RICE LAKE SCT-4X-MODBUS TCP IP Weight Transmitter User Guide
Electrical Schematic
Manuals are available from Rice Lake Weighing Systems at
www.ricelake.com/manuals
Warranty information is available at www.ricelake.com/warranties
Key Functions
Indicator Light Descriptions
Configuration Menu
- Reboot the weight transmitter
- Press the key when display shows the 888888 message
Function Mode
. Maximum Scale Capacity, Increment and Decimal Point Settings
Zeroing Mechanical Tare (pre-tare zeroing)
Inputs Settings
RS485 Port
Load Cell Exclusion (for dependent channel systems)
If a load cell is broken, it’s possible to temporarily exclude the channel
where it is connected and continue to weigh, pending replacement.
! WARNING: this operation reduces the accuracy of the weighing system. We
recommend use for liquid weighing or in applications
where the load is evenly distributed.
Example:
The unbalance condition is signalled via Modbus / Fieldbus or a digital output
(refer to the complete manual to set the output).
This function is only available if EXCL.CH = NoNE.
Use this function only in systems where the load is evenly distributed
Programming Errors
MESSAGE | DESCRIPTION | SOLUTION |
---|---|---|
preC. | Calibration error | First calibrate the zero point (zero), then proceed |
with sample weight acquisition (span) (section 9).
Err.pn| ****
Calibration error
| Check the connection of the load cell. Verify the load cell signal is
stable, valid and greater than the previously acquired point.
Er 11| Calibration error| Increase the calibration weight.
Er 12| Calibration error| Check the signal from the load cell increases when
weight is incremented on the scale.
Er 37| Calibration error| Repeat calibration and verify capacity and division
have been correctly set.
Er 39| Instrument not configured| Transmitter needs to be configurated.
C.er.36| Calibration error| Verify the signal from the load cell is not
negative.
C.er.37| Calibration error| Verify the signal from the load cell is not
negative.
Err.mo
| ****
Weight unstable
| Check in adC.uv parameter that the signal is stable.
If the connection of the cells is with 4 wires, check that the sense jumpers are inserted.
adC.err| A/D converter error| Converter failure. Reboot the instrument.
Cel.err| Global load cell error| Signal anomaly: check the load cells
connection.
Er.Cel.1
…
Er.Cel.4
| ****
Load cell error
| ****
Signal anomaly: check the indicated load cell connection.
Modbus TCP
MODBUS TCP REGISTERS – CH / ind.ch (1 SCALE)
Data | Register | DESCRIPTION |
---|
Gross weight
| 30001| ****
Bytes 1, 2, 3 and 4 contain the Gross Weight value.
30003
Net weight
| 30005| ****
Bytes 5, 6, 7 and 8 contain the Net Weight value.
30007
Input status register
| ****
30009
| Bit 15(msb) Bit 14
Bit 13
Bit 12
Bit 11
Bit 10
Bit 9
Bit 8 (lsb)
| Active channel. Bit 15 Bit 14 Active Channel
Active channel.
No function. 0 0 Channel 1
No function. 0 1 Channel 2
No function.
No function. 1 0 Channel 3
Status of input n. 2. 1 1 Channel 4
Status of input n. 1.
Bit 7(msb) Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0 (lsb)
| 1 = Scale unloaded (gross weight = 0). Tare PT (1 = PT tare is active).
Tare (1 = Tare is active).
Overload condition (0 = No; 1 = Overload). Underload condition (0 = No; 1 = Underload). Weight Stability (0 = Unstable; 1 = Stable).
Gross Weight Polarity (0 = “+”; 1 = “-”). Net Weight Polarity (0 = “+”; 1 = “-”).
Command status register
| ****
30011
| Last received command.
Bit 7(msb) Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0 (lsb)
| Last command result. Last command result. Last command result. Last command result.
Counting of processed commands. Counting of processed commands. Counting of processed commands. Counting of processed commands.
Output status register
| ****
30013
| No Function.
Bit 7(msb)
…
Bit 2
Bit 1
Bit 0(lsb)
| No function.
…
No function.
Digital output 2 status (0 = OFF; 1 = ON). Digital output 1 status (0 = OFF; 1 = ON).
Selected page| 30015| Shows the value of the selected page (3001).
µV Channel 1| 30017| Bytes 16 and 17 contain the µV value of the channel
- µV Channel 2| 30019| Bytes 18 and 19 contain the µV value of the channel
-
µV Channel 3| 30021| Bytes 20 and 21 contain the µV value of the channel
-
µV Channel 4| 30023| Bytes 22 and 23 contain the µV value of the channel
MODBUS TCP REGISTERS – ch (4 SCALES)
Data | Register | DESCRIPTION |
---|
Status register scale 1
| ****
30001
| Bit 15(msb) Bit 14
Bit 13
Bit 12
Bit 11
Bit 10
Bit 9
Bit 8 (lsb)
| Not used. Not used. Not used.
Scale active (0 = “no”; 1 = “yes”). Decimals (00 = 0; 01 = 1; 10 = 2; 11 = 3)
Unit of Measure (00 = “g”; 01 = “kg”; 10 = “t”; 11 = “lb”).
Bit 7(msb) Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0 (lsb)
| Tare PT (1 = PT tare is active). Tare (1 = Tare is active).
Net Weight Polarity (0 = “+”; 1 = “-”).
1 = Scale unloaded (gross weight = 0). Overload condition (0 = No; 1 = overload). Underload condition (0 = No; 1 = underload). Stability (0 = “unstable”; 1 = “stable”).
Gross Weight Polarity (0 = “+”; 1= “-”).
Status register scale 2| 30002| Same as Status register scale 1.
Status register scale 3| 30003| Same as Status register scale 1.
Status register scale 4| 30004| Same as Status register scale 1.
Input status register
| ****
30005
| Bit 15(msb) Bit 14
Bit 13
Bit 12
Bit 11
Bit 10
Bit 9
Bit 8 (lsb)
| Active channel. Active channel. No function.
No function. No function. No function.
Status of input n. 2. Status of input n. 1.
| | |
| |
| |
| |
| |
No function.
Command status register| 30006| Same as Command status register page 10.
Output status register| 30007| Same as Output status register page 10.
Selected page| 30008| Shows the value of the selected page (2000).
Gross weight scale 1
| 30009| ****
Bytes 16, 17, 18 and 19 contain the Gross Weight of scale 1.
30010
Gross weight scale 2
| 30011| ****
Bytes 20, 21, 22 and 23 contain the Gross Weight of scale 2.
30012
Gross weight scale 3
| 30013| ****
Bytes 24, 25, 26 and 27 contain the Gross Weight of scale 3.
30014
Gross weight scale 4
| 30015| ****
Bytes 28, 29, 30 and 31 contain the Gross Weight of scale 4.
30016
DEVICENET REGISTERS FOR COMMAND SENDING
Data | Register | DESCRIPTION |
---|
Command
| ****
30001
| Main available commands:
Value Command 00 Hex No command 01 Hex Scale zeroing 02 Hex Tare
03 Hex Preset Tare
0A Hex Setpoint 1 setting 0B Hex Setpoint 2 setting
19 Hex Digital output setting
22 Hex Reboot the weight transmitter
Parameter 1
| ****
30002
| ****
First parameter of the command.
Parameter is always expressed in absolute mode (no decimals, no sign).
30003
Parameter 2
| ****
30004
| ****
Second parameter of the command.
Parameter is always expressed in absolute mode (no decimals, no sign).
30005
| 30006| ****
Used in advanced configuration, refer to the complete Fieldbus manual for further information.
…
30016
EXAMPLE 1
For zeroing the weight on the scale:
Set the command in byte 2
Register | Value |
---|
30001
|
01 Hex
EXAMPLE 2
For setting a preset tare of 1000 lb:
- Set the tare value in parameter 1 (byte 3, 4, 5, 6)
- Set the command in byte 2
Register | Value |
---|
30001
|
03 Hex
30002
|
00 Hex
30003
|
03E8 Hex
Read More About This Manual & Download PDF: