MITSUBISHI ELECTRIC PKA-A24KA7 Wall Mounted Heat Pump System Owner’s Manual

June 17, 2024
Mitsubishi Electric

PKA-A24KA7 & PUZ-A24NHA7

24,000 BTU/H WALL-MOUNTED INDOOR UNIT

24,000 BTU/H HEAT PUMP UNIVERSAL OUTDOOR

American Standard logo

Job Name:
System Reference:                                      Date:

Indoor Unit ……………………….. PKA-A24KA7
Outdoor Unit …………………. PUZ-A24NHA7

MITSUBISHI ELECTRIC PKA-A24KA7 Wall Mounted Heat Pump System
1

INDOOR UNIT FEATURES

  • Sleek, compact design
  • Simple installation
  • Vane setting for air flow direction control
  • Auto fan speed mode
  • Ideal for spaces such as server rooms, daycare centers, classrooms, churches, small offices, and more
  • Multiple control options available:
    • kumo cloud® smart device app for remote access
    • Third-party interface options
    • Wired or wireless controllers

OUTDOOR UNIT FEATURES

  • Variable speed INVERTER-driven compressor
  • Pre-charged with refrigerant volume for piping length up to 70 ft
  • Low ambient cooling down to 0°F providing 100% capacity
  • 24-hour continuous operation (cooling mode)
  • High pressure protection
  • Fast restart
  • Superior energy and operational efficiency
  • Seacoast protection*
    • External Outer Panel: Phosphate coating + Acrylic-Enamel coating
    • Fan Motor Support: Epoxy resin coating (at edge face)
    • Separator Assembly Valve Bed: Epoxy resin coating (at edge face)
    • Blue Fin treatment is an anti-corrosion treatment that is applied to the Heat exchanger coil to protect it against airborne contaminants.
    • Heat exchanger coil and base panel rated for 2,000 hours in accordance with ASTM B117 testing

*Seacoast protection standard from 2022 production

SPECIFICATIONS: PKA-A24KA7 & PUZ-A24NHA7

Cooling at 95°F1| Maximum Capacity|

BTU/H

|

24,000

---|---|---|---
Rated Capacity|

BTU/H

|

24,000

Minimum Capacity|

BTU/H

|

10,000

Maximum Power Input|

W

|

1,960

Rated Power Input|

W

|

1,960

Moisture Removal|

Pints/h

|

5.0

Sensible Heat Factor| |

0.77

Power Factor [208V / 230V]|

%

|

95.7 / 95.7

Heating at 47°F2| Maximum Capacity|

BTU/H

|

28,000

Rated Capacity|

BTU/H

|

26,000

Minimum Capacity|

BTU/H

|

9,000

Maximum Power Input|

W

|

2,600

Rated Power Input|

W

|

1,750

Power Factor [208V / 230V]|

%

|

750.0 / 750.0

Heating at 17°F3| Maximum Capacity|

BTU/H

|

18,300

Rated Capacity|

BTU/H

|

15,700

Maximum Power Input|

W

|

1,820

Rated Power Input|

W

|

1,750

Heating at 5°F4| Maximum Capacity|

BTU/H

|

15,200

Maximum Power Input|

W

|

2,300

Efficiency| SEER | SEER2| |

21.4 | 21.3

EER1 | EER21| |

12.2 | 12.2

HSPF [IV] | HSPF2 [IV]| |

11.0 | 9.3

COP at 47°F2| |

4.35

COP at 17°F at Maximum Capacity3| |

2.95

COP at 5°F at Maximum Capacity4| |

1.94

ENERGY STAR® Certified| |

No

Electrical| Voltage, Phase, Frequency| |

208/230, 1, 60

Guaranteed Voltage Range|

V AC

|

198 – 253

Voltage: Indoor – Outdoor, S1-S2|

V AC

|

208/230

Voltage: Indoor – Outdoor, S2-S3|

V DC

|

24

Short-circuit Current Rating [SCCR]|

kA

|

5

Recommended Fuse/Breaker Size (Outdoor)|

A

|

25

Recommended Wire Size [Indoor – Outdoor]|

AWG

|

14

Power Supply| |

Indoor unit is powered by the outdoor unit

Indoor Unit| MCA|

A

|

1.0

Fan Motor Full Load Amperage|

A

|

0.36

Fan Motor Type| |

DC Motor

Airflow Rate at Cooling, Dry|

CFM

|

635–705–775

Airflow Rate at Cooling, Wet|

CFM

|

570–635–700

Airflow Rate at Heating, Dry|

CFM

|

635–705–775

Sound Pressure Level [Cooling]|

dB[A]

|

39–42–45

Sound Pressure Level [Heating]|

dB[A]

|

39–42–45

Drain Pipe Size|

In. [mm]

|

5/8 [16]

Coating on Heat Exchanger| |

External Finish Color| |

White Munsell 1.0Y 9.2/0.2

Unit Dimensions|

W x D x H: In. [mm]

|

46-1/16 x 11-5/8 x 14-3/8 [1,170 x 295 x 365]

Package Dimensions|

W x D x H: In. [mm]

|

51 x 14-1/4 x 18-1/2 [1,295 x 362 x 470]

Unit Weight|

Lbs. [kg]

|

46 [21]

Package Weight|

Lbs. [kg]

|

53 [24]

Indoor Unit Operating Temperature Range| Cooling Intake Air Temp [Maximum / Minimum]*|

°F

|

90 DB, 72 WB / 66 DB, 61 WB

Heating Intake Air Temp [Maximum / Minimum]|

°F

|

77 DB / 59 DB

Outdoor Unit| MCA|

A

|

19.0

MOCP|

A

|

26

Fan Motor Full Load Amperage|

A

|

0.4

Fan Motor Output|

W

|

86

Airflow Rate [Cooling / Heating]|

CFM

|

1940 / 1940

Refrigerant Control| |

LEV

Defrost Method| |

Reverse Cycle

Coating on Heat Exchanger| |

Blue Fin Coating***

Sound Pressure Level, Cooling1|

dB(A)

|

47

Sound Pressure Level, Heating2|

dB(A)

|

48

Compressor Type| |

INVERTER-driven twin rotary

Compressor Model| |

SNB172FWHM1

Compressor Rated Load Amps|

A

|

7

Compressor Locked Rotor Amps|

A

|

11.0

Compressor Oil [Type // Charge]|

oz.

|

FV50S // 23

External Finish Color| |

Ivory Munsell 3Y 7.8/1.1

Base Pan Heater| |

N/A

Unit Dimensions|

W x D x H: In. [mm]

|

37-13/32 x 13 (+1-3/16) x 37-1/8 [950 x 330 (+30) x 943]

Package Dimensions|

W x D x H: In. [mm]

|

40-15/16 x 17-11/16 x 40-11/16 [1040 x 450 x 1033]

Unit Weight|

Lbs. [kg]

|

153 [69]

Package Weight|

Lbs. [kg]

|

179 [81]

Outdoor Unit Operating Temperature Range| Cooling Air Temp [Maximum / Minimum]*|

°F

|

115 DB / 0 DB

Heating Air Temp [Maximum / Minimum]|

°F

|

70 DB, 59 WB / -4 DB, -4 WB

Heating Thermal Lock-out / Re-start Temperatures**|

°F

|

-8 / -4

Refrigerant| Type| |

R410A

Pre-Charged Refrigerant Amount|

Lbs, oz

|

7.0, 11.0

Maximum Pre-Charged Piping Length|

Ft. [m]

|

70.0 [20.0]

Additional Refrigerant Charge Per Additional Piping Length|

oz./Ft. [g/m]

|

0.7 [50]

Piping| Gas Pipe Size O.D. [Flared]|

In.[mm]

|

5/8 [15.88]

Liquid Pipe Size O.D. [Flared]|

In.[mm]

|

3/8 [9.52]

Maximum Piping Length|

Ft. [m]

|

165 [50]

Maximum Height Difference|

Ft. [m]

|

100 [30]

Maximum Number of Bends| |

15

NOTES:
AHRI Rated Conditions
(Rated data is determined at a fixed compressor speed)

1 Cooling (Indoor // Outdoor)                  °F 80 DB, 67 WB // 95 DB, 75 WB
2 Heating at 47°F (Indoor // Outdoor)     °F 70 DB, 60 WB // 47 DB, 43 WB
3 Heating at 17°F (Indoor // Outdoor)     °F 70 DB, 60 WB // 17 DB, 15 WB

*Indoor/Outdoor Unit Operating Temperature Range (Cooling Air Temp [Maximum / Minimum]):

  • Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions.
    » Wind baffles required to operate below 23°F DB in cooling mode.
    » Heat pump system with wind baffle: 0°F – 115°F.
    » Refer to wind baffle documentation for further information.

**Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re- start Temperatures; Heating Thermal Lock-out / Re-start Temperatures):

  • System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures.

***Blue Fin Coating Standard from 2022 production:

  • PU(Y/Z)-A(12/18)NKA7 – Beginning with serial number 12U*****
  • PU(Y/Z)-A(24/30/36/42)NKA7 – Beginning with serial number 1ZU*****
INDOOR UNIT ACCESSORIES: PKA-A24KA7
Control Interface 3-Pin Connector PAC-715AD
BACnet® and Modbus® Interface PAC-UKPRC001-CN-1
IT Extender PAC-WHS01IE-E
kumo station® for kumo cloud® TAC-WHS01HC-E
Thermostat Interface PAC-US444CN-1
Thermostat Interface PAC-US445CN-1
USNAP Adapter PAC-WHS01UP-E
Wireless Interface for kumo cloud® PAC-USWHS002-WF-2
Remote Sensor Flush Mount Remote Temperature Sensor PAC-USSEN002-FM-1
Flush Mount Temperature Sensor PAC-USSEN001-FM-1
Remote Temperature Sensor PAC-SE41TS-E
Wireless temperature and humitity sensor for kumo cloud® PAC-USWHS003-TH-1
Wired Remote Controller Deluxe Wired MA Remote Controller† AAR-40MAAU
Simple Ductless Wired Remote Controller PAC-SDW01RC-1
Simple MA Remote Controller† PAC-YT53CRAU-J
Touch MA Controller† PAR-CT01MAU-SB
Wireless Remote Controller kumo touch™ RedLINK™ Wireless Controller MHK2
Lockdown bracket for remote controller RCMKP1CB
Wireless MA Receiver PAR-SR32MA-E
Wireless MA Remote Controller PAR-FL32MA-E
Condensate Blue Diamond (Advanced) Mini Condensate Pump w/ Reservoir & Sensor
(208/230V) [recommended] X87-721
Blue Diamond (MegaBlue Advanced) Condensate Pump w/ Reservoir & Sensor

X87-835
Drain Pan Level Sensor/Control| SS610E
Refco Condensate Pump (100-240 VAC)| GOBI-II
Refco Condensate Pump (100-240 VAC) up to 120,000 BTU/H| COMBI
Disconnect Switch| (30A/600V/UL) [fits 2” X 4” utility box] – Black| TAZ- MS303
Lineset| 10’ x 3/8” x 10’ x 5/8” Lineset (Twin-Tube Insulation)| MPLS385812T-10
100’ x 3/8” x 100’ x 5/8” Lineset (Twin-Tube Insulation)| MPLS385812T-100
15’ x 3/8” x 15’ x 5/8” Lineset (Twin-Tube Insulation)| MPLS385812T-15
30’ x 3/8” x 30’ x 5/8” Lineset (Twin-Tube Insulation)| MPLS385812T-30
50’ x 3/8” x 50’ x 5/8” Lineset (Twin-Tube Insulation)| MPLS385812T-50
65’ x 3/8” x 65’ x 5/8” Lineset (Twin-Tube Insulation)| MPLS385812T-65

OUTDOOR UNIT ACCESSORIES: PUZ-A24NHA7
Air Outlet Guide Air Outlet Guide (1 Piece) PAC-SG59SG-E
Centralized Drain Pan Centralized Drain Pan PAC-SG63DP-E
Drain Pan PAC-SG64DP-E
Control/Service Tool Control/Service Tool PAC-SK52ST
M- & P-Series Maintenance Tool Cable Set M21EC0397
USB/UART Conversion Cable (Required for all laptop connection) M21EC1397
Hail Guards Hail Guard HG-A6
M-NET Converter M-NET Converter PAC-SJ85MA-E
M-NET Converter PAC-SJ95MA-E
Mini-Split Wire 14 Gauge, 4 wire MiniSplit Cable—250 ft. roll S144-250
14 Gauge, 4 wire MiniSplit Cable—50 ft. roll S144-50
16 Gauge, 4 wire MiniSplit Cable—250 ft. roll S164-250
16 Gauge, 4 wire MiniSplit Cable—50 ft. roll S164-50
Mounting Pad Condensing Unit Mounting Pad: 24” x 42” x 3” ULTRILITE2
Stand 18” Single Fan Stand QSMS1801M
24” Single Fan Stand QSMS2401M
Condenser Wall Bracket QSWB2000M-1
Condenser Wall Bracket – Stainless Steel Finish QSWBSS
Outdoor Unit Stand — 12” High QSMS1201M
Wind Baffle Front Wind Baffle WB-PA5
Rear Wind Baffle WB-RE5
Side Advanced Wind Baffle WB-SD5
INDOOR UNIT DIMENSIONS: PKA-A24KA7

Unit: inch (mm)

  Top side

MITSUBISHI ELECTRIC PKA-A24KA7 Wall Mounted Heat Pump System -
a1

  Left side

  1. Knockout hole for left piping

  Front side

MITSUBISHI ELECTRIC PKA-A24KA7 Wall Mounted Heat Pump System -
a3

  1. Operation lamp
  2. DEFROST/STAND BY lamp
  3. Receiver

  Right side

  1. Mount board
  2. Knockout hole for right piping

  Front side(Grille open)

MITSUBISHI ELECTRIC PKA-A24KA7 Wall Mounted Heat Pump System -
a11

  1. Terminal block for Outdoor unit
  2. Terminal block for power supply (option)
  3. Terminal block for MA-remote controller
  4. Emergency operation switch (cooling/heating)
  5. 17-15/32(444)Gas pipe
  6. 18-31/32(482)Liquid pipe
  7. Drain hose
  8. Filter hook

Piping connection

1  Liquid pipe| Refrigerant pipe: 3/8 O.D([ 9.52)
Flared connection: 3/8F
---|---
2  Gas pipe| Refrigerant pipe: 5/8 O.D([ 15.88)
Flared connection: 5/8F
3  Drain hose| 5/8([ 16) O.D
Effective length: 23-1/32 (585)

  Under side

MITSUBISHI ELECTRIC PKA-A24KA7 Wall Mounted Heat Pump System -
a7

  1. Vane(auto)
  2. Louver(manual)
  3. Knockout hole for lower piping

Sleeve
(purchased locally)| Through hole
---|---
[2-15/16] (75)| [ 2-15/16~[ 3-5/32] (75~[ 80)

  Required space(Indoor unit)

MITSUBISHI ELECTRIC PKA-A24KA7 Wall Mounted Heat Pump System -
a8

  1. Air inlet
  2. Air outlet

  Knockout hole for piping

MITSUBISHI ELECTRIC PKA-A24KA7 Wall Mounted Heat Pump System -
a9

MITSUBISHI ELECTRIC PKA-A24KA7 Wall Mounted Heat Pump System -
a12

  1. 4- 11/32 Bolt hole

  2. Center measurement hole
    3/32

  3. Mount board

  4. Indoor unit outline

  5. Wall hole for right rear piping

  6. Knockout hole for rear piping

  7. 75- 3/16
    Tapping screw hole

OUTDOOR UNIT DIMENSIONS: PUZ-A24NHA7

1 FREE SPACE (Around the unit)

The diagram below shows a basic example.
Explanation of particular details are given in the installation manuals etc.

2 SERVICE SPACE

Dimensions of space needed for service access are shown in the below diagram.

3 FOUNDATION BOLTS

Please secure the unit firmly with 4 foundation (M10<W3/8>) bolts.
(Bolts and washers must be purchased locally.)

  1. FOUNDATION

4 PIPING-WIRING DIRECTIONS

Piping and wiring connections can be made from 4 directions:
FRONT, Right, Rear and Below.

Unit: mm

MITSUBISHI ELECTRIC PKA-A24KA7 Wall Mounted Heat Pump System -
b5

  1. Rear Air Intake
  2. 2-U Shaped notched holes (Foundation Bolt M10<W3/8>)
  3. Installation Feet
  4. 2-12×36 oval holes (Foundation Bolt M10<W3/8>)
  5. Air Discharge
  6. Side Air Intake

Example of Notes

(1) … Refrigerant GAS pipe connection (FLARE) ø15.88(5/8F)
(2) … Refrigerant LIQUID pipe connection (FLARE) ø 9.52(3/8F)

*1… Indication of STOP VALVE connection location.

MITSUBISHI ELECTRIC PKA-A24KA7 Wall Mounted Heat Pump System -
b6

  1. Air Intake

  2. Handle for moving

  3. Rear Air Intake

  4. Side Air Intake

  5. Earth terminal

  6. Terminal Connections
    Left … Power supply wiring
    Right … Indoor/Outdoor wiring

  7. Service panel

  8. Front piping cover

  9. Rear piping cover

Piping knockout Hole Details

MITSUBISHI ELECTRIC PKA-A24KA7 Wall Mounted Heat Pump System -
b7

  1. Front piping hole (knockout)
  2. Front trunking hole (knockout)
  3. Power supply wiring hole (2-ø27knockout)
  4. Right piping hole (knockout)
  5. Right trunking hole (knockout)
  6. Power supply wiring hole (2- ø27<1-1/16>knockout)
  7. Rear trunking hole (knockout)
  8. Rear piping hole (knockout)

Set the attachment to the When installing the conduit, inner side of each panel.

  1. 1/2 Conduit attachment

MITSUBISHI ELECTRIC PKA-A24KA7 Wall Mounted Heat Pump System -
b9

  1. Bottom piping hole (knockout)
  2. Drain hole (5- ø33<1-5/16>)

FORM# PKA-A24KA7 & PUZ-A24NHA7 – 202304

AHRI CERTIFIED Certificate

Specifications are subject to change without notice.

© 2023 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

Read User Manual Online (PDF format)