RCO 350-255 BT-5 FLX Medium COM Gen2 Instruction Manual

May 15, 2024
RCO

Power Supply
BT-5 FLX Medium COM Gen2RCO 350-255 BT 5 FLX Medium COM
Gen2-RCO 350-255 BT 5 FLX Medium COM Gen2- qr
codehttps://www.rco.se/file/

Revisions and the edition of this document

The current and most recently published edition of this document is available at www.rco.se.
The validity of this document can not be guaranteed, as new editions are published without prior notice.
User manual in original language: Swedish.
Instructions for use, technical data and translations thereof may contain errors. It is always the responsibility of the installer to install the product in a safe manner.

Installation video

READ THIS FIRST!
Electronics, regardless of enclosure, are intended for use in a controlled indoor environment. Mains voltage should be disconnected during installation.
It is the installer’s responsibility that the system is suitable for its intended use. It is the installer’s responsibility that the system is suitable for its intended use. Only authorized persons should install and maintain the system.
All information subject to change.
Instruction manual in Swedish in original1.

ABOUT GLASS TUBE FUSES ON CERTIFIED DEVICES
There are glass tube fuses on the circuit board’s load outputs, these have a tripping time of approx. 150 ms. In the event that a glass tube fuse trips on ONE load output, the voltage on ALL load outputs drops to 0 V for 150 ms.
The installer is responsible for ensuring that there is an energy buffer of at least 150 ms in systems that the battery backup supplies power to or accepts a power failure of 150 ms.

You can find manuals at:www.rco.se/file

Links to manuals and product sheets
You will find manuals and product sheets at: www.rco.se/file 1
Translations in languages other than Swedish are only indicative and have not been verified. Translation must always be checked against the Swedish original to ensure correct information.

Address and contact details

RCO Security AB
Box 3130
S-169 03 Solna
Sweden
+46 8-546 560 00
info@rco.se
www.rco.se

This installation sheet’s article number:

Component overviews

Component overviewBT FLX Medium COM Gen2

RCO 350-255 BT 5 FLX Medium COM Gen2- Component
overviews

Letter Explanation
A Bracket, reversible for wall mounting or 19 “rack.
B Sabotage contact. If alarm class 3 (SSF) is to be met, the tamper switch

must be on the wall.
C| Cabinet in powder-coated sheet metal.
D| Load card – load is connected here.
E| Power supply.
F| Cable entries.
G| Motherboard.
H| Lockable door.
I| Space for batteries.

Enclosures

Bracket
The supplied brackets can be attached in two ways: When mounting on a wall, the brackets must sit backwards, against the wall. When mounting in a 19″ rack, the bracket must sit at the front of the unit.

RCO 350-255 BT 5 FLX Medium COM Gen2- Bracket

No Explanation
A Console is pushed in from the bottom up.
B Clip clicks in when bracket is pushed in correctly.

Mounting
Use the appropriate screw for mounting on a wall or in a 19″ rack. Screws for mounting on a wall or in a rack are not included.

Optional cards for power supply

Table 1. Optional cards for power supply

Power supply| Optional cards fitted on delivery| Additional cards that can be mounted
---|---|---
BT-5 MEDIUM| –| 1 BT-Fuse 5.
BT-5 FLX Small COM Gen2| –| 1 pc. BT-Fuse 5 or 1 pc. BT-Fuse 10.
BT-10 FLX Small COM Gen2| –| 1 pc. BT-Fuse 5 or 1 pc. BT-Fuse 10.
BT-5 FLX Medium COM Gen2| –| 2 pcs. BT-Fuse 5 or 2 pcs. BT-Fuse 10.
BT-5 FLX Large COM Gen2| 1 pc. BT-Fuse 5.| 1 pc. BT-Fuse 5 or 1 pc. BT-Fuse 10.
BT-10 FLX Large COM Gen2| 1 pc. BT-Fuse 5.| 1 pc. BT-Fuse 5 or 1 pc. BT-Fuse 10.

Batteries – placement and connection

Connect battery fuse/blade fuse

RCO 350-255 BT 5 FLX Medium COM Gen2- blade fuseFigure 1. Fuse holders with blade fuses are connected to + and minus on batteries

Connection of batteries in FLX S, FLX M and FLX L
Battery wiring is mounted on the circuit board upon delivery. Pictures below only show how to connect wiring.

  1. Place the batteries in the cabinet with the battery terminals facing outwards.
  2. Connect the battery cable. Red cable on + and black cable on -.
    • If possible, disconnect mains voltage when replacing the battery.

RCO 350-255 BT 5 FLX Medium COM Gen2- Power Supply

PRO3 motherboard

Motherboard – description

RCO 350-255 BT 5 FLX Medium COM Gen2- PRO3

Table 2. Circuit board overview, explanation

No . On circuit board Explanation
1 J24 Power supply control.
2 J5 1=not prioritized 2=external alarm.
3 JU1 LED.
4 JU7 Not used.
5 J11 Reset jumper, used when changing batteries.
6 JU6 Connection for relay card or communication card or for updating

firmware. Only one card or contact at a time can
fit.
7| J29| Connection to fan.
8| J101| Connection to tamper contact.
9| J17| Connection to tamper switch from battery box.
10| J35| Not used.
11| J14| Alarm input from external battery fuse, from battery box.
12 and 13| J10 and J100| Alarm from external option card.
14| D18, D19| LEDs show the status of communication (RS-485).
15| S3| Dip switch
16| P2:1-4| Load outputs
17| P3:1-3| Communication connection, RS-485.
18| P1:1-3| Connection to the mains.

Fuses

Table 3. Fuses on PRO3 / NEO3

Fuse Type Explanation
F1 T2.5A Mains fuse
F3 T16A Load fuse 1 – (for P2:2)
F4 T16A Battery fuse
F5 T3A-T10A* Load fuse 1+ (for P2: 1)
F7 T3A-T10A* Load fuse 2 + (for P2:3)

*The size of the fuse depends on the battery backup (rated) power outlet (A) .

FUSE REPLACEMENT WARNING (A)
There is a risk of damage if the fuse is changed to a larger one than what the unit is delivered with. The function of the fuse is to protect the connected load and cables against damage and fire. It is not possible to change the fuse to a larger one to increase the  power output.

Connect the mains to the motherboard (PCB)
Connect mains
Pull wiring through the cable entry on the cabinet.
If possible, secure the mains cable with cable ties where possible.
Electrical network cabling shall be kept separate from other cabling to avoid EMC interference.

Connect the mains cable to the terminal before it is put back on the motherboard. Secure F and N with cable ties for electrical safety.

Figure 4. Connect the mains to the motherboard
Table 4. Electrical network connections

Letter Explanation
F Phase
N Neutral
PE Protective earth

ELECTRICAL MAINS CONNECTION 230 V AC ON CIRCUIT BOARD
Check that the marking on the circuit board matches the cable arrangement on the terminal block.

Connect load

MAX CURRENT
The maximum current must not be exceeded. Max current is indicated on nameplate on the device.
If there are one or more connection cards (to increase the number of load outputs), load must be connected there and not on the main board.
Table 5. Load connections

Circuit board number Explanation
P2: 1 Connection for load 1 +
P2: 2 Connection for load 1 –
P2: 3 Connection for load 2 +
P2: 4 Connection for load 2 –

Dip switch 1-8
Dip-Switch has several different configuration modes:

Table 6. Dip switch 1-8

Dip switch In mains operation or in battery operation Comment
1 Address for external communication.
2 Address for external communication
3 Address for external communication
4 Address for external communication
5 Sets alarm for mains failure delay Available from software v1.5
6 Sets alarm for mains failure delay Available from software v 1.5
7 Sets alarm limit for low battery voltage in battery operation. Available

from software v 1.5
8| Turns LED off or on.| Upcoming feature through software update
8 in sequence| Performs battery test| Not available in NEO.

Address setting for external communication (Dip switch 1-4)
Dip-Switch S1: 1-4 sets addressing.
Table 7. Addressing Dip-Switch 1-4

| Dip: 1| Dip: 2| Dip: 3| Dip:4
---|---|---|---|---
Adress 1| ON| OFF| OFF| OFF
Adress 2| OFF| ON| OFF| OFF
Adress 3| ON| ON| OFF| OFF
Adress 4| OFF| OFF| ON| OFF
Adress 5| ON| OFF| ON| OFF
Adress 6| OFF| ON| ON| OFF
Adress 7| ON| ON| ON| OFF
Adress 8| OFF| OFF| OFF| ON
Adress 9| ON| OFF| OFF| ON
Adress 10| OFF| ON| OFF| ON
Adress 11| ON| ON| OFF| ON
Adress 12| OFF| OFF| ON| ON
Adress 13| ON| OFF| ON| ON
Adress 14| OFF| ON| ON| ON
Adress 15| ON| ON| ON| ON

Mains failure delay (dip 5-6)
It is possible to change the time for when the alarm for a power outage should be given. Use the matrix to set the alarm.
Table 8. Mains failure delay

Alarms for mains failure are given after: Dip 5 Dip 6
3 seconds OFF OFF
30 minutes ON OFF
60 minutes OFF ON
240 minutes (4 hours) ON ON

Low battery voltage (dip 7)
Dip: 7 has the same function regardless of whether the unit is in mains or battery operation or whether the tamper switch is held down.

Table 9. Low battery voltage

Alarm for low battery voltage is given when Dip 7
22,8 V* ON
24 V OFF
*25% of battery capacity remains.

LED (dip 8)
LED/battery-test always lights up when the door is open.
Dip-switch 8=ON turns off the LED.
Dip-switch 8=OFF turns on the LED.
Battery test (dip 8)
To do a battery test, dip 8 needs to change position and five seconds need to pass before the test is initiated.

  • If dip 8 in original position is on OFF then switch dip 8 to: ON (wait 5 seconds) and then switch back to OFF.
  • If dip 8 in original position is on ON then switch dip 8 to: OFF (wait 5 seconds) and then switch back to ON.

This activates the battery test after 3-8 seconds. The battery test lasts for about 6 seconds and then the LED flashes yellow quickly. Aged battery alarms may be indicated while the battery test is being performed.
Only reset dip 8 when the test is complete.
Reboot to confirm changes in address, battery and alarm settings to parent system
After the dip-switch has been set for various parameters, the device’s software needs to be restarted. This is for the new settings to be stored and take effect.

IMPORTANT
Rebooting according to this procedure does not interrupt the output voltage.
Restarting the device software is done by jumpering J11 (PRO3)
IMPORTANT
Reboot must be done every time a change is made to the device.
NEO cannot be connected to communication/UC.

Reset after battery replacement -PRO3
After battery replacement, the device needs to measure the capacity of new batteries and clear previously set battery capacity. All alarms are cleared from the units memory, statistics remains and can not be cleared.

  • Insert jumper on J11 and remove jumper on J11

After doing step, the battery capacity is cleared in the units memory and is ready to read the new battery capacity.
This procedure needs to be done each time the batteries are replaced or when connecting a battery box.

NOTE ON TEST OF BATTERIES
At start-up, it takes 72 hours before the system performs battery tests. This is to ensure fully charged batteries and to collect averages / history for at least 72 hours. Thereafter, every four hours, a qualified cell sample of the batteries is performed.
NOTE ON START-UP WITH SHORT-CIRCUITED BATTERIES
Peak current at start-up with short-circuited batteries: Up to 30 A p-p for 200 ms. Always follow the start-up procedure.

Card Description – Relay Card NOVA Series (PRO3)

Relay card – description, connections and alarm outputs.
The card is connected to the 10-pin header (6) on the PRO3 card.

Power Supply

No On circuit board Explanation
IN2 C
1 P5:9 SDA
2 P5:8 SCL
3 P5:7 System minus
4 JU5 Connection to PRO3 card.
X For internal programming. Do not use.

IMPORTANT
Do you use I2 C cards, you cannot use relay cards.

Multiple units into one parent system

To connect several units to a higher system, the load-minus between several battery backups must be connected together.

RCO 350-255 BT 5 FLX Medium COM Gen2- higher system

Bridge of UC-50 Gen2

When installing in environments sensitive to interference, communication interruptions may occur. By bridging to 0 V on the UC-50 Gen2, interference can be avoided.
IMPORTANT
The bridge must be located: i2 C, P6 to DC-IN, P6:12.

RCO 350-255 BT 5 FLX Medium COM Gen2- Bus
communication

Bus communication – connection to UC-50 Gen2
Connection to UC-50 Gen2 is made according to sketch.

RCO 350-255 BT 5 FLX Medium COM Gen2- Connection

No| On PCB in UC-50 Gen2| On PCB in power
supply| Color of cable| Explanation
---|---|---|---|---
1| SDA, P6:42| P5:9| Orange| SDA/DATA.
2| SCL, P6:41| P5:8| Brown| SCL/CLOCK.
3| 2 I C 0V, P6:40| P5:7| Black| V-Ground / minus.
4| –| –| –| Untwisted cable. Maximum three meters.
5| –| –| –| Max distance between power supply and UC-50 Gen2: 3 meters.
6| DC+ IN, P4:14| P2:3| RED| 24 V.
7| DC- IN, P4:14| P2:4| Black| 24 V.

IMPORTANT
Cable length max 3 meters. Cable must not be twisted in pairs.

Commissioning – how to start the unit

  1. Connect batteries
  2. Connect / switch on fuses
  3. connect load, alarm and possibly. other connections.
  4. Screw the mains cable into the terminal block and attach the terminal block to the motherboard.
  5. Switch on mains voltage.

The unit works normally when the indicator LED on the outside of the cabinet door lights up with a solid green light. See front panel for other status indications.
It may take up to 72 hours before the batteries are fully charged.
System test
Test the connected device by performing a system test afterwards commissioning [19].

  • Switch on incoming mains voltage.
  • Indicator LED on the outside of the cabinet door lights up with a solid green light. Disconnect the mains voltage to check that the unit is operating in battery mode and alarms.
  • Indicator LED on the cabinet door flashes, see alarm type panel.
  • Switch on incoming mains voltage. Indicator LED, on the outside of the cabinet door, lights up with a solid green light. Normal operation.

Recovery
Reset the unit by completely de-energizing the unit.
Disconnect battery wiring and mains voltage and reconnect after 5 seconds.
Alarm displayed on cabinet door
In normal mode, the indicator LED shows a solid green light.

RCO 350-255 BT 5 FLX Medium COM Gen2- Connection1

The indicator diode (LED) shows Explanation
Solid green light Normal operation.
Slow green flashes Sabotage alarm.
Fast green flashes Mains failure.
Solid yellow light Low battery voltage.
Slow yellow flashes Aged batteries.
Rapid yellow flashes Disconnected batteries / battery cell shortage.
Solid red light Overvoltage or undervoltage or charger fault.
Slow red flashes Low system voltage.
Rapid red flashes Blown load / battery fuse has blown.
No light / off Deep discharge protection is activated. (System shutdown).

When operating system: If the indicator LED is off, deep discharge protection has come into force.

Adjustment of tamper switch

The tamper switch lever must be in the closed position when the cabinet door is closed. If the alarm goes off (“tamper alarm”), the lever may needs to be adjusted.
The lever is adjusted by the following steps:

  1. Pinch with pliers in the middle of the lever.
  2. Carefully adjust the lever in the desired direction (up / down).
  3. Check by closing the door. A click is heard when the contact is closed.

NOTICE
Tamper switch will not give an alarm when closed and locked the door.

