**JB DV-285DC Professional Grade Vacuum Pump Instruction Manual
**
INSTALLATION INSTRUCTION
WARNING: UNIT DRAINED OF OIL FOR SHIPMENT. DO NOT OPERATE WITHOUT ADDING OIL.
| DV- 240DC| DV- 285DC
---|---|---
CFM| 8.4 CFM| 10 CFM
MOTOR| 1/2 HP DC Motor| 1/2 HP DC Motor
VOLTAGE| 115v/230v| 115v/230v
INTAKE PORT| 1/2″ x 1/4″ x 3/8″| 1/2″ x 1/4″ x 3/8″
OIL CAPACITY| 32oz (946cc)| 32oz (946cc)
IMPORTANT
WARNING: UNIT DRAINED OF OIL FOR SHIPMENT. DO NOT OPERATE WITHOUT ADDING OIL.
INTRODUCTION
Each PLATINUM® vacuum pump has been factory tested to guarantee 15 microns (25,4000 Microns = 1 Inch of Hg) or better, and listed CFM performance. The serial number has been recorded. Complete and mail the enclosed Warranty Registration Card or register online at www.jbind.com within 10 days of purchase to validate your warranty.
NOTE: PLATINUM® pumps are not to be used on Ammonia or Lithium Bromide
(salt water) systems. Pump maintenance is the responsibility of the owner.
MOTOR SPECIFICATIONS
Pump and oil must be above 30°F. Line voltage must be equal to motor
nameplate ±10%. Normal operating temperature is approximately 160°F, which is
hot to the touch. Line voltage and ambient conditions can slightly affect
this. Motor has automatic resetting thermal overload protection.
The PLATINUM® is designed for continuous duty and will run for extended periods without overheating.
OPERATION
The following procedures will prevent oil from being drawn into the pump
cartridge and creating hard start-up. Start-up: Close both sides of manifold
and make connection to vacuum pump or auxiliary blank-off equipment. Open one
intake port and isolation valve, close gas ballast valve and start pump. Make
vacuum connections (Figure 1).
Crack gas ballast valve for the first part of the evacuation procedure. After
pump quiets down from initial volume of air, close valve and continue
evacuating. Failure to close valve will result in poor pump performance.
Shutdown: Close isolation valve and open gas ballast valve all the way.
Continue running pump for 2-3 seconds. With gas ballast valve still opened,
stop pump and then close valve. Remove hose connections and cap intakes
**(Figure 1).
**
Isolation (Blank-Off) valve: Quarter-turn on/off. No additional valve needed to isolate system. When checking pressure rise, slowly turn handle counter- clockwise. Pause at 45°. Valve is completely closed at 90°.
PUMP MAINTENANCE
In order to make the best use of your investment, familiarize yourself with the features and operating instructions before starting pump. With routine care and following proper maintenance guidelines, your PLATINUM® will give you years of reliable service. PLATINUM® pumps are designed for deep vacuum work in air conditioning and refrigeration systems.
Adding Oil
Step 1: Remove cap (DV-240DC) or filter (DV-285DC) from pump. One-shot,
full quart oil fill brings oil to top of the oil level line. (Figure 2)
Step 2: Replace filter.
If oil level is too low, you will hear air out of the exhaust. If oil level is
too high, excess oil will be blown out of the exhaust.
IMPORTANT: Use oil specifically refined for deep vacuum pumps. Using oil
not
refined for deep vacuum pumps and/or operating with contaminated oil will void
warranty .
Pump oil should be changed after each use. If system is heavily contaminated,
oil may have to be changed several times during evacuation. After initial fill
up, it is best to check oil level with pump running. After evacuation, oil
contains rust forming water and corrosive acids. Drain immediately while pump
is warm.
Changing Oil
To reach deep vacuum, PLATINUM® pumps need clean, moisture-free oil throughout
evacuation. Care should be taken to avoid contact on skin and clothing when
changing oil. Used oil should be disposed of in the DV-T1 TANK Oil Caddy after
every evacuation while the pump is warm and the oil is thin.
Step 1 : Place the TANK on a level surface. Unscrew black plug in drain base to open.
Step 2 : Place vacuum pump in the cradle and drain pump.
Step 3: When pump has finished draining, replace black plug. The TANK can hold up to five oil changes.
Step 4: Close oil drain valve on pump. Remove oil fill plug and fill to top of oil level line with BLACK GOLD Pump Oil (Figure 2). Replace oil fill plug.
Flushing Oil
Step 1 : Always drain pump before flushing. If the oil is badly
contaminated, flushing may be necessary.
Step 2: While oil drain is open slowly pour 1/3 to 1/2 cup of BLACK GOLD
Pump Oil into the intake connection while pump is running.
Step 3: Repeat as required until contamination is removed from oil
reservoir, pump rotors, vanes and housing.
Step 4: Dispose of all oil used in flushing of pump.
WARNING : DO NOT START PUMP BEFORE ADDING OIL
Black Gold Pump Oil Acts as a coolant, lubricant
Black Gold Pump Oil
Acts as a coolant, lubricant and sealant—simultaneously
DV-T1 Tank Pump Oil Caddy
- Change oil between jobs
- No more mess and spills
- Easy, convenient, and portable
- Capacity for five oil changes
FEATURES
PLATINUM PRO REPAIR PARTS DV-240DC and DV-285DC
Repair parts can be ordered from your local JB wholesaler. When ordering please provide the following information:
- Model number
- Serial number
- Part number and description
REF.NO.| PART NO.| PLATINUM ® PRO **REPAIR
****PARTS DESCRIPTION
---|---|---
1| PR- 801| Sight glass with o-ring
2| PR- 805| Light and button
3| PR- 806| Light cover screw
4| PR- 807| Oil drain repair kit
5| PR- 811| Cover seal
6| PR- 211| Trap o-ring, gas ballast
7| PR- 3| Shaft seal
8| PR- 315| Trap o-ring, intake
9| PR- 78| Angled intake tee with caps
10| NFT5- 4| 1/4″ O-ring, cap
11| NFT5- 6| 3/8″ O-ring, cap
12| NFT5- 8| 1/2″ O-ring, cap
REF.NO.| PART NO.| PLATINUM ® PRO ****REPAIR
****PARTS DESCRIPTION
---|---|---
13| PR- 209| Plastic isolation valve handle and screw w/stem,
o-rings and retainer
14| PR- 208| Flexible coupler
15| PR- 840| Splash guard with piercing valve
16| PR- 307| Oil mist filter (DV-285DC)
17| PR- 607| Motor
18| PR- 7| Gas ballast valve w/o-ring
19| P90009| O-ring, gas ballast valve
20| PR- 75| Cushioned handle w/lift ring 1/2″ NPT
21| PR- 501| Cushion and cap 1/2″ NPT
22| PR- 4| Rubber feet assembly
23| PR- 862| Pump base with feet
24| PR- 822**| Oil fill cap for (DV-240DC)
TROUBLESHOOTING
SYMPTOM | POSSIBLE CAUSE(S) | CORRECTIVE ACTION |
---|---|---|
Pump hard to start | A. Power cord not plugged in securelyB. |
Motor switch not onC. Pump temperature below 30°FD. Pump has not been shut
down properly| A. Plug power cord in securelyB. Turn motor switch to ON
positionC. Warm up pump to 30°F and turn motor switch onD. Follow proper
start up and shut down procedures Step 1: Remove 1/4″ cap Step
2: Move blank-off valve to OPEN position Step 3: Turn pump on
Step 4: Run 2 to 3 seconds and close blank-off valve ** PROPER START
UP AND SHUT DOWN PROCEDURES : Step 1: Close blank-off valve Step
2: Open gas ballast valve Step 3: Run 2 to 3 seconds Step 4:
Shut pump off Step 5: Close gas ballast valve
Pump won’t pull deep vacuum In order for your pump to pull to a near
perfect vacuum, oil must be clean and moisture-free throughout evacuation.| A.
Contaminated oilB. Oil level too lowC. Air leak in system being evacuatedD.
Pump inlet fittings missing or not tightenedE. Coupler slippingF. Missing or
damaged seals or o-rings| A. Change oilB. Add oilC. Locate and repair
leak(s)D. Clean or replace o-ringE. Tighten coupler set screws to flats of
cartridge and motorF. Replace damaged seals or o-rings
| | Step 1: With isolation valve closed, start pump. Oil level should
be to the top of the oil level line embossed on the front of the pump’s cover.
Just a teaspoon low can affect the ultimate vacuum.
| | Step 2: Flush pump and refill with fresh oil.
| | Step 3: Check all connections to pump and system for damaged or
missing o-rings. If brass adapters are being used, make sure copper gaskets
are in place.
Oil drips from point where shaft enters the
pump housing| Damaged shaft seal| Replace shaft seal
Pump shuts down and will not start| A. Thermal overload may be
openB. Low Battery (DV-142-FLEX or DV-85-FLEX)| A. Step 1:
Disconnect pump from system Step 2: Wait approximately 15 minutes for
motor to cool Step 3: Turn pump on Step 4: If it cycles off
again, return for repair B. Check battery charge; re-charge if necessary
Pump cycles on and off from a completely cold
start and then runs smoothly| A. Oil backed up into cartridge and was being
cleared outB. Pump has not been shutdown properly| Step 1: Remove
1/4″ cap Step 2: Turn pump on
Motor just hums| If pump has been dropped, the armature in motor may be
out of alignment with the motor’s bell housing| Step 1: Set pump on
bench with motor standing up Step 2: Loosen the four motor bolts
Step 3: Shake motor and re-tighten motor bolts Step 4: Start
pumpIf this doesn’t work, the pump most likely will need to be sent in for
repair.
Motor runs, but no suction| A. Flexible coupler is either
broken or loose| Step 1: Set pump on bench with motor standing up
Step 2: Look between motor and pump housing from the bottom to see if
the flexible part of the coupler is split or broken.If the coupler is not
broken, the coupler may be spinning on either the shaft to motor or cartridge.
Step 3:** Replace cartridge. Instructions at
www.jbind.com – Support – User Manuals.
WARRANTY
PLATINUM® PRO pumps are warrantied against defects in materials and workmanship for two years OTC—not changing oil will void warranty.
JB products are guaranteed when used in accordance with our guidelines and
recommendations. Warranty is limited to the repair, replacement, or credit at
invoice price, (our option) of products which in our opinion are defective due
to workmanship and/or materials. In no case will we allow charges for labor,
expense or consequential damage. Repairs performed on items out of warranty
will be invoiced on a nominal basis; contact wholesaler for details. Product
Warranty Registration, Limited Warranty and OTC Warranty are available online
at www.jbind.com.
RETURN FOR REPAIR
In the event your pump requires repair, please contact the JB Wholesaler the
pump was purchased from. JB Wholesalers contact JB Customer Service Department
to obtain a Return Goods Authorization (RGA) number. Ensure that all returned
products are packed to avoid any damage in shipment. Paperwork should be
placed in a separate plastic bag and should include
JB’s assigned RGA number, a description of the problem and any customer
assigned repair or purchase order number, if applicable.
Contact Customer Service for RGA number:
800.323.0811 Toll-free phone, 800.552.5593 Toll-free fax
Customers in Alaska, Arizona, California, Idaho, Montana, Nevada, Oregon,
Utah, and
Washington have the option of sending vacuum pump repairs to JB or Merced.
JB Industries
RGA#
601 N. Farnsworth Ave.
Aurora, IL 60505
Merced AC Equipment Service
RGA#
805 S. Fremont
Alhambra, CA 91803
Documents / Resources
| JB
DV-285DC Professional Grade Vacuum
Pump
[pdf] Instruction Manual
DV-285DC Professional Grade Vacuum Pump, DV-285DC, Professional Grade Vacuum
Pump, Grade Vacuum Pump, Vacuum Pump, Pump
---|---