hyco SF7 Pressure and Expansion Kit Instruction Manual

June 2, 2024
hyco

hyco SF7 Pressure and Expansion Kit

Product Information

  • Specifications
    • Product: SF7 Pressure and Expansion Kit
    • Compatibility: Speedflow range of unvented water heaters (5, 10, and 15L capacity)
    • Contents:
    • Manifold including check valve and service valve
    • Pressure reducing valve
    • Expansion vessel
    • Flexible hose
    • Bracket
    • Tundish
    • 1/2 to 15 mm compression fitting adaptor
    • 3 x 1/2 black rubber washers

Product Usage Instructions

  • Installation
    • The installation of the SF7 Pressure and Expansion Kit should be carried out by a competent person in compliance with local plumbing regulations.
  • Commissioning
    • Once installed, ensure proper commissioning of the kit according to the provided guidelines.
  • Maintenance
    • Regular maintenance is essential for optimal performance. Refer to the maintenance section in the manual for detailed instructions.
  • Troubleshooting
    • If you encounter any issues like water discharge from the relief valve, refer to the troubleshooting section for possible causes and solutions.
  • Guarantee and Service Policy
    • The product is guaranteed against faulty materials and manufacturing defects for one year from the date of purchase. Contact the service department for assistance.
  • Contact Us
    • If you experience any problems, contact our service department before taking further action. Most issues can be resolved without returning or uninstalling the product.

FAQs

  • Q: What should I do if water is discharged from the pressure relief valve when the appliance is turned off?
    • A: Check the pressure-reducing valve as outlined in the maintenance section of the manual.
  • Q: What could be causing water discharge from the pressure relief valve while the appliance is heating?
    • A: This could be due to pressure build-up caused by water expansion. Check the charge of the expansion vessel as per maintenance instructions.
  • Q: How can I address water discharge from the pressure relief valve during appliance heating?
    • A: Ensure there are no obstructions between the water heater and expansion vessel, referring to the installation diagram provided in section 2.

Overview

  • Thank you for purchasing an SF7 Pressure and Expansion Kit with a fast-install inlet group (manifold) incorporating a check valve and service valve.
  • To be used with the Speedflow range of unvented water heaters, available in 5, 10 and 15L capacity.
  • Please read and follow these instructions to ensure that installation and operation are as simple and safe as possible.

Box Contents

  • Manifold inc. check valve and service valve
  • Pressure reducing valve
  • Expansion vessel
  • Flexible hose
  • Bracket
  • Tundish
  • 1/2″ to 15 mm compression fitting adaptor
  • 3 x 1/2″ black rubber washers

Installation

The installation of this kit should be carried out by a competent person per any local plumbing regulations.

Important: Grey area represents an expansion zone. It is imperative that no fittings, other than those specified, are fitted in the expansion zone:

hyco-SF7-Pressure-and-Expansion-Kit-FIG-1

  • Connect the inlet of the manifold to the incoming water supply. The orientation of the manifold is optional, but the direction of flow must follow the arrow marked on the manifold.
  • Connect the flexible hose to the bottom outlet of the manifold using the supplied black washer.
  • Connect the ½” to 15mm compression fitting to the top outlet of the manifold using the supplied black washer.
  • Select a suitable location for the expansion vessel, consider the reach of the flexible hose as well as the need to keep the vessel itself in an upright orientation (hose connection at the bottom).
  • Attach the bracket to the wall before securing the vessel to it using the supplied banding.
  • Connect the flexible hose to the vessel using the black washer.
  • Using a length of 15 mm piping, connect the pressure relief valve (supplied with the heater) to the top outlet of the manifold. Run the outlet side of the pressure relief valve to a suitably safe drain via the tundish. The tundish must be installed vertically.
  • Make the final connection to the cold inlet of the water heater from the remaining outlet of the manifold.
  • Choose a suitable location to install the pressure-reducing valve. It must be upstream of the expansion vessel and nearby cold water draw-off.
  • The orientation of the valve is optional, but the direction of flow must follow the arrows marked on the body of the valve.
  • The pressure-reducing valve offers 15mm compression fittings on the inlet/ outlet.

Commissioning

  • Upon completion of installation, turn on the water supply to the manifold and allow the water heater to fill. Open the hot water tap to allow air to be purged from the system.
  • Once the water runs smoothly from the hot water tap and the air is purged from the system, close the tap, and inspect all fittings for leaks. Inspect the tundish to ensure no signs of discharge from the pressure relief valve (see section 6. Trouble Shooting).
  • Turn on power to the water heater and set the thermostat dial to maximum temperature. This is required to ensure the expansion vessel can accommodate the full amount of expansion the water heater can produce.
  • Allow the heating cycle to finish and inspect all fittings for leaks. Inspect the tundish to ensure no signs of discharge from the pressure relief valve (see section 6. Trouble Shooting).
  • Upon completion of commissioning, set the water heater to the desired temperature setting and leave these instructions for future reference with the property owner/ user of this kit.

Maintenance

  • Whilst the system is unpressurised and with the vessel drained of any water, check the expansion vessel to ensure the pressure meets that stated on the rating label. This must be done annually or if unexplained discharge from the relief valve is present.
  • Refer to the instructions supplied separately with the pressure-reducing valve for maintenance guidance.
  • Keep records of maintenance and ensure any future occupier of the building is fully aware of the requirement for maintenance.

Specification

Product| Manifold| Flexi hose| Expansion Vessel| Tundish| Pressure Reducing Valve
---|---|---|---|---|---
Connections| 2 x 15 mm compression 2 x 1/2” FBSP| 1/2 ” MBSP to 1/2 ” FBSP| 1/2 ” MBSP| 15 mm to 22 mm compression| 2 x 15 mm compression
Details| Built-in service and check valve| 600 mm length| 2 L preset at 3.5 bar| Plastic| Preset at 3.0 bar

Troubleshooting

Problem Possible Cause Solution

Water is discharged from the pressure relief valve whilst an appliance is turned off| Water pressure too high (above 4.2 bar)| Check pressure reducing valve (see section 4. Maintenance)
Water is discharged from the pressure relief valve whilst an appliance is heating| Pressure build-up caused by water expansion| Check the charge of the expansion vessel (see section 4. Maintenance)
Water is discharged from the pressure relief valve whilst an appliance is heating| Pressure build-up caused by water expansion| Ensure no obstruction between the water heater and the expansion vessel (see diagram in section 2. Installation)

Guarantee and Service Policy

  • This product is guaranteed against faulty materials and manufacture for a period of one year from the date of purchase.
  • Hyco will in its sole discretion replace, repair or refund any faulty unit.
  • Incorrect installation and failure to follow correct operating instructions are excluded.
  • Consequential costs such as labour charges or damage to surroundings are expressly excluded.

Contact Us

  • If you experience a problem with this product you should first contact our service department on 01924 225 200 before taking any further action.
  • Experience has shown that issues can often be resolved without the need to return or uninstall the product.
  • Hyco Manufacturing Ltd
  • Normandy Court
  • Express Way
  • Castleford, WF10 5NR
  • hyco.co.uk.
  • T 01924 225 200
  • E sales@hyco.co.uk.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

hyco User Manuals

Related Manuals