Maintenance

The system with the exception of batteries is maintenance-free when installed in an indoor environment.
About batteries
Batteries generate electricity through a chemical process and there is thus a natural degradation of capacity.
The biggest factor in battery life is temperature. The higher the temperature, the shorter the battery life. The date of manufacture stamped on the battery and the service life (as stated by the battery manufacturer). An ideal temperature is 20 °C both in operation  and in storage. Higher ambient temperature greatly reduces the service life. Thus, actual lifespan varies when used. Batteries should be replaced after half specified (from the battery manufacturer) lifetime for safe operation. Batteries purchased through the manufacturer of the battery backup have a lifespan (from the battery manufacturer) of between 10-12 years with recommended replacement after 5-6 years.

battery change

  • If possible, disconnect mains (voltage) when replacing the battery.
  • Disconnect battery cables. Note how battery cables are mounted before removing them.
  • Remove battery fuse between batteries.
  • Insert and fasten the new batteries.
  • Connect the battery cables in the same way as before.
  • Connect battery fuse between batteries.
  • Switch on mains voltage. The indicator LED may not be green (up to 72 hours), until the batteries are charged.
  • Test the system by briefly disconnecting the mains voltage, (= the load is driven by the batteries), and then switch on the mains voltage again.

Have you changed the size of the battery? Then don’t forget to change the battery capacity, see Battery capacity setting, Dip switch 5-7
Battery recycling
All batteries must be recycled. Return to manufacturer or return to recycling station.

Appendix: Mount I2C board

RCO 350-255 BT 5 FLX Medium COM Gen2- board

The board is pressed into place on the motherboard in the power supply.
The power supply may be commissioned.

Power supply – product sheet

SSF1014 certified battery backup with communication

Name, article number and e-number

Name Article number E-number
BT-5 FLX MEDIUM COM 28160142 52 574 56
BT-5 FLX Medium COM Gen2 28160143 52 57 699

About BT FLX COM Gen2
BT FLX COM Gen2 is mainly used in safety systems where SSF 1014 approved battery backup is required or where the requirements are higher. Requirements such as better flexibility, more alarm functions, longer backup operating times or where the battery  backup needs to handle higher loads.

  • SSF1014, Alarm class 1-3 approved battery backups / power supply.
  • Controlled charging function.
  • Qualified battery capacity test
  • Can be supplemented with several different optional cards.
  • Mounted on a wall or in a 19 ”rack.
  • Flexible battery capacity with battery boxes increases backup operating time.

Flexibility
Power supply BT-5 FLX Small COM Gen 2 and BT-10 FLX Small COM Gen 2 can be expanded with an extra battery box: Battery box 24V FLX S with space for four 14 Ah batteries. Power supply BT-5 FLX Medium COM Gen 2, BT-5 FLX Large COM Gen 2, BT- 10 FLX Large COM Gen 2, BT-15 FLX Large COM Gen 2 and BT-25 FLX Large COM Gen 2 can be extended by 1- 4 extra battery boxes. Power Supply Medium and Power Supply Large can also be expanded with battery shelves in 19” racks. Battery box Battery  box 24V FLX M Has room for two 45 Ah batteries. Battery shelves have room for two 45 Ah batteries (Medium) and two 150 Ah batteries (Large) on each battery shelf. Adapter required.
Fixed installation
The product is intended for fixed installation. The battery backup must be installed by a qualified installer.
Area of use
BT FLX COM Gen2 mostly used for: Access control system, burglar alarms, (integrated security systems), in public environments such as schools, offices and commercial properties.

The unit meets the requirements for installation in systems that must be SSF 1014 approved. SSF 1014 certificate is only valid for certification together with a higher-level system.

IMPORTANT
In order for the SSF 1014 certificate to be valid, only one (1) load output may be used.

Regulations and certifications

Standards that product (s) meet and are approved for
Table 10. SBF
SBF 110:8
Table 11. SSF
SSF1014 Alarm class 1-4 (burglar alarm).
Table 12. Certificate and certificate number

Certificate number, SBSC Designation SBSC
No. 18-246 NOVA 27 250-FLX, NOVA 27 150-FLX, NOVA 27 100-FLX, NOVA 27 50-FLX,

NOVA 13 100-FLX, NOVA 27 100-XS2, NOVA 27 50-XS2, NOVA 27 30-XS2, NOVA 13 100-XS2, NOVA 13 50-XS2

Requirements that the product meets

EMC: EMC Directive 2014 / 30EU
Electricity: Low voltage directive: 2014/35 / EU
CE: CE directive according to: 765/2008
Emission EN55032 (CISPR32) Class B

Circuit boards – Technical data

Technical data, motherboard: PRO 3

Info Explanation
Short name: PRO 3
Product description Motherboard in battery backup with advanced functions and

communication to parent system.
Own consumption, with relay card| Less than 100 mA. All relays retracted on external alarm card in normal mode.

Alarm
Alarm displayed on indicator LED on the front of the cabinet.

  • Cell fault in battery or unconnected battery.
  • Charger fault, undervoltage.
  • Charger fault, overvoltage.
  • Low system voltage, system voltage below 24.0 V in mains operation.
  • Low battery voltage, below 24.0 V DC in case of mains failure.
  • Power failure alarm.
  • Sabotage switch.
  • Fuse fault.
  • Aged battery

Expanding alarm functions are available via communication or with alarm cards.

Table 13. Fuses

Fuses Type
5:00 AM T5A
Mains fuse for 24 V units up to 15 A T2.5AH250V. Ceramic.

Table 14. Protection

Info Explanation
Deep discharge protection (Yes / No) Yes. 12 V units protection at 10V, +/-

0.5 V. 24 V units protection at 20, +/- 0.5 V.
Surge protection (Yes / No)| Yes
Overtemperature protection (Yes / No)| Yes
Short circuit protected = (Yes / No)| Yes

Technical data, PRO3 I2C board

Info Explanation
Card name: PRO3 I2C board
Version: 1.6
Product description Card that makes it possible to communicate with UC via

i2C.
Recommended environment| Indoors, class 1. Ambient temperature: + 5 ° C – 40 ° C.
Protection class| IPX0
Recommended installation| Battery backup with PRO3 motherboard.
Input voltage| 27,3 VDC
Self-consumption| 10 mA
Alarm via| I2 C
Number of alarm outputs| 4 pcs

Table 15. Alarm overview

Alarm overview in alphabetical order| Communication (P5: 1-9)| Indicator LED on main card and LED on door.
---|---|---
Network outages| X| X
Fuse fault| X| X
Sabotage switch| X| X
Fan fault| X| –
Charger fault, overvoltage| X| X
Charger fault, undervoltage| X| X
Cell fault or unconnected battery| X| X
Low system voltage. | X| X
Low battery voltage (<24.0 V DC) or power failure| X| X
Overtemperature| X| –
Undertemperature| X| –
Undertemperature| X| –
Short battery life left| X| –
Aged battery| X
| X **
Overcurrent 80%, daily average| X| –
Overcurrent 100%, minute average| X| –
Overcurrent 175%, second average| X| –

Power supply

Power supply – Technical Data LRS-150-24
In:
BT-5 FLX MEDIUM COM Gen 2

Info Explanation
Output voltage 27.3 V
Output current: 0 A – 6.5 A
Output voltage, ripple 200 mVp-p
Overvoltage 28.8 V – 33.6 V
Voltage recharge, ripple / current limitation Less than 0.6 Vp-p
Efficiency 89%
Current limitation 110% – 140%
Constant voltage +/- 0.5%
Regulatory accuracy + / – 1.0%
Input current (230 V) 1,7 A
Mains voltage frequency 47 Hz- 63 Hz
Mains voltage 230 V AC – 240 V AC
Brand effect 156 W
Temperature range -30°C – +70°C
Humidity range 20% – 90% RH non-condensed

The power supply is adapted and calibrated with the battery / hardware of the battery backup. Only power and calibrated power supplies may be used. Contact support when changing power supplies. Use of power supplies coming from another source may cause damage not covered by the warranty. Warranty is canceled if power supplies (from a source other than support / designated by support) that are not correctly calibrated are used.

Technical data enclosures

Enclosures – Technical Data FLX M

Info Explanation
Name FLX M
Enclosure class IP 32
Measure Height: 224 mm, width 438 mm, depth 212 mm
Height units 5 HE
Mounting Wall or 19 “rack
Ambient temperature + 5 ° C – + 40 ° C. For best battery life: + 15 ° C to +

25 ° C.
Environment| Environmental class 1, indoors. 20% ~ 90% relative humidity
Material| Powder coated sheet
Color| Black
Cable entries, number| 4
Batteries that fit| 2 pieces 12 V, 20 Ah.
2 pcs 12 V, 45 Ah.

Warranty, support, country of manufacture and country of origin

Warranty 5 years
The product has a five-year warranty, from the date of purchase (unless otherwise agreed). Free support during the warranty period is reached at support@milleteknik.se or telephone, +46 31-34 00 230. Compensation for travel and or working hours in  connection with the location of faults, installation of repaired or replaced goods is not included in the warranty. Contact Milleteknik for more information.
Milleteknik provides support during the product’s lifetime, however, no later than 10 years after the date of purchase.
Switching to an equivalent product may occur if Milleteknik deems that repair is not possible. Support may be added (at Millteknik’s desrection) after the warranty period has expired.
Support
Do you need help with installation or connections? Our support phone is available: Monday-Thursday 08:
00-16: 00 and Fridays 08: 00-15: 00. Telephone support is closed between 11: 30-13: 15.
You will find answers to many questions at: www.milleteknik.se/support
Phone: +46 31-340 02 30
Support is open: Monday-Thursday 08:00-16:00, Fridays 08:00-15:00. Closed 11:30-13:15.
Spare parts
Contacted support for questions about spare parts.
Support after the warranty period
Milleteknik provides support during the life of the product, but no longer than 10 years after the date of purchase. Replacement for an equivalent product may occur if the manufacturer deems that repair is not possible. Costs for support and replacement are  added after the warranty period has expired.
Country of manufacture
Country of manufacture / country of origin is Sweden. For more information, contact your seller.
Designed and produced by: Milleteknik AB
Designed and produced by Milleteknik AB
Batteries – recommended, not included
Batteries are not included they are sold separately
Batteries are sold separately.
20 Ah, 12 V AGM battery

Fits in Number of batteries
BT-5 FLX Medium COM Gen 2 2
Ba ttery type V
--- ---
Maintenance-free AGM, lead-acid battery. 12 V

*Table 16. 10+ Design life battery
* Design life is the shelf life in years for an unused battery. Environmental factors such as heat and load affect the service life. Batteries that have a durability (+10 Design Life) of 10+ years usually need to be replaced after 5-6 years.
Connection of battery box
Mounting battery box with battery backup
The battery box is pushed in during the battery backup, (or previous battery box). The battery box is then screwed to a rack or wall. The two enclosures must meet each other without gap.

RCO 350-255 BT 5 FLX Medium COM Gen2- certified battery
backup1

Nr Explanation
1 Track in battery backup.
2 Protruding part on the roof of the battery box.

Installation of battery box, what to do in battery backup
Cable gland / knock-out is located on the underside of the battery backup and must be disconnected before mounting.
The unit must be de-energized during installation and connection.

  • Use the wiring that comes with the battery box to meet the wiring from the battery backup. See picture.
    The picture shows cable wiring from the battery backup that meets cables from the battery box

Connection to batterybox

RCO 350-255 BT 5 FLX Medium COM Gen2- Connection to
batterybox

The picture also gives an overview of connection points for battery cables and battery fuses.

Battery cables Explanation
B1+ Connects to fuse .
B1- Cable from motherboard is connected to battery .
B2+ Cable from motherboard is connected to battery .
B2- Connects to fuse .
B3+ Connects to fuse .
B3- Connected via connector to battery in battery backup .
B4+ Connected via connector to battery in battery backup .
B4- Connects to fuse .

Table 17. Connection

Number Explanation
1 Battery fuse.
2 Connect battery backup and battery box with white square connector.

Address and contact details

RCO Security AB
Box 3130
S-169 03 Solna
Sweden
+46 8-546 560 00
info@rco.se
www.rco.se
This installation sheet’s article number:

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals