MITSUBISHI ELECTRIC A24KA7 Wall Mounted Air Conditioning System Owner’s Manual

June 17, 2024
Mitsubishi Electric

MITSUBISHI ELECTRIC logoMITSUBISHI ELECTRIC A24KA7 Wall Mounted Air
Conditioning System - logo 2PKA-A24KA7 & PUY-A24NHA7
24,000 BTU/H WALL-MOUNTED INDOOR UNIT
24,000 BTU/H COOLING ONLY OUTDOOR

MITSUBISHI ELECTRIC A24KA7 Wall Mounted Air Conditioning
System

A24KA7 Wall Mounted Air Conditioning System

Job Name:————-
System Reference: ————— Date: ———–

Indoor Unit ————- PKA-A24KA7
Outdoor Unit ————- PUY-A24NHA7

INDOOR UNIT FEATURES

  • Sleek, compact design
  • Simple installation
  • Vane setting for air flow direction control
  • Auto fan speed mode
  • Ideal for spaces such as server rooms, daycare centers, classrooms, churches, small offices, and more
  • Multiple control options available:
    ○ kumo cloud® smart device app for remote access
    ○ Third-party interface options
    ○ Wired or wireless controllers

OUTDOOR UNIT FEATURES

  • Variable speed INVERTER-driven compressor
  • Pre-charged with refrigerant volume for piping length up to 70 ft
  • Low ambient cooling down to -40°F providing 100% capacity (with wind baffles)
  • 24-hour continuous operation (cooling mode)
  • High pressure protection
  • Fast restart
  • Superior energy and operational efficiency
  • Seacoast protection
    ○ External Outer Panel: Phosphate coating + Acrylic-Enamel coating
    ○ Fan Motor Support: Epoxy resin coating (at edge face)
    ○ Separator Assembly Valve Bed: Epoxy resin coating (at edge face)
    ○ Blue Fin treatment is an anti-corrosion treatment that is applied to the Heat exchanger coil to protect it against airborne contaminants.
    ○ Heat exchanger coil and base panel rated for 2,000 hours in accordance with ASTM B117 testing
    Seacoast protection standard from 2022 production

SPECIFICATIONS: PKA-A24KA7 & PUY-A24NHA7

Cooling at 95°F1 Maximum Capacity BTU/H 24,000
Rated Capacity BTU/H 24,000
Minimum Capacity BTU/H 10,000
Maximum Power Input W 1,960
Rated Power Input W 1,960
Moisture Removal Pints/h 5.0
Sensible Heat Factor 0.77
Power Factor [208V / 230V] % 95.7 / 95.7
Efficiency SEER SEER2 21.4
EER1 EER21 12.2
ENERGY STAR® Certified No
Electrical Voltage, Phase, Frequency 208/230, 1, 60
Guaranteed Voltage Range V AC 198 – 253
Voltage: Indoor – Outdoor, S1-S2 V AC 208/230
Voltage: Indoor – Outdoor, S2-S3 V DC 24
Short-circuit Current Rating [SCCR] kA 5
Recommended Fuse/Breaker Size (Oudoor) A 25
Recommended Wire Size [Indoor – Outdoor] AWG 14
Power Supply Indoor unit is powered by the outdoor unit
Indoor Unit MCA A 1.0
Fan Motor Full Load Amperage A 0.36
Fan Motor Type DC Motor
Airflow Rate at Cooling, Dry CFM 635–705–775
Airflow Rate at Cooling, Wet CFM 570–635–700
Airflow Rate at Heating, Dry CFM 635–705–775
Sound Pressure Level [Cooling] dB[A] 39–42–45
Sound Pressure Level [Heating] dB[A] 39–42–45
Drain Pipe Size In. [mm] 5/8 [16]
Coating on Heat Exchanger
External Finish Color White Munsell 1.0Y 9.2/0.2
Unit Dimensions W x D x H: In. [mm] 46-1/16 x 11-5/8 x 14-3/8 [1,170 x 295 x

365]
Package Dimensions| W x D x H: In. [mm]| 51 x 14-1/4 x 18-1/2 [1,295 x 362 x 470]
Unit Weight| Lbs. [kg]| 46 [21]
Package Weight| Lbs. [kg]| 53 [24]
Indoor Unit Operating Temperature Range| Cooling Intake Air Temp [Maximum / Minimum]*| °F| 90 DB, 72 WB / 66 DB, 61 WB
Outdoor Unit| MCA| A| 19.0
MOCP| A| 26
Fan Motor Full Load Amperage| A| 0.4
Fan Motor Output| W| 86
Airflow Rate [Cooling / Heating]| CFM| 1940
Refrigerant Control| LEV
Defrost Method| Reverse Cycle
Coating on Heat Exchanger| Blue Fin Coating**
Sound Pressure Level, Cooling1| dB(A)| 47
Compressor Type| INVERTER-driven twin rotary
Compressor Model| SNB172FWHM1
Compressor Rated Load Amps| A| 7
Compressor Locked Rotor Amps| A| 11.0
Compressor Oil [Type // Charge]| oz.| FV50S // 23
External Finish Color| Ivory Munsell 3Y 7.8/1.1
Base Pan Heater| N/A
Unit Dimensions| W x D x H: In. [mm]| 37-13/32 x 13 (+1-3/16) x 37-1/8 [950 x 330 (+30) x 943]
Package Dimensions| W x D x H: In. [mm]| 40-15/16 x 17-11/16 x 40-11/16 [1040 x 450 x 1033]
Unit Weight| Lbs. [kg]| 151 [68]
Package Weight| Lbs. [kg]| 176 [80]
Outdoor Unit Operating Temperature Range| Cooling Air Temp [Maximum / Minimum]
| °F| 115 DB / -40 DB
Refrigerant| Type| R410A
Pre-Charged Refrigerant Amount| Lbs, oz| 7.0, 11.0
Maximum Pre-Charged Piping Length| Ft. [m]| 70.0 [20.0]
Additional Refrigerant Charge Per Additional Piping Length| oz./Ft. [g/m]| 0.3 [22.5]

NOTES:
AHRI Rated Conditions
(Rated data is determined at a fixed compressor speed)
1Cooling (Indoor // Outdoor)
°F 80 DB, 67 WB // 95 DB, 75 WB

*Indoor/Outdoor Unit Operating Temperature Range (Cooling Air Temp [Maximum / Minimum]):

  • Wind baffles required to operate below 23°F DB in cooling mode.
  • Cooling-only system with advanced wind baffle: -40°F – 115°F.
  • Refer to wind baffle documentation for further information.

**Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re- start Temperatures; Heating Thermal Lock-out / Re-start Temperatures):

  • System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures.

***Blue Fin Coating Standard from 2022 production:

  • PU(Y/Z)-A(12/18)NKA7 – Beginning with serial number 12U*****
  • PU(Y/Z)-A(24/30/36/42)NKA7 – Beginning with serial number 1ZU*****
Piping Gas Pipe Size O.D. [Flared] In.[mm] 5/8 [15.88]
Liquid Pipe Size O.D. [Flared] In.[mm] 3/8 [9.52]
Maximum Piping Length Ft. [m] 225 [68]
Maximum Height Difference Ft. [m] 100 [30]
Maximum Number of Bends 15

NOTES:
AHRI Rated Conditions
(Rated data is determined at a fixed compressor speed)
1Cooling (Indoor // Outdoor)
°F 80 DB, 67 WB // 95 DB, 75 WB

*Indoor/Outdoor Unit Operating Temperature Range (Cooling Air Temp [Maximum / Minimum]):

  • Wind baffles required to operate below 23°F DB in cooling mode.
  • Cooling-only system with advanced wind baffle: -40°F – 115°F.
  • Refer to wind baffle documentation for further information.

**Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re- start Temperatures; Heating Thermal Lock-out / Re-start Temperatures):

  • System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures.

***Blue Fin Coating Standard from 2022 production:

  • PU(Y/Z)-A(12/18)NKA7 – Beginning with serial number 12U*****
  • PU(Y/Z)-A(24/30/36/42)NKA7 – Beginning with serial number 1ZU*****

INDOOR UNIT ACCESSORIES: PKA-A24KA7

Control Interface 3-Pin Connector □ PAC-715AD
BACnet® and Modbus® Interface □ PAC-UKPRC001-CN-1
IT Extender □ PAC-WHS01IE-E
kumo station® for kumo cloud® □ TAC-WHS01HC-E
Thermostat Interface □ PAC-US444CN-1
Thermostat Interface □ PAC-US445CN-1
USNAP Adapter □ PAC-WHS01UP-E
Wireless Interface for kumo cloud® □ PAC-USWHS002-WF-2
Remote Sensor Flush Mount Remote Temperature Sensor □ PAC-USSEN002-FM-1
Flush Mount Temperature Sensor □ PAC-USSEN001-FM-1
Remote Temperature Sensor □ PAC-SE41TS-E
Wireless temperature and humitity sensor for kumo cloud® □ PAC-USWHS003-TH-1
Wired Remote Controller Deluxe Wired MA Remote Controller† □ AAR-40MAAU
Simple Ductless Wired Remote Controller □ PAC-SDW01RC-1
Simple MA Remote Controller† □ PAC-YT53CRAU-J
Touch MA Controller† □ PAR-CT01MAU-SB
Wireless Remote Controller kumo touch™ RedLINK™ Wireless Controller □ MHK2
Lockdown bracket for remote controller □ RCMKP1CB
Wireless MA Receiver □ PAR-SR32MA-E
Wireless MA Remote Controller □ PAR-FL32MA-E
Condensate Blue Diamond (Advanced) Mini Condensate Pump w/ Reservoir & Sensor
(208/230V) [recommended] □ X87-721
Blue Diamond (MegaBlue Advanced) Condensate Pump w/ Reservoir & Sensor

X87-835
Drain Pan Level Sensor/Control| □ SS610E
Refco Condensate Pump (100-240 VAC)| □ GOBI-II
Refco Condensate Pump (100-240 VAC) up to 120,000 BTU/H| □ COMBI
Disconnect Switch| (30A/600V/UL) [fits 2” X 4” utility box] – Black| □ TAZ- MS303
Lineset| 10’ x 3/8” x 10’ x 5/8” Lineset (Twin-Tube Insulation)| □ MPLS385812T-10
100’ x 3/8” x 100’ x 5/8” Lineset (Twin-Tube Insulation)| □ MPLS385812T-100
15’ x 3/8” x 15’ x 5/8” Lineset (Twin-Tube Insulation)| □ MPLS385812T-15
30’ x 3/8” x 30’ x 5/8” Lineset (Twin-Tube Insulation)| □ MPLS385812T-30
50’ x 3/8” x 50’ x 5/8” Lineset (Twin-Tube Insulation)| □ MPLS385812T-50
65’ x 3/8” x 65’ x 5/8” Lineset (Twin-Tube Insulation)| □ MPLS385812T-65

OUTDOOR UNIT ACCESSORIES: PUY-A24NHA7

Air Outlet Guide Air Outlet Guide (1 Piece) □ PAC-SG59SG-E
Centralized Drain Pan Centralized Drain Pan □ PAC-SG63DP-E
Drain Pan □ PAC-SG64DP-E
Control/Service Tool Control/Service Tool □ PAC-SK52ST
M- & P-Series Maintenance Tool Cable Set □ M21EC0397
Maintenance Tool Interface □ PAC-USCMS-MN-1
USB/UART Conversion Cable (Required for all laptop connection) □ M21EC1397
Hail Guards Hail Guard □ HG-A6
M-NET Converter M-NET Converter □ PAC-SJ85MA-E
M-NET Converter □ PAC-SJ95MA-E
Mini-Split Wire 14 Gauge, 4 wire MiniSplit Cable—250 ft. roll □ S144-250
14 Gauge, 4 wire MiniSplit Cable—50 ft. roll □ S144-50
16 Gauge, 4 wire MiniSplit Cable—250 ft. roll □ S164-250
16 Gauge, 4 wire MiniSplit Cable—50 ft. roll □ S164-50
Mounting Pad Condensing Unit Mounting Pad: 24” x 42” x 3” □ ULTRILITE2
Stand 18” Single Fan Stand □ QSMS1801M
24” Single Fan Stand □ QSMS2401M
Condenser Wall Bracket □ QSWB2000M-1
Condenser Wall Bracket – Stainless Steel Finish □ QSWBSS
Outdoor Unit Stand — 12” High □ QSMS1201M
Wind Baffle Front Wind Baffle □ WB-PA5
Rear Wind Baffle □ WB-RE5
Side Advanced Wind Baffle □ WB-SD5

INDOOR UNIT DIMENSIONS: PKA-A24KA7

MITSUBISHI ELECTRIC A24KA7 Wall Mounted Air Conditioning System - INDOOR
UNIT DIMENSIONS

OUTDOOR UNIT DIMENSIONS: PUY-A24NHA7

  1. FREE SPACE (Around the unit)
    The diagram below shows a basic example.
    Explantion of particular details are given in the installation manuals etc.

  2. SERVICE SPACE
    Dimensions of space needed for service access are shown in the below diagram.
    Dimensions of space needed for service access are shown in the below diagram.

  3. OUNDATION BOLTS
    Please secure the unit firmly with 4 foundation (M10<W3/8>) bolts. (Bolts and washers must be purchased locally.)

  4. PIPING-WIRING DIRECTIONS
    Piping and wiring connections
    can be made from 4 directions:
    FRONT, Right,Rear and Below.Piping and wiring connections
    can be made from 4 directions:
    FRONT, Right,Rear and Below.

MITSUBISHI ELECTRIC A24KA7 Wall Mounted Air Conditioning System - INDOOR
UNIT DIMENSIONS 2MITSUBISHI ELECTRIC A24KA7 Wall Mounted Air Conditioning
System - INDOOR UNIT DIMENSIONS 3

FORM# PKA-A24KA7 & PUY-A24NHA7 – 202304
Specifications are subject to change without notice.www.ahridirectory.org
Unitary Small AC
AHRI Standard 210/240
Certification applies only when the complete system is listed with AHRI. © 2023 Mitsubishi Electric Trane HVAC US LLC.
All rights reserved.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Mitsubishi Electric User Manuals

Related Manuals