condair DA160 Adsorption Dehumidifier Instruction Manual
- June 17, 2024
- condair
Table of Contents
- condair DA160 Adsorption Dehumidifier
- INSTALLATION AND OPERATION MANUAL
- Introduction
- For your safety
- Important notes
- Product overview
- Installation
- Commissioning
- Maintenance
- Troubleshooting
- Product specification
- Spare parts
- Electrical wiring diagrams
- EU declaration of conformity
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
condair DA160 Adsorption Dehumidifier
Specifications
- Model: Condair DA 160 – 440
- Function: Desiccant dryer for dehumidification and drying
- Applications: Industrial, commercial, or residential dehumidification needs
Product Overview
The Condair DA 160 – 440 desiccant dryer is designed for efficient
dehumidification and drying purposes. It consists ofvarious components:
- Casing
- Rotor
- Filters
- Fan for process- and reactivation air
- Heater for reactivation air
- Electrical panel
- Operation Options
Installation
Proper installation is crucial for optimal performance:
- Ensure access for installation and service.
- Connect ducts appropriately based on installation type.
- Complete electrical installation by following provided guidelines.
Commissioning
After installation, carry out the commissioning process as per the manual
to ensure the desiccant dryer functions correctly.
Maintenance
Regular maintenance is essential for longevity:
- Clean or replace filters periodically.
- Inspect and maintain rotor, electrical motors, heater, and rotor drive belt.
- Follow recommended maintenance intervals.
Troubleshooting
If issues arise, refer to the troubleshooting section in the manual to
identify and resolve problems effectively.
Product Usage Instructions
-
Ensure proper installation following the installation manual.
-
Set the desired dehumidification settings based on requirements.
-
Monitor the unit regularly for any signs of malfunction or
maintenance needs. -
Refer to the manual for troubleshooting guidance in case of issues.
FAQ
Q: How often should filters be replaced?
A: Filters should be checked regularly and replaced when they are
visibly dirty or clogged to maintain optimal performance.
INSTALLATION AND OPERATION MANUAL
Thank you for choosing Condair
- Installation date (MM/DD/YYYY):
- Commissioning date (MM/DD/YYYY):
- Site:
- Model:
- Serial number:
Proprietary Notice
This document and the information disclosed herein are proprietary data of Condair Group AG. Neither this document, nor the information contained herein shall be reproduced, used, or disclosed to others without the written authori- zation of Condair Group AG, except to the extent required for installation or maintenance of recipient’s equipment.
Liability Notice
Condair Group AG does not accept any liability due to incorrect installation
or operation of the equipment or due to the use of parts/components/equipment
that are not authorized by Condair Group AG.
Copyright Notice
© Condair Group AG, All rights reserved.
Technical modifications reserved
Introduction
To the very beginning
We thank you for having purchased a Condair DA 160 – 440 desiccant dryer (for
short: Condair DA).
The Condair DA desiccant dryers incorporate the latest technical advances and
meets all recognized safety standards. Nevertheless, improper use of the
Condair DA desiccant dryer may result in danger to the user or third parties
and/or damage to property.
To ensure a safe, proper, and economical operation of the Condair DA desiccant
dryer, please observe and comply with all information and safety instructions
contained in the present documentation as well as in the separate
documentations of the components installed in the drying system.
If you have questions after reading this documentation, please contact your
Condair representative. They will be glad to assist you.
Notes on the installation and operation manual
Limitation
The subject of this installation and operation manual are the Condair DA 160 –
440 desiccant dryers in their different versions. The various options and
accessories are only described insofar as this is necessary for proper
operation of the equipment. Further information on options and accessories can
be obtained in the respective manuals.
This installation and operation manual is restricted to the installation,
commissioning, operation, maintenance and troubleshooting of the Condair DA
desiccant dryer and is meant for well-trained personnel being sufficiently
qualified for their respective work.
Symbols used in this manual
Safekeeping
Please safeguard this installation and operation manual in a safe place, where
it can be immediately accessed. If the desiccant dryer changes hands, the
documentation must be passed on to the new operator.
If the documentation gets misplaced, please contact your Condair
representative.
Language versions
This installation and operation manual is available in other languages. Please
contact your Condair representative for information.
For your safety
General
Every person working with the Condair DA desiccant dryer must have read and
understood this installation and operation manual before carrying out any
work.
Knowing and understanding the contents of the installation and operation
manual is a basic requirement for protecting the personnel against any kind of
danger, to prevent faulty operation, and to operate the unit safely and
correctly.
All ideograms, signs and markings applied to the Condair DA desiccant dryer
must be observed and kept in readable state.
Qualification of personnel
All work described in this installation and operation manual may only be
carried out by specialist who are well trained and adequately qualified and
are authorized by the customer.
For safety and warranty reasons any action beyond the scope of this manual
must be carried out only by qualified personnel authorised by the
manufacturer.
It is assumed that all persons working with the Condair DA desiccant dryer are
familiar and comply with the appropriate regulations on work safety and the
prevention of accidents.
The Condair DA desiccant dryer may not be used by persons (including children)
with reduced physical, sensory or mental abilities or persons with lacking
experience and/or knowledge, unless they are supervised by a person
responsible for their safety or they received instructions on how to operate
the system. Children must be supervised to make sure that they do not play
with the Condair DA desiccant dryer.
Intended use
The Condair DA 160 – 440 desiccant dryers are intended exclusively for air
dehumidification at atmospheric pressure within the specified operating
conditions (see chapter 9.1 – Technical data). Any other type of application,
without the written consent of Condair, is considered as not conforming with
the intended purpose and may lead to the Condair DA desiccant dryer becoming
dangerous. Operation of the equipment in the intended manner requires that all
the information contained in this installation and operation manual are
observed (in particular the safety instructions).
Danger that may arise from the Condair DA desiccant dryer
DANGER!
Danger of electric hazard!
The Condair DA desiccant dryer is mains powered. Live parts may be exposed
when the unit is open. Touching live parts may cause severe injury or danger
to life.
Prevention: Before carrying out any work set the Condair DA desiccant dryer
out of operation (switch off the unit, disconnect it from the mains) and
secure the unit against inadvertent power-up.
WARNING!Risk of injury!
- Inside the Condair DA desiccant dryer there are moving parts present, which can cause seri-ous injury to hands and fingers.
- Prevention: Before carrying out any work set the Condair DA desiccant dryer out of operation (switch off the unit, disconnect it from the mains) and secure the unit against inadvertent power-up.
- Keep hands away from moving parts.
- Inside the Condair DA desiccant dryer are heating element present, which can cause burns if touched.
- Prevention: Before carrying out any work set the Condair DA desiccant dryer out of operation (switch off the unit, disconnect it from the mains), secure the unit against inadvertent power-up, and wait at least 15 minutes prior to opening any service panel, allowing the heater to cool down.
Warning signs attached to the unit
Preventing
unsafe operation
If it is suspected that safe operation is no longer possible, the Condair
DA desiccant dryer should immediately be shut down and secured against
accidental power-up. This can be the case under the following circumstances:
- if the Condair DA desiccant dryer is damaged
- if the electrical installations are damaged
- if the Condair DA desiccant dryer is no longer operating correctly
All persons working with the Condair DA desiccant dryer must report any alterations to the unit that may affect safety to the owner without delay.
Prohibited modifications to the unit
No modifications must be undertaken on the Condair DA 160 – 440 desiccant
dryers without the express written consent of Condair.
For the replacement of defective components use exclusively original
accessories and spare parts available from your Condair representative.
CAUTION!
- The desiccant dryer must only be used for dehumidification of air at atmospheric pressure.
- Never use the desiccant dryer without the filters as the desiccant rotor can become contaminated and lose capacity.
- The desiccant dryer must not be installed in areas where explosion proof equipment is required.
Important notes
Inspection of the delivery
After receiving:
- Inspect shipping boxes for damage. Any damages of the shipping boxes must be reported to the shipping company.
- Check packing slip to ensure all parts has been delivered. All material shortages are to be reported to your Condair supplier within 48 hours after receipt of the goods. Condair assumes no responsibility for any material shortages beyond this period.
- Unpack the parts/components and check for any damage. If parts/components are damaged, notify the shipping company immediately
- Check whether the components are suitable for installation on your site according to the model key stated on the type plate
Storing/Transportation/Packaging
Storing
The Condair DA desiccant dryer must be stored in a weather-protected
environment.
- Room temperature: -30°C to +40°C
- Room humidity: 0-90%RH (noncondensing)
Transportation
Observe the following for transport or handling of the Condair DA desiccant dryer:
- The desiccant dryer should always stand upright on its feet.
- Never put other goods on top of the desiccant dryer.
For optimum protection always transport the unit in the original packaging and use an appropriate lifting/transporting device.
Packaging
Keep the original packaging of the components for later use. In case you wish
to dispose of the packag-ing, observe the local regulations on waste disposal.
Please recycle packaging where possible.
Product overview
Product designation
The product designation and the most important unit data are found on the
specification label fixed on the left side of the DA 160 – 440 desiccant dryer
(see example below):
Applications
The Condair desiccant dryers are based on the sorption principle and are
designed to dry air of atmospheric pressure. The desiccant dryer can be used
for drying air of up to 100 % relative humidity (RH) with air temperatures
from -30°C to+40°C.
The applications are numerous and widespread. Below are some examples:
- Controlling humidity levels in production processes.
- Drying of temperature-sensitive products.
- Maintaining correct humidity in storage areas.
- Protection of equipment sensitive to corrosion.
- Controlling humidity levels in museums and archives.
- Drying after water damage and drying of buildings during construction.
- Climatic improvements in damp areas.
Method of operation
The desiccant dryer operates with two air streams. A larger air stream to be
dehumidified, and a smaller air stream to exhaust the moisture out of the
desiccant rotor. Both airstreams are created by one com-mon fan which
pressurises a compartment of the desiccant dryer creating two separate
airstreams.
The larger air volume, the process air, passes through the slowly rotating
silica gel rotor. Silica gel is a hygroscopic material adsorbing water vapour
direct from the air. When passing through the rotor the humidity of the air is
reduced, whilst the moisture content of the rotor material increases. On
exiting the rotor the dried air is introduced into the area, or the process to
be dehumidified. The adsorption process works in temperatures from -30°C to
+40°C.
The smaller air volume, the reactivation air, desorbs the moisture from the
silica gel rotor. This reactivation air is heated by an internal heater to a
temperature of approximately+120°C. As the reactivation air passes through the
rotor, in an opposite direction to the dry air, it will decrease the moisture
content of the rotor material. The reactivation air will leave the desiccant
dryer as warm, moist air, which is then exhausted out from the building.
Product description
Casing
The casing is fabricated from 1.4301 (AISI 304) stainless steel. The top of
the desiccant dryer has a top hood that can be removed for service access to
electrical and mechanical components. All duct connections to the desiccant
dryer are designed for connections to standard size spiral ducts except for
the process air inlet.
Rotor
The desiccant dryer has a drying rotor fabricated from 82% desiccant material, 16% fibreglass and 2%adhesive sealant. The rotor has a matrix of corrugated and flat heat resistant sheets, which houses the Silica Gel desiccant agent. This matrix creates a large number of axial flutes through the rotor, which together builds up an immense surface area for moisture adsorption in a small volume. The rotor is manufactured and processed to be able to withstand moisture-saturated air without being damaged. Furthermore, the rotor will not be damaged even if the fan or the heater for reactivation should fail during operation. The desiccant rotor is tested according to ASTM E84-18b, and the results are Flame Spread Index (FSI) 0 and Smoke Developed Index (SDI) 0.
Rotor drive system
The slow rotation of the rotor is achieved by an electrical gear motor and a
belt drive. The belt sits on the outer rim of the rotor and is driven by a
pulley on the drive motor. A adjustable belt tension device keeps the belt in
place and maintains tension to prevent belt slip. Correct operation of the
drive system, and direction of rotation can be checked by opening the top
panel.
The centre hub of the rotor is equipped with ball bearings. The rotor shaft is
made from stainless steel. The complete rotor part can easily be removed and
lifted as one piece out from the casing.
Filters
The desiccant dryer has one common air filter for process- and reactivation air. This filter primary serves to protect the components installed in the unit.
Fan for process- and reactivation air
The fan is a direct drive radial fan with a single phase standard motor class
IP 54, ISO F. The fan is accessible for service after removing the service
hood of the desiccant dryer. The exact type can be found in the respective
table in chapter 10.
Heater for reactivation air
The reactivation heater is of the PTC-type (Positive Temperature Control),
which can not be overheated.
Electrical panel
The electrical panel is located inside the desiccant dryer and is accessible
through the service hood.Switches and indications for operation are mounted at
the front of the electrical panel.
Operation Options
Using the operation switch on the front side of the desiccant dryer, different
running options can be selected:
- Dehumidifier not in operation.
- 1 Dehumidifier in operation mode.
- MAN Dehumidifier in continuous operation.
- AUTO Automatic operation by remote humidistat or other external on/off signal.
Installation
Installation and service access
The Condair DA 160 – 440 desiccant dryers are designed for indoor
installation.
All components in the desiccant dryer are accessible from the top of the unit.
For inspection and service, a space of 500 mm must be left free above the
desiccant dryer to accommodate for servicing of filters, fans and rotor.
When using a mounting plate, the desiccant dryer must be put so that the
rotorshaft still is horizontal and the wet air outlet is placed low.
Duct connection for permanent installation
The DA 160 – 440 desiccant dryers can be installed in the room that should to
be dehumidified or in a separate room.
To obtain the best performance the outlets from the fans should be equipped
with diffusors.
Wet air duct from the desiccant dryer
The wet air from the desiccant dryer should be exhausted to the outside. The
duct should be as short as possible to minimize the chance of condensation of
the wet air. This duct should slope down in angle of at least >2°, to stop any
condensed water from flowing back into the desiccant dryer. If the wet air
duct is extremely long, or must be installed sloping upwards from the
desiccant dryer, it should have a drainage point (2-3 mm) drilled at its
lowest position.
The exhaust opening should have a coarse wire net.
A damper should be installed in the wet air duct to enable correct setting of
the reactivation air volume during commissioning.
Process- and dry air with the desiccant dryer installed in the dehumidified
room
When the desiccant dryer is installed in the dehumidified room space it
would normally take the process air direct from the room without any duct
system, with only a protection net for the inlet required.
The dry air outlet would normally have a duct system designed for distribution
of the dry air in the building.
Process- and dry air with the desiccant dryer installed outside the dehumidified room
When the desiccant dryer is installed in a separate plant room all inlet and
outlet openings are usually
ducted.
The desiccant dryer draws ambient air from the place of installation. The dry
air from the desiccant dryer can be connected for post treatment or ducted
back to the dehumidified room.
The control of the reactivation and process air volume flow takes place via
the on-site installation of dampers in the wet and dry air duct.
Duct connection for basement installation
If the desiccant dryer should be installed in the basement it is sometimes
desirable to achieve a slight negative pressure in the space to prevent odours
from penetrating up into the building. In these circumstances the reactivation
air is taken directly from the basement and the wet air is exhausted out
fromthe basement. This method of installation will create a small negative
pressure. The ducts should be installed according to “Duct connections for
permanent installation”.
Temporary installation
With temporary installations for water damage or building drying, flexible
plastic ducts would normally beused instead of the spiral duct type. The
drying method differs depending on situation and construction to be dried. The
complete room could be dehumidified, or just the damaged part. For the later
option plastic sheet is used to cover the damaged area, and the dry air is
supplied under the sheet. For both options the wet air must be exhausted out
from the building via flexible duct, or alternatively connected to the general
exhaust ventilation system for the building.
Electrical installation
See chapter 11 – Electrical wiring diagrams
Commissioning
On initial start-up, the following steps should be taken in this order
- Ensure that the external isolation switch is isolating the unit from the mains, or that the power plug is disconnected.
- Select the OFF position on the main switch (orange) at the front of the desiccant dryer.
- Open the service hood on the top of the desiccant dryer and ensure no foreign objects are left inside the unit or in the electrical compartment
- Make sure the air filter is installed.
- Rotate the fan impeller by hand and make sure it can move freely.
- Ensure that the dry and wet air dampers are open, and that ducts are clean and free of blockages.
- Ensure that the mains supply fuse is suitably rated (10A), and that the fuse is of a slow kind.
- Connect the desiccant dryer to the main electrical supply by turning the isolation switch to ON, or alternatively connect the power plug to the socket.
- Select the MAN position on the operation switch (black) of the desiccant dryer. Switch the main switch (orange) to the ON position for 3-4 seconds. Check that the rotor is slowly rotating, the fans are starting, and that the orange lamp in the main switch lights up. Turn OFF the desiccant dryer.
- Mount the service hood and ensure it seals properly to the casing.
- The desiccant dryer is now ready for operation.
- Start the desiccant dryer and check that the unit is operating at the correct air volumes.
- From the factory the desiccant dryer is electrically wired in such a way that when operating in AUTO mode, the controls operate the complete unit to start or stop. By shifting one terminal connection in the electrical panel the operation mode can be altered to operate the fan continuously. The control will then only operate the heater on/off, depending on the signal from the humidistat or other external signal.
Maintenance
Important notes on maintenance
Qualification of personnel
All maintenance work must be carried out only by well qualified and trained
personnel authorised by the owner. It is the owner’s responsibility to verify
proper qualification of the personnel.
General note
- The instructions and details for maintenance work must be followed and upheld.
- Only the maintenance work described in this documentation may be carried out.
- Only use original Condair spare parts to replace faulty parts.
DANGER!
Danger of electric hazard!
The Condair DA desiccant dryer is mains powered. Live parts may be exposed
when the unit is open. Touching live parts may cause severe injury or danger
to life.
Prevention: Before carrying out any work set the Condair DA desiccant dryer
out of operation (switch off the unit, disconnect it from the mains) and
secure the unit against inadvertent power-up.
WARNING! Risk of injury!
Inside the Condair DA desiccant dryer there are moving parts present, which
can cause serious injury to hands and fingers.
Prevention: Before carrying out any work set the Condair DA desiccant dryer
out of operation (switch off the unit, disconnect it from the mains) and
secure the unit against inadvertent power-up.
Keep hands or other body parts away from moving parts.
WARNING! Risk of burns!
Inside the Condair DA desiccant dryer are heating element present, which can
cause burns if touched. Prevention: Before carrying out any work set the
Condair DA desiccant dryer out of operation (switch off the unit, disconnect
it from the mains), secure the unit against inadvertent power-up, and wait at
least 15 minutes prior to opening any service panel, allowing the heater to
cool down.
The maintenance intervals for the desiccant dryer depend on the surrounding environment and instal-lation site. Recommended maintenance intervals could therefore differ from one installation to another. Incorrect maintenance and service may result in reduced dehumidification capacity.
Filters
The desiccant dryer is equipped with one common filter for the process air and
reactivation air. The filter is positioned at the inlet and will clean the air
prior to entering the desiccant dryer.
Intervals for cleaning or replacement of the filters will be determined by the
amount of dust and particles in the air at the installation site.
We recommend that the filter is checked at least once a month, at least for
the first year of a new installation.
CAUTION!
Never operate the desiccant dryer without the filters, as the rotor can be
damaged by dust.
Rotor
The rotor is maintenance free. However should it be necessary to clean the
rotor the first choice should be careful use of compressed air. With severe
contamination, the rotor can be washed with water. Cleaning with water is no
routine matter; please contact your Condair representative.
Check the rotor bearing and the rotor surface once a year.
CAUTION!
Airborne chemical compounds, e.g. oily vapors or solvents can also be adsorbed
by the rotor and permanently reduces its capacity.
Electrical motors
The electrical motors are equipped with ball bearings. The bearings are
designed to last the life of the motor and therefore no maintenance is
required.
Check the motors once a year for any abnormal sound.
Heater
The reactivation electric heater does not need maintenance, but should be
checked twice a year for any dust or mechanical damage to the heating rods.
Clean with a soft brush, or vacuum clean with dust. Gentle use of compressed
air is another alternative.
Rotor drive belt
Check the belt tensioning at regular intervals. Adjust when needed by moving
the tensioning support wheel closer to the desiccant rotor.
General summary of maintenance intervals
Troubleshooting
Malfunction | Possible cause of trouble | Corrective action |
---|---|---|
None, or reduced dehumidification capacity | Filter dirty. | Clean or |
replace filters.
Electrical heater faulty.| Check fuses.
Airflow reduced.| Check openings and dampers.
No rotation of rotor.| Check belt tensioning.
Internal leakage in unit.| Check seals and springs.
Altered air volumes.| Measure and check air volumes.
Altered reactivation tempera- ture.| Check reactivation heater.
Air leakage.| Check panels and check seals.
Circuit breaker or fuse faulty| Fan faulty.| Check fans and motors.
Too large air volume.| Check air volumes and dampers.
Rotor does not rotate.| Check drive motor and drive belt.
Reactivation heater faulty.| Check reactivation heater.
Desiccant dryer does not start| No control circuit.| Check control
fuses.
Faulty control signal.| Check external start/stop signal
Phase fault.| Check main fuses.
Fuse for controls faulty.| Check electrical components.
Rotor does not rotate| Drive belt is slipping.| Check belt tensioning.
Drive belt broken or worn.| Replace drive belt.
Rotor jammed.| Check centre shaft, rim of rotor.
Drive motor faulty.| Replace complete gear motor.
No dry- or wet air volume| Filter dirty.| Clean or replace filters.
Fan faulty.| Check fan, motor and impeller.
Phase fault.| Check main fuses and phase sequence.
Ducts blocked.| Check dampers and ducts.
Product specification
Technical data
| DA 160| DA 250| DA 440
---|---|---|---
Drying capacity at 20°C – 60%rh| kg/h| 0.6| 1.1| 1.4
Nominal dry air volume| m3/h| 160| 250| 440
Nominal reactivation air volume| m3/h| 40| 50| 100
Nominal ext. pressure processair| Pa| free blowing| free blowing| free blowing
Nominal ext. pressure reactivationair| Pa| free blowing| free blowing| free
blowing
Electrical connected load| kW| 1.0| 1.3| 2.1
Current| A| 4.30| 5.65| 9.10
Operation range — temperature| °C| -30 to +40
Operation range — humidity| %rF| 0 to 100
Voltage supply| V/Ph/Hz| 230/1/50
Air inlet dimension| mm| 145 x 155| 145 x 255
Connection diameter dry air| mm| 100| 125
Connection diameter wet air| mm| 63| 80
Air filter class 1)| | ISO Coarse 45%
Dimension (H x W x D)| mm| 273 x 322 x 329| 351 x 335 x 357
Sound pressure level 2)| dB(A)| 53.0| 52.9| 69.0
Weight| kg| 10.5| 14.0| 14
- Classification according to ISO 16890
- Maximum value at 1 m distance, with 3 m applied ducting
NOTE!
Valid only for standard units, with standard fans, air-flows and standard
reactivation heat power.
Dimensions Condair DA 160
Spare parts
Part| Part No.| Technical specification| Numbers
installed| Numbers of recommended spare parts
---|---|---|---|---
Drive motor incl. gear box DA 160| 2597808| Crouzet 823055BJ,
230-240 V, 50 Hz 10/3 rpm
| 1| 1
Belt Pulley DA 160| 2597811| HTD 20-5M-09| 1|
Drive belt for DA 160| 2597812| 800-5M-09| 1|
Fan DA 160| 2597850| ZiehlAbegg GR19V-2EP.W6.1R| 1|
Capacitor for fan DA 160| 2597849| 2 μF 450 V| 1|
Heater PTC DA 160| 2597835| HRK01| 1| 1
Complete Heater PTC DA 160| 2597842| Complete heating package incl. cables| 1|
Wet air duct DA 160| 2597822| Heat-resistant flexcord d=63| |
Rotor DA 160| 2597800| Rotor DA 160| 1|
Belt Tensioner DA 160| 2597813| | 1|
Filter DA 160| 2597867| AAF R29 EN779: G3 200 x 250 mm| 1| 3
Toggle switch DA 160| 2597876| Orbitus| 1|
Spare parts Condair DA 250
Part| Part No.| Technical specification| Numbers
installed| Numbers of recommended spare parts
---|---|---|---|---
Drive motor incl. gear box DA 250| 2597808| Crouzet 823055BJ, 230-240 V, 50 Hz
10/3 rpm
| 1| 1
Belt Pulley DA 250| 2597811| HTD 20-5M-09| 1|
Drive belt for DA 250| 2597489| 1050-5M-9| 1|
Fan DA 250| 2597850| GR19V-2EP.W6.1R| 1|
Capacitor for fan DA 250| 2597849| 2 μF 450 V| 1|
Heater PTC DA 250| 2597836| DBK HRKK04/50/22| 1| 1
Wet air duct DA 250| 2597824| Heat-resistant flexcord d=80| |
Rotor DA 250| 2597801| Rotor DA 250| 1|
Belt Tensioner DA 250| 2597813| | 1|
Filter DA 250| 2597869| AAF R29 EN779: G3 220 x 330 mm| 1| 3
Toggle switch DA 250| 2597876| Orbitus 255O36| 1|
Ampere meter DA 250| 2595680| Tälje Mätinstrument RQ48E 10A| 1|
Spare parts Condair DA 440
Part| Part No.| Technical specification| Numbers
installed| Numbers of recommended spare parts
---|---|---|---|---
Drive motor incl. gear box DA 440| 2597808| Crouzet 823055BJ, 230-240 V, 50 Hz
10/3 rpm| 1| 1
Belt Pulley DA 440| 2597811| HTD 20-5M-09| 1|
Drive belt for DA 440| 2597489| 1050-5M-9| 1|
Fan DA 440| 2597854| GR19V-4IP.Z8.AR| 1|
Capacitor for fan DA 440| 2597849| 2 μF 450 V| 1|
Heater PTC DA 440| 2597836| DBK HRKK04/50/22| 1| 1
Wet air duct DA 440| 2597824| Heat-resistant flexcord d=80| |
Rotor DA 440| 2597801| Rotor DA 440| 1|
Belt Tensioner DA 440| 2597813| | 1|
Filter DA 440| 2597869| AAF R29 EN779: G3 220 x 330 mm| 1| 3
Toggle switch DA 440| 2597876| Orbitus 255O36| 1|
Ampere meter DA 440| 2595680| Tälje Mätinstrument RQ48E 10A| 1|
Electrical wiring diagrams
Electrical wiring diagram Condair DA 160
Pos. | Component | Type | Number | Manufacturer |
---|---|---|---|---|
M1 | Gear motor 230 V, 50 Hz, 3 rpm | 823055BJ | 1 | Crouzet AB |
M2 | Radial fan, K2E 190-RA26-09 | 1 | ebmpapst AB | |
C | Built in capacitor in fan | 1 | ebmpapst AB | |
S1/S2 | Toggle switch 2×1-pol. bl/or | 255036 | 1 | Nedis |
E | Heater, 230 V | DA 160-PTC | 1 | OEM |
P1 | Terminal, male 7-pin | sls 5.08/7B sn or | 1 | Weidmüller AB |
P1 | Terminal, female 7-pin | blz 5.08/7 sn or | 1 | Weidmüller AB |
P2 | Connection cable for fan | 1 | ebmpapst AB | |
– | Blind plug, 22,0-25,5 mm | SE E 14 757 16 | 1 | RUTAB |
H02 | Cable, H05RN-F/3G1/2m | 17722000 | 1 | Axjo Kabel |
PH3/HS | Humidistat plug connection | * |
Optional operation method when controlled by humidistat
If continuos operation of the fan is requested, and the humidistat should
control only a reactivation heater, shift wire 2-2 from terminal P1:2 to
terminal P1:1
Connection of humidistat
Connect the humistat to terminals P3:8-9
Electrical wiring diagram Condair DA 250
Pos. | Component | Type | Number | Manufacturer |
---|---|---|---|---|
M1 | Gear motor 230 V, 50 Hz, 3 rpm | 823055BJ | 1 | Crouzet AB |
M2 | Radial fan, K2E 190-RA26-09 | 1 | ebmpapst AB | |
C | Built in capacitor in fan | 1 | ebmpapst AB | |
S1/S2 | Toggle switch 2×1-pol. bl/or | 255036 | 1 | Nedis |
E | Heater, 230 V | DA 250-PTC | 1 | OEM |
P1 | Terminal male 7-pin | sls 5.08/7B sn or | 1 | Weidmüller AB |
P1 | Terminal, female 7-pin | blz 5.08/7 sn or | 1 | Weidmüller AB |
P2 | Connection cable for fan | 1 | ebmpapst AB | |
– | Blind plug, 22,0-25,5 mm | SE E 14 757 16 | 1 | RUTAB |
H02 | Cable, H05RN-F/3G1/2m | 17722000 | 1 | Axjo Kabel |
A | Ammeter, 0-10A | RQ48E 0-10A | 1 | Tälje Mätinstr. |
h | Runtime meter | * | ||
P3/HS | Humidistat plug connection | * |
Optional operation method when controlled by humidistat
If continuos operation of the fan is requested, and the humidistat should
control only a reactivation heater, shift wire 2-2 from terminal P1:2 to
terminal P1:1
Connection of humidistat and runtime meter
Connect the humistat to terminals P3:8-9
Connect the runtime meter to terminals P1:4 and P1:5
Electrical wiring diagram Condair DA 440
Pos. | Component | Type | Number | Manufacturer |
---|---|---|---|---|
M1 | Gear motor 230 V, 50 Hz, 3 rpm | 823055BJ | 1 | Crouzet AB |
M2 | Radial fan, K3G190-RD45-03 | 1 | ebmpapst AB | |
C | Built in capacitor in fan | 1 | ebmpapst AB | |
S1/S2 | Toggle switch 2×1-pol. bl/or | 255036 | 1 | Nedis |
E | Heater, 230 V | DA 250-PTC | 1 | OEM |
P1 | Terminal male 7-pin | sls 5.08/7B sn or | 1 | Weidmüller AB |
P1 | Terminal, female 7-pin | blz 5.08/7 sn or | 1 | Weidmüller AB |
P2 | Connection cable for fan | 1 | ebmpapst AB | |
– | Blind plug, 22,0-25,5 mm | SE E 14 757 16 | 1 | RUTAB |
H02 | Cable, H05RN-F/3G1/2m | 17722000 | 1 | Axjo Kabel |
A | Ammeter, 0-10A | RQ48E 0-10A | 1 | Tälje Mätinstr. |
h | Runtime meter | * | ||
P3/HS | Humidistat plug connection | * |
Optional operation method when controlled by humidistat
If continuos operation of the fan is requested, and the humidistat should
control only a reactivation heater, shift wire 2-2 from terminal P1:2 to
terminal P1:1
Connection of humidistat and runtime meter
Connect the humistat to terminals P3:8-9
Connect the runtime meter to terminals P1:4 and P1:5
EU declaration of conformity
EU declaration of conformity
- Condair Group AG
- Gwattstrasse 17
- 8808 Pfäffikon SZ
- Switzerland
- declare under own responsibility that the product:
Condair Dehumidifier DA 160, DA 250, DA 440, DA 210, DA 350, DA 400 and DA
450
which is detailed in this declaration complies to the following harmonized
European standards and technical specifications:
- EN ISO 12100:2010 Safety of machinery – General principles for design –
- Risk assessment and risk reduction (ISO
- 12100:2010)
- EN 60204-1:2018 Safety of machinery – Electrical equipment of machines – Part
- 1: General requirements
- EN 61000-6-3:2007/A1:2011/AC:2012
- Electromagnetic compatibility (EMC) – Part 6-3: Generic standards –
- Emission standard for residential, commercial and light-industrial environments
- EN 61000-6-2:2005/C1:2005 Electromagnetic compatibility (EMC) – Part 6-2: Generic standards –
- Immunity for industrial environments
- EN 61000-3-2:2014 Electromagnetic compatibility (EMC) – Part 3-2: Limits – Limits
- for harmonic current emissions (equipment input current ≤ 16 A per phase)
- EN 61000-3-3:2013 Electromagnetic compatibility (EMC) – Part 3-3: Limits –
- Limitation of voltage changes, voltage fluctuations and flicker in
- public low- voltage supply systems, for equipment with rated
- current ≤ 16 A per phase and not subject to conditional connection according to conditions in directive:
- 2006/42/EC Machinery Directive
- 2009/125/EC Ecodesign requirements for fans driven by motors with an
- electric input power between 125 W and 500 kW
- 2014/30/EU Electromagnetic Compatibility (EMC) Directive
Condair Group AG
Gwattstrasse 17, 8808 Pfäffikon SZ, Switzerland
Phone +41 55 416 61 11, Fax +41 55 588 00 07
info@condair.com,
www.condairgroup.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>