
-
3/8” hex drive
-
Drill or duct cutting tool
-
Wire stripper/cutter
-
Standard screwdriver
-
T20 Torx screwdriver
-
Duct tape
-
8” round duct and starter collar
-
18-22 gauge, 5 conductor thermostat wire
-
1/2” diameter drain line (8’)
-
1/2” drain clamps (2)
-
3/4” male NPT drain outlet
Options -
1/2” drain p-trap (may be required by local code)
-
Drain pan
-
Float switch or water sensor (normally closed)
Note: Float switch or drain pan required if installed in location where water damage can occur if drain line gets clogged.
Warning: Installation must be performed by a qualified service technician
and must comply with local codes.
Remove power to the device before installing or servicing the device.
Failure to connect the device according to these instructions may result in
damage to the device or the controls.
INSTALLATION INSTRUCTIONS BEGIN ON PAGE 2
- The DR65A3000 is designed to be installed indoors in a space that is protected from rain and flooding.
- Install the unit with space to access the front panel for maintenance and service.
- Avoid directing the discharge air at people, or over the water in pool areas.
- If used near a pool or spa, be certain there is no chance the unit could fall into the water or be splashed, and that it is plugged into a ground fault interrupt (GFI) outlet.
- To ensure quiet operation, do not place the device directly on the structural supports of the home.
- A drain pan must be placed under the unit if installed above a living area or above an area where water leakage could cause damage.
- DR65 should be installed on a stationary base or sitting on the floor. It should not be mounted above other HVAC components such as the A-coil.
- Never operate a unit with a damaged power cord. If the power cord is damaged it must be replaced by the manufacturer, its service agent, or similarly qualified person in order to avoid a hazard.
- The appliance is not intended for use by persons (including children) with reduced physical, sensory, or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
The DR65A3000 ensures the home is maintained at proper humidity levels through its high performance and efficiency.
Benefits
- Removes up to 65 pints (30.8 l) of water per day from the indoor air.
- Built-in humidity control requires no additional wiring to an external control. Just plug in and go! Choice of external control options also available for centrally ducted control.
- Electrocoating reduces coil corrosion and helps prevent refrigerant leaks
- Built-in transformer and fuse.
Maintaining Ideal Humidity
Dew points and relative humidity (RH) affect the way your body senses heat. Higher humidity levels cause the air to feel much hotter than the actual temperature. When maintained properly, you can run your cooling equipment less because dehumidified air feels cooler.
Ideal humidity is defined by industry experts* as being between 40-60% on an average annual basis.
Capacity:
34 pints/day (60 ºF [15.6 ºC], 60 %RH)
47 pints/day (70 ºF [21.1 ºC], 60 %RH)
65 pints/day (80 ºF [26.7 ºC], 60 %RH)
When indoor humidity exceeds 60%, the home is more susceptible to mold and
mildew growth. DR65A3000 safe- guards against excessive humidity in the home
year-round.
*American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE).
Setting the Controls
BUILT-IN HUMIDITY CONTROL: An intuitive ‘set and forget’ humidistat is built into the DR65A3000 to set the humidity level right on the device. Optional external control wiring is also available. If an external DE humidistat is used, the on-board dehumidification control should be set to 80% RH.
Control Options
The DR65A3000 may be used with one of the following external controls:
T10 or T10+ Pro Smart Thermostat (T10 models begin with THX321WF. T10+ kits begin with YTHM1004R)
- Controls heating/cooling and dehumidification.
- Advanced dehumidifier setting options to run system fan with dehumidifier or lock out dehumidifier if cooling is running.
Prestige IAQ Thermostat Kit (kit numbers start with YTHX9421R)
- Controls heating/cooling, dehumidification, and ventilation.
- Wireless sensor for displaying outdoor temperature and humidity.
- Advanced dehumidifier setting options to run system fan with dehumidifier or lock out dehumidifier if cooling is running.
- Maintenance and service reminders.
- High definition color display.
- Red LINK Wireless technology
Vision PRO Smart or Vision PRO Red LINK Thermostat
- WiFi (TH8321WF1001) or Red LINK Wireless technology (TH8321R1001)
- Controls heating/cooling and dehumidification.
- Display outdoor temperature and humidity.
- Advanced dehumidifier setting options to run system fan with dehumidifier or lock out dehumidifier if cooling is running.
HumidiPRO Digital Control (H6062A1000)
- Manual dehumidification control
- Dehumidifier compressor protection
- RH% and outdoor temperature calibration
- Adjustable high and low range stops (10-90%)
Specifications
Install DR65A3000 according to National Electric Codes.
Dry-Bulb Temp | Intake Humidity | Capacity (Pints/Day) |
---|---|---|
80°F (26.7°C) | 60% RH | 65 |
70°F (21.1°C) | 60% RH | 47 |
60°F (15.6°C) | 60% RH | 34 |
Home Size (square ft) @ 8 ft ceiling | **Dehumidifier Capacity Required |
to Maintain Desired Indoor RH*
---|---
60% RH Indoor (pints/day)| 50% RH Indoor (pints/day)| 40% RH
Indoor (pints/day)**
2080| 49–54| 55–58| 71–78
2600| 61–68| 65–72| 90–97
3120| 75–82| 79–86| 95–110
*Based on extreme climates where outdoor humidity is 70-90% RH. For less extreme climates, larger homes can be adequately served with less capacity. Actual requirements may vary
Dimensions in inches and (mm):
Airflow versus external static pressure (0–1” water pressure) with collars attached
0” | 160 CFM |
---|---|
0.2” | 140 CFM |
0.4” | 120 CFM |
0.6” | 100 CFM |
Product weight : 60lb (27 Kg)
Shipping weight : 68lb (31 Kg)
Shipping dimensions : 16.7” H × 17” W × 32.9” L
Media Filter : MERV 11, 9” H x 11” W x 0.75” D
Drain connection : 3/4” threaded female NPT connection.
Duct connections: 8” round inlet and outlet. ABS plastic, compatible for
connection to rigid or flexible ducting with sheet metal screws and/or tape.
Cabinet: 20 gauge galvanized steel powder-coat painted.
Insulation: R value 1
Compressor: Rotary-style, 6.1 KBTU
Refrigerant: R-410A, 15 oz.
Operating Temp Range (outside cabinet): 34ºF to 135ºF (1.1ºC to 57.2ºC)
Operating Humidity Range: 0-99% RH
Input ratings
- Electrical input voltage: 120 VAC, 60 Hz nominal
- Input current: 5.2 A
Output ratings
- Power transformer to R/C terminals: 24 VAC, 0.85 A
- Energy Performance: 2.22 liters (4.7 pints) per kilowatt hour (KWH)
Standards and approval body requirements
- ETL Listed per UL 60335-1, 60335-2-40, CSA C22.2 No. 60335-1 and 60335-2-40
Install to Fit Your Application
Flex duct is recommended in connecting to the DR65A3000 collars to reduce vibration noise.
Duct Sizing: Use minimum 8” diameter round for duct lengths up to 25’ Minimum 10” required for lengths longer than 25’ Duct branches from the main inlet/ exhaust should be minimum 8” round for 2-3 branches, and 8” round or larger for 4 branches or more.
Isolated Areas: Effective dehumidification may require ducting to isolated or
stagnant air flow areas.
Electrical requirements:
120 VAC outlet. Ground fault interrupter (GFI) recommended.
Note: If voltage is below 102 VAC or above 132, dehumidifier may be
locked out.
A: Dedicated Return to Dedicated Supply
- DR65A3000 will not be ducted to a DEHUMIDIFIER forced air HVAC system.
B: Main Return to Main Return
Ideal when…
- Running DR65A3000 with A/C operation.
- System fan must run with dehumidifier.
- Minimizing discharge air temperature (DAT) increase is preferred.
- Access to a dedicated central return for DR65A3000 is not available.
Plumbing
Attach 3/4″ male NPT PCV drain nozzle (use teflon tape if needed). Do not over-tighten.
Connect 1/2” drain tube to male connection drain outlet.
Secure drain tube to connector with hose clamp.
Run drain hose continuously downhill to an approved drain or condensate pump.
The drain line must include a water trap to prevent air from entering or
exiting the dehumidifier.
NOTE: It is important that the DR65 is leveled for drain line to work properly.
Terminal Description
CAUTION: Low voltage hazard.
Can cause equipment damage.
Disconnect HVAC equipment before beginning installation.
Two wiring terminal blocks are located on the exhaust end of the dehumidifier.
NOTE: The outer screws on each terminal block secure the block to the chassis. They are not used for wiring.
The six terminals for the left hand terminal block are:
FLOAT (2): External low-voltage water sensor or float switch
DHUM: Compressor and fan operation for dehumidification
R : 24V hot (output)
FAN: Fan activation only for ventilation
C : 24V common (output)
External 24V devices can be powered from R and C terminals (20VA max.)
The right hand terminal block in the above image is used only for interlocking
a DR65A3000 with an equipment fan. These terminals are needed if:
A : The dehumidifier is mounted on the HVAC ducting.
B : The dehumidifier control cannot turn on the blower fan with a call
for dehumidification (H6062, H8908).
The three terminals are:
Gt : Wires to G at thermostat
Rf : Wire to R at HVAC (furnace/air-handler)
Gf : Wire to G at HVAC (furnace/air-handler)
Wiring
Wire the DR65A3000 according to the diagram that applies to your desired
operation.
Follow this diagram for ducted operation with the onboard DE humidistat.
Follow this diagram if using the H6062 Digital Humidity Controller.
NOTE: When H6062 control is used with a DR65 connected to HVAC ducting, make sure to wire the Rf, GT, and GF as shown in the diagram for the mechanical de humidistat below.
Follow this diagram if using an external manual de humidistat.
Dehumidifier with zoning
When a DR65 is used with a zoned system, wire Rf and Gf from DR65 to R and G
at HVAC (furnace/air-handler). Wire Gt from DR65 to G on equipment terminals
of zone panel. Set the de humidity control to dehumidify independent of system
fan (the DR65 will be turning on the fan).
Usually only one control is used for the dehumidifier in a zoned system. That could be an IAQ thermostat from a central zone or a stand alone dehumidify control. This control is wired to the R and DHUM on the DR65 as shown in any of the diagrams in this file.
Follow this diagram for ducted operation with external ventilation control.
NOTE: Dehumidity control circuit not shown in this diagram.
Follow this diagram if using DR65A3000 with either a Prestige or TH8321R1001
Red LINK Vision Pro & EIM.
Checkout
Plug in the DR65A to power. Turn the humidity control knob to a low RH% level
to initiate a dehumidification call. Confirm that the DR65A3000 compressor and
fan turn on. If the RF and GF on the DR65A is wired to the furnace, the
furnace fan should also run. There may be a delay of up to 5 minutes before
the unit turns on.
When checkout is complete, be sure to turn the control to the desired RH%. If
an external control is wired to the DR65A, then turn the control knob on the
DR65A to the highest RH setting.
Cleaning
On an annual basis, perform the following maintenance requirement to ensure the dehumidifier runs at peak efficiency.
-
Unplug the dehumidifier before beginning service. Remove magnetic access panel to access the filter.
-
Remove filter and replace with new filter. Reinstall magnetic access panel.
-
Check the drain connection and drain line to ensure it is clear of debris and sludge. Ensure all hose connections are secure once maintenance of the drain lines is complete.
-
When service is complete, initiate a call for dehumidification and check that the compressor and fan activate.
If your thermostat has maintenance reminders, reset those. All thermostats listed in this file have optional maintenance reminders.
Technical Description
DR65A3000 uses a refrigeration system similar to an air conditioner to remove
heat and moisture from incoming air and add heat to the air that is
discharged. Hot, high-pressure refrigerant gas is routed from the compressor
to the condenser coil. The refrigerant is cooled and condensed by giving up
its heat to the air that is about to be discharged from the unit. The
refrigerant liquid then passes through a filter drier and capillary tubing
which causes the refrigerant pressure and temperature to drop. It next enters
the evaporator coil where it absorbs heat from the incoming air and
evaporates. The evaporator operates in a flooded condition, which means that
all the evaporator tubes contain liquid refrigerant during normal operation. A
flooded evaporator should maintain nearly constant pressure and temperature
across the entire coil, from inlet to outlet.
Defrost
If the DR65 dehumidifier coil starts to freeze up it goes into defrost mode. The dehumidifier shuts off the compressor and runs the fan until the coil temperature rises. For rev 2 models (a sideways 2 after the model number on the sticker) the dehumidifier makes a single beep when first powered up or when it enters defrost mode.
Troubleshooting
Troubleshooting videos are available on the Resideo Pro YouTube channel playlist.
CAUTION: Servicing the DR65A3000 with its high pressure refrigerant system and high voltage circuitry presents a health hazard which could result in death, serious bodily injury, and/or property damage. Service should only be performed by a qualified service technician.
Problem | Troubleshooting Steps/Possible Causes of Issue |
---|
Neither the dehumidifier fan nor compressor run when the control is calling for dehumidification.|
- Bypass any external control (if used) by turning the control knob on DR65 to “ON”. If that works, and an external control is used, troubleshoot the control and wiring to the R and DHUM on DR65.
- Verify the drain line is not clogged. An internal float switch can lock out the dehumidifier if the drain line gets clogged.
- Wait 5 minutes from the time you made the call for dehumidify. Series 2 versions of the DR65 have a 2-5 minute compressor protection delay. If the control is digital, it may also have a delay. These delays will overlap, so if the humidity control has been calling for over 5 minutes and power has not cycled, the dehumidifier should run.
- If it does not run after the delay, install a jumper between the R and DHUM terminals on the dehumidifier. This bypasses the control circuit. If the unit runs, the issue was with the control or wires to the control.
- If the unit still does not run within 5 minutes of installing a jumper from R to DEHUM, verify voltage to the outlet that the dehumidifier is plugged into. This should be 120 VAC nominal and if it drops below 102 VAC or above 132 VAC, the dehumidifier will not run.
Note: Be sure to remove the jumper after testing.
The dehumidifier fan runs but the compressor does not when the con- trol is
calling for dehumidification.| If there is a wire to “FAN” on the
dehumidifier, remove that wire and see if the dehumidifier fan continues to
run. If the fan shuts off, then whatever is controlling the fan was
calling for ventilation. That doesn’t mean a control is calling for
dehumidify. Follow the steps from the first issue for further testing.
If there is no wire to the “FAN” terminal and the dehumidifier FAN is running
but the compressor is not, the dehumidifier may be running in defrost.
Fan runs when there is a call for dehumidification and the ventilation control
is OFF, but the compressor cycles on and off too frequently.|
- Low ambient temperature and/or humidity causing unit to cycle through defrost mode.
- Defective compressor overload.
- Defective compressor.
- Defrost thermostat defective.
- Dirty air filter(s) or airflow restricted.
- Low refrigerant charge, causing defrost control to cycle.
- Bad connection in compressor circuit. Fan does not run with fan switch in either position.
Fan does not run with ventilation activated.
Compressor runs briefly but cycles on & off with humidity control turned to
ON.
|
- Loose connection in fan circuit.
- Obstruction prevents fan rotation.
- Defective fan.
- Defective fan relay.
- Defective fan capacitor.
Evaporator coil frosted
continuously, low de-humidifying capacity.
|
- Defrost thermostat loose or defective.
- Low refrigerant charge.
- Dirty air filter(s) or airflow restricted.
Unit not providing ventilation.|
- Check control wire connections (check connections at fresh air damper also).
- Defective fresh air damper.
- Dirty air intake. Clean outside intake hood.
Unit removes some water, but not as much as expected.|
- Air temperature and/or humidity have dropped.
- umidity meter and or thermometer used are out of calibration.
- Unit has entered defrost cycle.
- Dirty air filter.
- Defective defrost thermostat.
- Low refrigerant charge.
- Air leak such as loose cover or ducting leaks.
- Defective compressor.
- Restrictive ducting.
- Optional Condensate Pump Safety Switch open.
Unit Test to determine problem:|
- Detach field control wiring connections from main unit.
- Connect the R and FAN contacts from the main unit together; only the impeller fan should run. Disconnect the wires.
- Connect the R and DHUM contacts from the main unit together; the compressor and impeller fan should run.
- If these tests work, the main unit is working properly. You should check the control panel and field control wiring for problems next.
- Remove the control panel from the mounting box and detach it from the field installed control wiring. Connect the blue, yellow, and green wires from the control panel directly to the corresponding colored pigtails on the main unit. Leave the violet, white, and red wires disconnected!
- Turn on the humidity control. The compressor and impeller fan should run.
- If these tests work, the problem is most likely in the field control wiring.
Parts List
Figure Reference | Base and Accessory Parts | Part Number |
---|---|---|
1 | Dehumidifier | DR65A3000 |
2 | Filter | 50049537-005 |
5-Year Limited Warranty
Resideo warrants this product to be free from defects in workmanship or materials, under normal use and service, for a period of five (5) years from the date of first purchase by the original purchaser. If at any time during the warranty period the product is determined to be defective due to workmanship or materials, Resideo shall repair or replace it (at Resideo’s option).
If the product is defective, (i) return it, with a bill of sale or other dated proof of purchase, to the place from which you purchased it; or (ii) call Resideo Customer Care at 1-800-468-1502. Customer Care will make the determination whether the product should be returned to the following address: Resideo Return Goods, 1985 Douglas Dr. N., Golden Valley, MN 55422, or whether a replacement product can be sent to you.
This warranty does not cover removal or reinstallation costs. This warranty shall not apply if it is shown by Resideo that the defect was caused by damage which occurred while the product was in the possession of a consumer.
Resideo’s sole responsibility shall be to repair or replace the product within the terms stated above. RESIDEO SHALL NOT BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND, INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING, DIRECTLY OR INDIRECTLY, FROM ANY BREACH OF ANY WARRANTY, EXPRESS OR IMPLIED, OR ANY OTHER FAILURE OF THIS PRODUCT.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so this limitation may not apply to you.
THIS WARRANTY IS THE ONLY EXPRESS WARRANTY RESIDEO MAKES ON THIS PRODUCT. THE DURATION OF ANY IMPLIED WARRANTIES, INCLUDING THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, IS HEREBY LIMITED TO THE FIVE YEAR DURATION OF THIS WARRANTY. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.
This warranty gives you specific legal rights, and you may have other rights which vary from state to state.
If you have any questions concerning this warranty, please write Resideo Customer Care, 1985 Douglas Dr, Golden Valley, MN 55422 or call 1-800-468-1502.
CUSTOMER SUPPORT
© 2024 Resideo Technologies, Inc. All rights reserved. The Honeywell Home
trademark is used under license from Honeywell International, Inc.
This product is manufactured by Resideo Technologies, Inc. and its affiliates.
Resideo Technologies Inc.
1985 Douglas Drive North, Golden Valley, MN 55422
1-800-468-1502
33-00297EFS—17 SA Rev. 01-24
www.resideo.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>