DEGA UPA III Compact Controller User Manual
- October 30, 2023
- DEGA
Table of Contents
- DEGA UPA III Compact Controller
- Product Information
- Product Technical Data
- Product For Your Safety
- Product Usage Instructions
- For your safety
- Technical data
- Operational conditions
- Product description
- Assembling and connecting the wiring
- Controls
- Maintenance
- Attachments
- warranty
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
DEGA UPA III Compact Controller
Product Information
DEGA UPA III Compact Controller
The DEGA UPA III is a third-generation compact evaluating controller designed as a separate device for mounting on a wall or on distributors. It is used to supply up to 32 transmitters via RS485 and up to 8 transmitters via current loop. The device evaluates the gas leak of the transmitters in 4 levels and can also connect one flooding sensor DEGA ZC II and one temperature sensor DEGA Tc II. The status of each transmitter is indicated on the LCD display of the controller.
Product Technical Data
-
Supply Voltage:
- 230 V AC/ 40VA
- 24 V DC/2 A nominal, operational range 20-28 V
-
Cable for Connecting of the Transmitters:
- via 4-20mA:
- shielded cable 3 x 1 mm (max. 1200 m), or 3 x 1,5 mm (max. 2400 m)
- via RS485:
- shielded cable 4 x 0,8 mm (max. 1200 m) – see section Wiring installation for RS485
-
Cable for Connecting the Sensors:
- Temperature Sensor DEGA Tc II:
- shielded cable 3 x 0,25 mm (max. 100 m)
- Flooding DEGA Zc II:
- shielded cable 4 x 0,25 mm (max. 100 m)
- Cable for Connecting Signalization a Pushbutton Cable 2 x 1mm
-
Output:
- USB (for PC configuration)
- RS485 – protocol DEGA, or MODBUS (on request) for the host system (PLC, PC)
- 10x switching relays 250 V/10 A
- 2x output for visual and acoustic alarms, max. load see chapter “Assembling and Connecting the Wiring Paragraph 6”
-
Communication Speed of RS485: 9.6 kB
-
Functional Safety EN61508: SIL 1
-
Dimensions without Bushings: 280x200x85 mm (WxHxD)
-
Weight: 1.4 kg
-
Capacity of the Internal Memory of History: 34 days at 60s
recording interval -
Interval Record Storage Memory: 60 s (adjustable range 1-255 s)
Product For Your Safety
- Beware of Static Electricity: Electronic components are sensitive to static electricity. Do not touch them directly – they may get damaged.
- The device is intended to be installed by a trained person: The product is designed for installation only by a certified technician. The manufacturer is not liable for damages resulting from incorrect or improper handling.
- In Case of Malfunction, Immediately Unplug from the Power Supply: If you notice an unusual smell or smoke emitting from the product, unplug it from the power supply, battery backup, and all other attachments. Continued operation could result in injury or property damage. After disconnecting, have the device inspected at an authorized dealer or manufacturer.
- Do Not Disassemble the Product and Ensure Against Its Contact with Water: Contact with internal components of the product maycause an electric shock. In case of any malfunction, entrust the servicing of the product exclusively to a certified service center. Contact with water can create a short circuit in the product and consequent damage to property or personal injury.
- Use Appropriate Cable Types: To ensure compliance with the parameters of the product, only use cable types recommended in this guide.
- Dispose of Used Products with Respect to the Environment: Dispose of them in accordance with the current legislation on environmental protection.
Product Usage Instructions
The DEGA UPA III compact controller is designed for use in evaluating gas leak transmitters. Follow the instructions below for proper usage:
- Install the device by a certified technician only. The manufacturer is not liable for damages resulting from incorrect orimproper handling.
- Ensure that the device is not touched directly as electronic components are sensitive to static electricity.
- Use appropriate cable types recommended in the user manual to ensure compliance with product parameters.
- In case of malfunction, immediately unplug the device from the power supply, battery backup, and all other attachments. After disconnecting, have the device inspected at an authorized dealer or manufacturer.
- Do not disassemble the device and ensure that it is not in contact with water to prevent damage to property or personal injury.
- Dispose of used products in accordance with the current legislation on environmental protection.
For your safety
-
Beware of static electricity
Electronic components are sensitive to static electricity. Do not touch them directly – they may get damanged. -
The device is intended to be installed by a trained person
The product is designed for installation only by a certified technician. The manufacturer is not liable for damages resulting from incorrect or improper handling. -
In case of malfunction, immediately unplug from the power supply
If you notice an unusual smell or smoke emitting from the product, unplug it from the power supply, battery backup and all other attachments. Continued operation could result in injury or property damage. After disconnecting, have the device inspected at an authorized dealer or manufacturer. -
Do not disassemble the product and ensure against it’s contact with water
Contact with internal components of the product may cause an electric shock. In case of any malfuction entrust the servicing of the product exclusively to a certified service centre. Contact with water can create a short circuit in the product and consequent damange to property or personal injury. -
Use appropriate cable types
To ensure compliance with the parameters of the product, only use cable types recommended in this guide. -
Dispose of used products with respect to the environment
Dispose of them in accordance with the current legislation on environmental protection.
Technical data
-
Supply voltage: 230 V AC/ 40VA 24 V DC/2 A nominal, operational range 20-28 V
-
Cable for connecting of the transmitters:
- via 4-20mA: shielded cable 3 x 1 mm (max. 1200 m), or 3 x 1,5 mm (max. 2400 m)
- via RS485: shielded cable 4 x 0,8 mm (max. 1200 m) – see section “ Wiring installation for RS485“
-
Cable for connecting the sensors:
- Temperature sensor DEGA Tc II: shielded cable 3 x 0,25 mm (max. 100 m)
- Flooding DEGA Zc II: shielded cable 4 x 0,25 mm (max. 100 m)
-
Cable for connecting signalization a pushbutton cable 2 x 1mm
-
Output: USB (for PC configuration)
RS485 – protocol DEGA, or MODBUS (on request) for the host system (PLC, PC) 10x switching relays 250 V/10 A
2x outupt for visual and acoustic alarms, max. load see chapter „Assembling and connecting the wiring“ paragraph 6 -
Communication speed of RS485: 9,6 kB
-
Functional safety EN61508: SIL 1
-
Dimensions without bushings: 280x200x85 mm (WxHxD)
-
Weight: 1,4 kg
-
Capacity of the internal memory of history: 34 days at 60s recording interval
-
Interval record storage memory: 60 s (adjustable range 1-255 s)
Operational conditions
- Ambient temperature: -20 to +85 °C
- Relative humidity: 0-95 % RH
- Air pressure: 86 – 108 kPa
- Protection level with a cover: IP 54
- Location: BE1 – non-explosive atmosphere
Product description
DEGA UPA III – The third generation compact evaluating controller is designed as a separate device used for mounting on a wall or on distributors. It is used to supply up to 32 transmitters via RS485 and up to 8 transmitters via current loop. It evaluates the gas leak of the transmitters in 4 levels. It is also possible to connect one flooding sensor DEGA ZC II and one temperature sensor DEGA Tc II. The status of each transmitter is indicated on the LCD display of the controller. The controller is equipped with 10 pieces of freely configurable relays, 2 outputs for visual and acoustic alarms, an output for impulsive closing of emergency valves, a USB port and a RS485 for connecting to the host system (PLC, PC with visualization)
Outer case
- Cover
- Bottom
- Indents for bushings
- Opening handle
- LCD DISPLAY
Terminal block
- Terminal block relay RE1-RE3
- Terminal block relay RE4 and RE5
- Terminal block relay RE6-RE7
- Trimmer for regulating the suppy voltage 22-26V
- Terminal block relay RE8-RE10
- Fuse T400mA
- Auxiliary input/output 24V DC
- Power supply terminal block 230VAC
- Temperature sensor terminal block
- Acoustic alarm lay-key terminal block
- Flooding sensor terminal block
- Acoustic alarm terminal block
- Bus temrinal block #1 for digital transmitters
- Bus temrinal block #0 for digital transmitters
- RS485 for the host system
- Analog inputs
- Optical alarm terminal block
- Emergency valve output terminal block
- Backup battery for memory
- USB connector
DegaConfig – adjustment software enabling full configuration of the controller
Assembling and connecting the wiring
Before assembling, read the valid instalation standarts EN 60079-29-2
(Selection, instalation, use and maintenance of detectors for combustible
gases and oxygen) and EN 45544-4 (Guildelines for the selection, installation,
use and maintenance of detectors of toxic substances).
In explosive environments the electrical installation must be performed
according to ČSN EN 60079-14 (Electrical instalation in hazardours areas).
-
Assembly of the controller
- a) Pull the handle on the right side of the controller to unlock and lift the cover
- b) Drill the required amount of holes for bushings into the indents of the top and bottom part of the case
- c) Anchor the controller on a flat surface using four 6mm fasteners
- d) Connect the wiring
- e) Close the cover of the case and lock the controller by using the handle
-
Connecting a transmitter via current loop
Connect one transmitter on each channel of the controller: -
Connecting a transmitter via RS485
It is possible to connect up to 16 transmitters on each controller input, depending on their electrical distance from the controller.
Wiring installation for RS485
Wiring must be done using bus topology and according to the RS485 principles.
Wiring must be done using bus topology and according to the RS485 principles.
Maximum number of connected transmitters per controler channel is 32 (may be less depending on the configuration of the controller), while the total length of the connecting cable (electrical distance between the controller and the last transmitter) should not exceed 1200 meters. The maximal amount of transmitters connected to the bus and the type of cable used, according to the distance from the controller, is provided in the manuals of each transmitter.
According to the RS485 specifications, the last device on the bus must be ending with a terminating resistor 120R. Plug a jumper on the JP2 connector of the last device on the bus to include the 120R terminating resistor. In the default configuaration the jumper connector is not plugged -
Connecting the temperature sensor, flooding sensor and lay-off button of the beeper
-
Connecting the visual and acoustic alarms and the emergency valve
-
Selecting the supply voltage and the maximum current load
Supply voltage 230V AC
The highest current load of the controller is 1,4A. This current serves to
power the connected transmitters and the visual and acoustic alarms, which are
connected to the terminal blocks „LIGHT_SIG“ and „SOUND_SIG“.
Example: There are 4 transmitters connected to the controller with a
consuption of 60 mA each. The remaining 1,16 A (I=1400-4×60) are used to
supply the visual and acoustic alarms.
Supply voltage 24V DC
The consuption of the controler’s electronics is 300mA. Maximal current on
terminal blocks „+24V IN/OUT“ is 10A. Maximal current load on each output on
terminal blocks „LIGHT_SIG“ and „SOUND_SIG“ is 4A.
Example: There are 4 transmitters connected to the controller with a
consuption of 60 mA each. The controller has a consuption of 300mA. The
remaining 7,46 A (I=8000-300-4×60) are used to supply the visual and acoustic
alarms.
Information on the constuption of each transmitters and components of the
visual and acoustic alarms is given in the respective manuals.
Warning: never connect the supply voltage 24V and 230V simultaneously
Output relay
Each relay can by default be configured to activate on any number and any combination of events:
- Transmitter: 4 levels of gas leek alarms, PEL, STEL, transmitters malfunction
- Controller: 2 levels of temperature, flooding, controller malfunction, 2 levels of exceeded temperature, flooding indication
- Relays can after activations be configured for the following output functions: normally closed, normally open, cycling of open/close, automatic deativation of deactivatable outputs after a certain time or after pressing a button.
- Specific configurations of the relays are given in the configuration protocol provided to the controller
Regulating the supply voltage
- By means of trimru we can regulate the output voltage of the source in the range of 22-26V.
- If the sensors are connected at a great distance, it may be necessary to increase the supply voltage for proper function.
Controls
The control panel is equipped with a segmented LCD display and can be
controlled using the LEFT, RIGHT and ENTER buttons.
In Basic mode the controller displays the concentration and the states of the
configured channels. Digital channels (transmitters connected via RS485) are
numbered 1 to 32, and analog channels (connected via current loop) are in the
range of 41 to 48. The controller sequentially switches between the configured
channels (basic interval 3s). For a longer display of a specific channel,
briefly press ENTER (the channel remains displayed for 30s). The ENTER button
also serves as a confirmation key for switching-off of the off-switchable
outputs of the controller. The respective output remains in the defaul state
for as long as there is no fading of the event that triggered it
(concentration drop, disappearance of the error code).
Panel
- LCD display
- Indication of proper operation of the controller
- Gas leek
- LEFT button (move through menus, switch between transmitters)
- RIGHT button (move through menus, switch between transmitter)
- ENTER button (unblocking of the acoustic alarms and thelatch function, confirm)
LCD display
-
Time
-
Date
-
Secondary display
-
Warning: calibration required
-
RS485 address of the current transmitter
-
„Channel“ of the current transmitter
-
Interrupted RS485 bus indication
-
Transmitter calibration via RS485
-
Marker (selecting a transmitter in the menu)
-
Malfunction of the controller or a connected transmitter
-
Exceeding the critical temperature level
-
Indication of an alarm record in the history
-
Flooding indication
-
Exceeding the time-weigted avarage
-
Alarm PEL – long-term exposure limit
Alarm STEL – short-term exposure limit -
Gas leek alarm
-
Type of detected gas / substance
-
Measured units
-
Main segments of the display, currently measured concentration
Launch of the controller
After turning on the power supply, the whole LCD Display lights up and loads
the highest meassured concentration, which remains on the display for cca 3s.
After that the controller goes into preheating mode. The main LCD displays a
countdown to the end of preheating and the secondary segments display the
inscription „HEATING“.
Basic status/alarms
The controller displays the concentration on 4 main segments. To it’s right,
units and the detected gas are being displayed. The 8 auxiliary segments
display the location or an evnetual sensor malfunction. If the displayed
channel is digital
(1 to 32), the adress of the connected sensor is also displayed. Connected
analog transmitters have a range of 41 to 48. The controller sequentially
switches the configured channels in a 3s interval. If we want to select a
transmitter manually, we can do so with the buttons LEFT and RIGHT.
The status of the sensor bundled with an output relais (alarms, time-weigted
avarages, statuses of temperature sensors and floodings, malfunctions) is
displayed in the right part of the LCD.
In case of an increased concentration, the LED ALARM starts shining and the
controller switches to the channel, which meansured this concentration. After
30s the channels will again be sequentially switched.
The latch function – catalytic and semiconducter sensors can, when exceeding
the measuring range, indicate a lower measured value than it really is. If the
measured concentration of these sensors exceed 100% of the lower explosion
level, the latch will activate. Even after a drop of the measured
concentration, the transmitter will still be in it’s highest alarm level. The
detection area must be physically checked by an independent transmitter and
after that the controller can be unblocked by pressing the ENTER button.
The ENTER button also serves as a confirmation button for the acoustic alarm.
Malfunction
If a malfunction should occur, the LCD displays the measured values, an error
code and also a key symbol . The meaning of individual error codes can be
found in the attachments.
Monitoring the calibraton periods
After 12 months since the last calibration (Max. calibration interval) an
inscription starts flashing on the LCD display. The connected transmitters
must be calibrated immediately.
Reading the record of measured concentrations and alarms
The controller periodically after 60s stores the current detected
concentration into it’s internal memory. The internal memory retains data from
the last 49 000 measurements (cca 34 days). In order to read this information,
the program DegaConfig is required. Refer to the DegaConfig program
instruction
Indication of past alarms
The controller is equipped with an indication of alarms that have already
faded. If such an alarm occurred, the icon is displayed. To view these alarms,
enter the menu HIST HILA, where the date and time since the highest measured
alarm since reseting HIST _RST is displayed for each transmitter. After
viewing the history it’s possible to reset the counter throught HIST _RST and
the icon disappears.
Automatic adjustment of the 0 point
The connected digital transmitters have an inner diagnostic, which detects
whether or not the 0 point is in disbalance. If so, an automatic adjustment
will take place and the controller indicates this with the icon .
Menu
Enter the menu by pressing the ENTER button and hold it for cca 5s. The main
segments of the LCD display the menu functions. Use the arrows to move from
one entry to another and press ENTER for selecting an entry. The last entry is
always EXIT, which returns you to a higher menu level. The menu stucture is as
follows:
History Menu HIST
HI1 | Displays the alarm history for the last hour |
---|---|
HI8 | Displays the alarm history for the last 8 hours |
HI12 | Displays the alarm history for the last 12 hours |
HI24 | Displays the alarm history for the last 24 hours |
HI2D | Displays the alarm history for the last 2 days |
HI7D | Displays the alarm history for the last week |
HIAL | Displays the alarm history for the entire memory (cca 34 days) |
HILA | Displays the alarm history since the last reset of the entry _RST |
_RST | Resets the time from which „HILA“ starts counting |
EXIT | Returns to a higher menu level |
This menu displays the highest measured concentrations in a selected time
interval for each channel. There is a total of 8 intervals: – the last 1h
(HI1H), 8h (HI8H), 12h (HI12H), 24h (HI24), 2 days (HI2D), 7 days, the entire
memory (cca 34 days) and the interval since the last reset of „_RST“.
Selecting an entry will perform a custom search in the memory for the selected
channel. If during the whole interval the concentration hasn’t changed and
remained on the minimal value, „9999“ will be displayed instead of the date
and time. Switch between the channel by using the arrows and use ENTER to
return back to selecting a time interval.
The entry _RST serves for setting the time interval for the user alarm. If
since the last change of the entry _RST an alarm occurred at one of the
transmitters, the basic status of the controller displays the segment „H“. At
the entry, the date and time since evaluation of „HILA“ is displayed. Pressing
ENTER on this entry sets the interval to the current date and time a the
segment H disappears from the basic status. Press ENTER again to return the
the history menu.
Note.: In case of equipping a larger quantity of transmitters, the
loading of the history may take a few seconds.
Information menu INFO
NCAL | Displays the date of the next transmitter calibration |
---|---|
LCAL | Displays the date of the calibration |
TEMP | Displays the temperature of the DEGA Tc II sensor |
ADDR | Displays the controller address on the RS485 HOST bus |
EXIT | Returns to a higher menu level |
The entries TMP1 and TMP2 change the temperature value of the external sensor
at which an alarm occurs. Pressing LEFT decreases the temperature and pressing
RIGHT increases the temperature. Press ENTER to confirm the change. Attention,
the temperature alarm value changes immediately after pressing LEFT or RIGHT.
If the immediate temperature value exceeds the alarm value, it will change the
output state.
The entries ALM1 to ALM4 are used to set the alarm of the transmitters. Press
ENTER to browse the alarms by using LEFT and RIGHT. Each channel shows the
size of the alarm and the segment 1-4 shines, based on the selected alarm.
Press ENTER again to move to the edit mode. The segment 1-4 blinks and we can
set the value by using LEFT and RIGHT. Pressing ENTER again will end the edit
mode. Attention, analog channel value changes are immediate and so are the
output changes. The changes are saved after pressing ENTER.
The entry CALI serves for calibration of the digital transmitters. LEFT and
RIGHT changes the displayed channel and ENTER selects the channel (displayed
). Moving to the entry NEXT and pressing ENTER goes to zero-calibration of the
selected transmitters. This mode displays a minimal AD conversion value on the
main segment. The secondary segments display the maximal value. The oxygen
detector is an exception, which always detects a 0 value in the zero-mode. By
using LEFT and RIGHT it’s possible to check the detected value of every
selected transmitter and eventually wait for it to drop. Press NEXT to move to
the calibration range mode. Inletting a calibration gas to the transmitter
will start a concentration measuring of the calibration gas. The highest value
of the AD conversion is displayed on the main display and the lowest value is
displayed on the secondary segments. If we are satisfied with the values, we
can move on to the next part by clicking NEXT, which will bring us to the
settings of the calibration interval. This can be changed with LEFT and RIGHT
and using ENTER will confirm the selection. In the final part of this whole
process select either YES for saving the values into the transmitters, or no
for finishing the calibration without saving the values.
Controller testing menu TEST
TMP1 | Setting the critical temperature level 1 |
---|---|
TMP2 | Setting the critical temperature level 2 |
ALM1 | Setting the 1. level of gas leek alarm |
ALM2 | Setting the 2. level of gas leek alarm |
ALM3 | Setting the 3. level of gas leek alarm |
ALM4 | Setting the 4. level of gas leek alarm |
CALI | Calibration of the digital transmitters |
EXIT | Returns to a higher menu level |
The entry RELE is used for direct setting of the controller outputs. Entering
this entry saves the current state of the outputs, which are later modified by
the user. The controller outputs (RE1 to RE10, LIGH, SOUN, _HV) can be browsed
with LEFT and RIGHT and pressing ENTER will switch the output state. The
outputs will remain in these settings for as long until we don’t press ENTER
on the last EXIT entry. That will restore the output state, which existed
before the user change.
The entry TRAN is similar to the entry RELE, except for the fact that the user
sets the concentrations on the given channel. Use LEFT and RIGHT to select a
channel and then press ENTER to enter the edit mode. Here we can use the
arrows to change the concentration ranging from minimal to maximal value of
the configured transmitter. The controller reacts to this set concentration as
if it was directly measured, which leads to occurring alarms and switching
outputs.
The entry _RST resets the controller.
Service Menu SERV
The entry SERV ALL SENS makes the controler go into service mode. The
communication with transmitter is stopped and the outputs are set in the last
known state. Use LEFT and RIGHT to set the servise interval in a range of 1 to
24 hours. Press ENTER to start it’s own regime.
The main segments display a countdown of the set interval in seconds and the
malfunction segments (key symbol) blinks. After the countdown finishes, the
controller returns to the detection mode. This regime can be interrupted
anytime by pressing ENTER.
The entry SERV SEL SENS causes a blockage of any transmitter until the next
restart of the controller. Use LEFT and RIGHT to select a transmitter and
ENTER to block/unblock. Blocked transmitters are indicated with an inscription
DIS on the main segments.
Maintenance
Operation/Maintenance
In case of contamination the surface can be cleaned with a slightly moistened
cloth. The connected transmitters require performing of regular checks and
calibrations, which can be done in two ways:
- a) 1x every six months carry out a „calibration“ and functional control – adjust the sesitivity of the sensor using calibration gas and check the functionality of the system. The exact interval depends on the purity of the environment, required accuracy and the occurrance of disturbing gases in the atmoshpere.
- b) 1x every twelve months carry out a „calibration“ – adjust the sesitivity of the sensor using calibration gas and check the functionality of the system. The exact interval depends on the purity of the environment, required accuracy and the occurrance of disturbing gases in the atmoshpere. Also carry out a „functional control” 1 x every three months – checking the function of the entire detection system using a test gas, which does not exceed the range of the sensor. We recommend using gas intended for laboratory use.
For the „functional control“ do not use means for testing fire alarm detectors!
Perform calibration only at certified service centers with a valid certificate of competence or the manufacturer. For the Czech Republic only DEGA CZ s.r.o.
Replacement of the battery
The battery lifetime in the controller is approximately 5 years. After this time some functions of the controller may not work properly. Remove the battery from the holder and replace it with one of the recommended types. Replacing the battery in the controller, which is not connected to the power supply, will erase the internal clock.
Attachments
Table of error codes
Occurs on digital channels
(1 to 32)
| Occurs on analog channels
(41 to 48)
| Displayed on the secondary segments| ****
Cause
| ****
Solution
---|---|---|---|---
| ****
X
| ****
„SENSOR E“
| ****
Interrupted current loop or faulty transmitter
| Check the transmitter connection, otherwise contact the
manufacturer
X
| | ****
„ NO SENS“
| Sensor is not present (EEPROM is not communicating)| Disconnect and reconnect the sensor, then restart the sensor by disconnecting and
reconnecting the power
X| | „UNK SENS“| Unknows sensor type| Contact the
manufacturer
X
| | ****
„ELCHEM E“
| Type 2 senesor type ID not found in the table
setting LMP91000
| Contact the manufacturer – FW
update required
X| | „SENS CRC“| CRC does not match the
sensor EEPROM
| Sensor error – contact
the manufacturer
X| | „LMP9 ERR“| LMP91000 does not
respond
| Sensor error – contact
the manufacturer
X
| | ****
„SEN MISM“
| The set sensor ID does not match with the
connected sensor
| Checking the configuration of the
sensor required
X
| | ****
„ELFAILED“
| EL sensor test error| Sensor error, only informative, subsides by
itself
X
| ****
X
| ****
„ HEATING“
| Transmitter is in preheating mode| Wait a few minutes, the transmitter will
automatically enter measurement mode
X
| | ****
„EE25 ERR“
| Error reading the internal FLASH| Restart the transmitter. If the error persists, contact the
manufacturer
X
| | ****
„FLASHCRC“
| Error reading the internal FLASH| Restart the transmitter. If the error persists, contact the
manufacturer
X
| | ****
„EEPR CRC“
| Error reading the internal FLASH| Restart the transmitter. If the error persists, contact the
manufacturer
X| | „INFRA ER“| Infrared sensor error| Replace the sensor
X
| | ****
„ CALIB18“
| The device exceeded the maximum calibration
interval by 50%
| Calibration is necceserry
X
| | ****
„COMM ERR“
| The transmitter doesnt respond| Check the connection between the controller
and the transmitter
warranty
General warranty terms and conditions
When following the instructions for installation, operation and maintenance, the manufacturer guarantee 24 months from the date of receipt for the product. Should the product purchased be put into operation by an entity other than the seller, the warranty period commences from the date that the product is put into operation, provided that the buyer ordered its commissioning within three weeks of its receipt. The customer expressly acknowledges that during the warranty period that extends beyond the length of the warranty period that is specified in the Commercial Code (the statutory warranty) s/he can neither require replacement of the product nor may s/he withdraw from the contract.
- When claiming a product defect it is necessary to submit a proof of purchase that contains the following information: name and surname, name and business name, address and the warranty card, if the buyer received one from the seller. The validity of the warranty shall not be affected by non-compliance with the obligations related to the issuance of the warranty card.
- Claims concerning the product (for a warranty repair only complete devices are accepted) may be filed during the warranty period only with the seller from which it was purchased; subsequently the seller is required to forward the product to an authorised service centre or to the manufacturer.
- A condition for the recognition of the rights under the warranty is the installation of the product having been undertaken by an authorised person in possession of a valid certificate from the manufacturer.
- Claims regarding a product defect that can be dealt with reasonably quickly and without additional consequences will be resolved by remedying the defect (repair) or by replacement of the product part , because in such a case it is a contradiction of the standard norms that the entire product shall be replaced (§ 616, paragraph 4 of the Commercial Code).
- The buyer who exercises the right of warranty repair is not entitled to the return of the parts that have been replaced.
- The warranty period can be extended for up to 48 months and its validity can be extended beyond the standard length on the basis of the conclusion of an individual warranty contract. Further information may be obtained through a specific business meeting.
This warranty is not applicable to:
- a product that has not been put into operation by the manufacturer or by a certified employee in possession of a valid certificate issued by the manufacturer
- A product that did not have regulary performed calibrations and functional checks by the manufacturer or by a certified employee is possession of a valid certificate issued by the manufacturer.
- damage caused by fire, water, static electricity, power surges in the electric supply or in the public network, accident, improper use of the product, wear and tear contamination of the product and its subsequent cleaning damage caused by improper installation, any adjustment, modification or improper manner of use inconsistent with the instruction manual, the technical standards or the applicable safety regulations in the Czech Republic
- damage to the product during transportation caused by improper handling or handling of the product in a manner contrary to the advice provided in the instruction manual
- DEGA products that have been used in association with other than original DEGA products, including consumables and accessories bearing additional parts or consumables (e.g. a foil label, seal, etc.), that are detrimental to normal wear and tear during operation, together with wear and tear of the product and its parts caused by their normal use
For the complete version of the general business conditions and of the claims procedure go to www.dega.cz
- Manufacturer: DEGA CZ s.r.o., Malešická 2850/22c, 130 00 Praha 3, Czech republic
- VAT: CZ 279 029 43,
- Telephone +420 774 447 660
- E-mail: info@dega.cz ,
- Web: www.dega.cz
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>