Intended Use

The read-out head ecom-AK enables the recall of data made available by digital firings automats. Information like trouble sources, error history, flame signal and operation voltage are received by the ecom-AK as optical signal at the reset button of the firing automat and shown on the graphic display.
The ecom-AK is able to identify the make and the model of the following firing automats:
Siemens-Landis & Staefa: LMG, LMO, LME
Honeywell-Satronic: Dxx, Dxx-N, SH, SH-N, SG, SG-N (DKO 970, DKO 972, DKO 974, DKO 976, DKO 992, DKW 972, DKW 976, DMO 976, DIO 974, DIO 976, DKG 970, DKG 972, DLG 974, DLG 976, DMG 970, DMG 971, DMG 972, DMG 973, DMG 991, DVI 980, DVI 982, SH 11 x, SH 21 x, SH 12x, SH 23x, SG 11 x, SG 51 x, SG 13x, DKO 970-N, DKO 972-N, DKO 974-N, DKO 976-N, DKO 992-N, DKO 996-N, DKW 972-N, DKW 976-N, DMO 976-N, DIO 974-N, DIO 976-N, DKG 970-N, DKG 972-N, DLG 974-N, DLG 976-N, DMG 970-N, DMG 971-N, DMG 972-N, DMG 973-N, DMG 991-N, DVI 980-N, DVI 982-N, SH 11x-N, SH 21x-N, SH 12x-N, SH 23x-N, SG 11x-N, SG 51x-N, SG 13x-N)

Scope of Delivery

  • ecom-AK
  • Connection cable
  • Protective bag
  • 2x 1,5 V AA Batteries

General Safety Instructions

WARNING

Hazard of Injury
Improper work on incinerators can cause injuries.
Work on incinerators may only be done by qualified specialists.

CAUTION

Malfunction of the Readout Process
Exposure to strong light can disturb the readout process. Protect ecom-AK from strong light.

Device Description

  1. Photo Diode
  2. Housing Head
  3. Housing
  4. Display
  5. Setting Key
    Device Description

Set Language

  1. Hold down the setting key until Language: English on the display appears.
  2. Use the setting key to select the required language.

NOTICE:
ecom-AK starts after about 5 s in the selected language.

Initiation/Measurement

Set burner control units to diagnostic mode

NOTICE:
Applies only to Siemens burner controls!

Burner control in operating position:

  • Press reset button for at least 3 seconds.

Burner control in Lockout position:

  • Press reset button for at least 3 seconds.
  • Press reset button again for at least 3 seconds.

Read out burner control

  1. Set ecom-AK to the interference suppression button.

  2. Enable ecom-AK by pressing the setting key.
    NOTICE
    When using the Satronic or Siemens PC software, hold down the setting key until PC mode appears on the display.
    When using the AK PC software, the ecom-AK must not be started in PC mode.

  3. ecom-AK searches for automat information.
    NOTICE
    ecom-AK schaltet sich nach 2 min. ab, wenn es kein Signal erkennt.

Display

Use the setting key to recall the data step by step:

  1. Operating Status of the Burner

  2. Error

  3. Flame identified

  4. Valve 2

  5. Valve 1

  6. Ignition

  7. Oil Preheater

  8. Engine

  9. Operating Voltage

  10. Flame Signal
    Display

  11. Flame Signal

    • current flame signal – minimum signal
  12. Reserve safety time

    • Difference between flame detection and end of safety time – Satronic burner controls only.
  13. Error

    • Satronic:
      Display of the current and the last 2 errors – fault description, flame signal with operation-voltage at fault, time of fault shut-down are displayed in 3-second intervals.

    • Siemens:
      Display of the current and last 5 faults – with number of burner starts when the fault occurred.

  14. Statistics

    • Satronic:
      Display Total number of faults, number of ,,extraneous light” faults, number of ,,no flame after safety time” faults, number of ,,flame failure” faults, total number of burner starts, number of burner starts since resetting the service counter.

    • Siemens:
      Total number of burner starts, number of burner starts since resetting the service counter.

  15. Control Times of the burner control

NOTICE

The type and scope of the data vary according to the type and software version of the burner control.

Switch-off

  • Keep setting key pressed for 4 seconds.
  • If no key is pressed during operation, the display lighting is switched off after 10 minutes.
  • The device switches off after 60 minutes.

Change Batteries

NOTICE
The two 1.5 V AA batteries must be replaced when the battery capacity indicator flashes.

  1. Press locking latches on the housing head inwards.
  2. Pull off housing head to the front.
  3. Remove circuit board.
  4. Change batteries.
  5. Reassemble ecom-AK in reverse order.

PC Software AKPC

NOTICE

A special cable is required for the connection to the PC:

  • PC interface RS232: data cable AK-PC or
  • PC interface USB: Data cable AK-PC + adapter cable RS232- USB.
  1. Start programme with ,,Start”/,, Programmes”/,, AKPC”.
  2. Select COM port from ,,Setup” menu.
  3. Select COM Port.
  4. Confirm with ,,OK”.
  5. Connect ecom-AK to PC via the connection cable.
  6. Connect ecom-AK to burner control.
  7. Switch on ecom-AK.

NOTICE
The data of the automatic burner control are displayed on 2 pages in the software.

  1. Oil preheater / Air pressure switch
  2. Engine is running
  3. Ignition is active
  4. Actual flame signal
  5. Flame signal min
  6. Flame is detected
  7. Valve 2
  8. Operating voltage
    PC Software AKPC
1 Model designation
2 Total number of burner starts
3 Error statistics
4 Control times burner control
5 Current error
6 Error history
7 Active burner components
8 Save data to Text file
9 Print data
10 Copy data to clipboard

PC Software AKPC

FAQ

FAQ

Connection to ecom-devices| Connection to the devices:

  • ecom-D
  • ecom-EN3
  • ecom-J2KNpro is possible with included connection cable

Data reading does not work|

  1. Burner control cannot be read out (see list)
  2. Burner control is not set to diagnostic mode (onl Siemens burner controls)

Technical Data

Technical Data

Power Supply| 2x Rechargeable Battery Type AA; 1.2 V
2x Battery Type AA; 1.5 V
Power Consumption| ca. 100mA
Storage Temperature| -20 °C – +50 °C
Operating Temperature| -20 °C – +50 °C
Size| 88 mm x 41 mm x 32 mm

NOTICE
Subject to technical changes! (Status 02.2023)

Maintenance

To ensure the accuracy of your measuring device, we recommend an annual inspection by an authorised ecom partner. In case of heavy use, shorter inspection intervals should be chosen – please contact your ecom partner.

Disposal

  • Dispose of used batteries at the designated collection points.
  • Dispose of packaging material in an environmentally friendly manner.
  • Old devices must be disposed of in an environmentally friendly manner by an authorised centre.

NOTICE
On request we take back old appliances and dispose of them in an environmentally friendly way.

CE Declaration of Conformity

Declaration of Conformity

UK Declaration of Conformity

Declaration of Conformity

Customer Support

ecom GmbH
Am GroBen Teich 2 D-58640 Iserlohn
info@ecom.de
www.ecom.de

Phone: +49 2371 945-5
Fax: +49 2371 40305

UK importer:

DRM Technic Ltd.
Unit 25 Raleigh Hall Industrial Estate, Stafford, Staffordshire, ST21 6JL, UK
sales@drmtechnic.com
www.drmtechnic.com

Phone: +44 (0) 1785 556 593

Logo

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals