Condair RO-H Reverse Osmosis System User Guide

June 17, 2024
condair

Condair RO-H Reverse Osmosis System

Condair-RO-H-Reverse-Osmosis-System-PRO

Product Information

Specifications

  • Model: Condair RO-H
  • Capacity: 4.8 gal (18 l) tank, 3.17 gal (12 l) tank
  • Intended Use: Humidification and Evaporative Cooling

Product Overview
The Condair RO-H Reverse Osmosis System is designed for humidification and evaporative cooling purposes. It ensures safe use, performance, and longevity of the equipment. This system is intended for use by engineers and properly trained technical personnel. Please read the manual thoroughly before specifying, designing, or installing the RO System from Condair Ltd.

Product Usage Instructions

Introduction

  • First things first: Familiarize yourself with the Condair RO-H Reverse Osmosis System.
  • About this quick starting guide: This guide is meant to provide quick setup instructions for initial use.

For your safety

  • Intended use and not intended use: The pure water from the RO system is not for drinking and should not be connected to any drinking water outlet.
  • Hygiene: Follow local health and safety guidelines to prevent the growth of microorganisms in the system.
  • Ensure safe operation: Operate the system following safety guidelines provided in the manual.
  • Qualification of personnel: Only qualified personnel should perform installation and maintenance work on the system.
  • Important note regarding warranty: Warranty details are provided in the Installation, Operation, and Service Manual. Failure to follow installation and maintenance recommendations may void the warranty.

Product Overview

  • Condair RO-H description: The system is designed for humidification and evaporative cooling purposes.

FAQs

  • Q: Can the RO water from this system be consumed?
    A: No, the pure water produced by the RO system is not for drinking and should not be connected to any drinking water outlet.

  • Q: What is the warranty coverage for the RO-H parts?
    A: RO-H parts are covered by a two-year warranty from the invoice date, except for replacement parts listed in the routine maintenance section.

Introduction

First things first
Thank you for choosing the Condair RO-H Reverse Osmosis System.
The Condair RO-H Reverse Osmosis System incorporates the latest technical advances and meets all recognized safety standards. Nevertheless, improper use of the Condair RO-H Reverse Osmosis System may result in danger to the user or third parties and/or property damage. To ensure a safe, proper, and economical operation of the Condair RO-H Reverse Osmosis System, please observe and comply with all information and safety instructions contained in the present documentation as well as in the separate documentation of the components used together with the Condair RO-H Reverse Osmosis System. If you have questions after reading this documentation, please contact your Condair representative. They will be glad to assist you.

About this quick starting guide
The subject of this manual is the Condair RO-H Reverse Osmosis System. This manual has been written to ensure the safe use, performance and longevity of the equipment, and is intended for use by engineers and properly trained technical personnel. Please read this manual thoroughly before specifying, designing or installing an RO System from Condair Ltd. Keep for future reference. As our policy is one of continuous research and development, we reserve the right to amend, without notice, the specifications provided in this document. Condair Ltd. does not guarantee nor accept liability for the accuracy of information in this document.

Scope of delivery

RO-HM:

  • RO-H base
  • Pressure tank 4.8 gal (18 l) including mounting kit
  • Installation kit RO
  • Sediment filter 5 µm
  • Granular Active Carbon Filter
  • RO Membrane 400 gal
  • Wrenches (3x)

RO-HB:

  • RO-H base
  • Expansion tank 3.17 gal (12 l) including fittings
  • Installation kit RO
  • Sediment filter 5 µm
  • Granular Active Carbon Filter
  • RO Membrane 400 gal
  • Wrenches (3x)
  • Housing cover

For your safety

Intended use and not intended use
The Condair RO-H Reverse Osmosis System is intended to be used exclusively for pure water production within the operating conditions as specified in the Installation, Operation and Service Manual, chapter 5.3 and must not be installed/used in explosion hazard areas. Any other use without the written consent of Condair is considered as not conforming with the intended purpose and may lead to the Condair RO-H Reverse Osmosis System becoming dangerous and will void any warranty. Operation of the equipment in an intended manner requires that all the information contained in this manual are observed (in particular the safety and hygiene instructions).

Not intended use
Pure water (RO water) is not drinking water and must not be connected to any drinking water outlet.

Hygiene
Please observe the local health and safety executive’s technical guidance on the control of Legionellosis in water systems. The user is responsible for ensuring that the water system complies with local regulations, bylaws and guidelines (such as the HSE ACoP L8, VDI 6022, ISO 22000, HACCP or equivalent). If inadequately maintained, the RO System, can support the growth of microorganisms, including the bacterium that causes Legionnaires’ disease. The RO-H is produced according to best hygiene standards, which means that we have considered all aspects of this equipment to reduce the risk of Legionnaires’ disease and other similar conditions. However, the user is responsible for ensuring that the installation, operation and maintenance work on the equipment is performed in a manner, ensuring that the system stays clean!

  1. Guidelines to ensure your system stays clean and prevent the growth of Legionella
    • Carry out a risk assessment of the water system using a competent person and implement an appropriate monitoring and control program.
    • Initiate procedures for checking the system, cleaning tanks, changing filters, disinfection etc.
    • The RO-H must be connected to a clean, potable mains water supply.
    • Enter into a service contract that suits you or your company.
    • Stop the system if polluted drinking water is found in your area.
    • Avoid water temperatures above 77 °F that favor the growth of Legionella. If the water temperature surpasses 86 °F, the RO-H cannot be used in connection with a Condair MN.
    • Do not stop the system unless it is faulty or leaking (avoid water stagnation).
    • Disinfect the Condair RO-H System at least once a year and after every maintenance or repair. Always carry out a complete system disinfection inclusive humidifier if it has been turned off for more than 48 hours.
    • Have water samples taken and tested for harmful bacteria at least once a year.
    • Conduct follow-up measurements until the system is clean if bacteria have been detected in the system.

The Condair service team can help. Condair has expert technicians who can provide:

  • Bacteriological troubleshooting on-site
  • Cleaning and disinfecting
  • Preventive maintenance
  • Repair and fault finding
  • Training and guidance

Ensure safe operation
If it is suspected that safe operation has been compromised, the RO-H should immediately be shut down and secured against accidental power-up.
Shut down the RO-H if:

  • Components are damaged, worn or very soiled.
  • The RO-H does not work correctly.
  • Joints, pipes or hoses are leaking.

No modifications must be made on the RO-H without the manufacturer’s consent. All persons working with the RO-H must report any alterations made to the RO-H to the owner immediately. Use only original accessories and spare parts available from your Condair representative.

Qualification of personnel
All installation work must be performed only by persons who are familiar with the Condair RO-H System and sufficiently qualified for such work. All work on electric installations must only be performed by adequately qualified electricians.
Further details of qualification of personnel, safety considerations and warranty can be found in the complete Installation, Operation and Service Manual.

Important note regarding warranty
RO-H parts are covered by a two-year warranty from the invoice date except the replacement parts listed in the routine maintenance section. Failure to observe the manufacturer’s installation and maintenance recommendations and instructions will invalidate the warranty. Condair Ltd. cannot be made liable for damage or injury attributable to failure to observe the manufacturer’s installation and maintenance recommendations and instructions.

Product Overview

Condair RO-H description
Reverse osmosis system (from now on called RO) with reservoir tank for removal (>95 %) of salts and minerals in tap water. The systems are designed by Condair Ltd. with focus on reliable and hygienically correct solutions. The system uses a membrane separation process in which water molecules can pass through the membrane, while the majority of salts and minerals are retained and thereafter flushed out to drain. From the inlet, the water passes through a two steps of filtering before reaching the RO membrane. First step is an activated carbon filter to remove any residual free Chlorine in the inlet water. The second filter step is a sediment filter to remove particles above a size of 5 µm.

Inlet water quality requirements
The quality of the water being used in the Condair RO-H System should be checked before system commissioning. The RO-H system must be connected to a clean, potable drinking water quality mains. If the inlet water does not meet the quality specified in the preconditions table in Chapter 3.3, it may be necessary to install additional water treatment.

Installation considerations
Do not install the RO-H in a room that often surpasses an air temperature of 77 °F. Also keep installation away from heat-producing applications, such as boiler, central heating etc.
Observe the following restrictions concerning the length of piping:

  • Junction from tap water line to RO inlet: max. 6.5 ft
  • RO to tank: max. 6.5 ft
  • Tank to product inlet: max. 9.8 ft
  • RO to drain siphon: max. 16.3 ft

Condair-RO-H-Reverse-Osmosis-System- \(4\)

Installation Condair RO-H

Important notes on installation

  • WARNING! Do not retighten/unscrew hoses while the system is pressurized!
  • CAUTION!
    • Do not use oil, grease, glue, silicon, O-ring lubrication, etc.
    • when assembling pipes or hose connections.
    • All of the above products can act as food for bacteria and are thus pose health risks.
    • Only approved lubricant: Liquid dish soap.
    • Wash your hands before or wear clean gloves while assembling parts in direct contact with water.
    • Keep dust covers on pipes and hoses until just before assembly.
  • CAUTION! Do not fasten the pump station or hoses/pipes to vibrating installations.
  1. Water piping and connections
    The following flow diagram shows the needed fittings and their placement for RO-HM. Please follow the information strictly.Condair-RO-H-Reverse-Osmosis-
System- \(5\) Condair-RO-H-Reverse-Osmosis-System-
\(6\)

Installation of filters and RO membrane
CAUTION! The first time a new RO membrane is to be used, it is important to flush out any preservation fluids so that they do not end up in the system.Condair-RO-H-Reverse-Osmosis-System- \(7\) Condair-RO-H-Reverse-Osmosis-System- \(8\)

Maintenance

For regular maintenance please consult the full Installation, Operation and Service Manual.

Maintenance work
To ensure safe, hygienic and economic operation of the RO-H, vital components must be checked and maintained periodically according to the table below. The maintenance intervals and maintenance work stated below are guideline values. Local conditions, quality of the water etc. could influence the maintenance intervals. The relevant personnel is responsible for any maintenance work not carried out.

Service, to be carried out Service interval [months]
Control weekly monitoring checklist 12

Check the condition of the pump (pressure & noise) pressure should be min. 60 psi above inlet water pressure – if pressure is unstable – replace filters and test again.|

12

Functional testing of pressure switch. Close inlet water and check that system stops – Close pressure tank valve and check that RO system stops. “8” should be shown in display.|

12

Leak testing (check for leaks).| 6
Disinfection/cleaning of tank| 12
Control units|
Test display for errors (visual inspection)| 6
Hygiene|
Disinfection/cleaning of the system| 12

Controller menu
The computer box controls the working status, to ensure the machine work normally, and the RO membrane is in good working condition.Condair-RO-H
-Reverse-Osmosis-System- \(9\)

Letter state Display instructions
8 (dynamic rotation) means water production When the high-pressure switch

detects that the water pressure in the tank is lower than the set value, the water purifier enters the water production process.
F means flushing| Flushing of RO either at startup or when the “strong washing” button has been pressed. If there has not been any pure water production within 12 h, the function is triggered automatically.
8 (static display) means the water tank is full and there is no water demand| When the high-pressure switch detects that the water pressure in the tank reaches the set value, the RO will stop production.
0 means lack of water| When the low-pressure switch detects that the inlet water pressure is lower than 8 psi, the water purifier will stop working and the buzzer sounds.
6 means maintenance| The buzzer sounds. A service (filter, RO membrane change) is necessary. Please contact Condair Service.

Troubleshooting

Fault indication| Cause of the problem| Indication| Resolution
---|---|---|---
RO not starting| Power off| Lights off on RO

Detected by humidifier – low water pressure

| Plug power.

Check power supply.

No water| Status of RO = “0”

Detected by humidifier – low water pressure

| Check inlet valve.
Too low water pressure| Check raw water pressure.
High/low-pressure switch damaged| Switch needs replacement. Call Condair support.
No pure water production / no visible drain water| Inlet valve failed to open or clogged| No drain/pure water on RO. Detected by humidifier – low water pressure| Inlet valve needs replacement. Call Condair support.
Check valve blocked.| No pure water, only drain water on RO. Detected by humidifier – low water pressure| Check valve needs replacement. Call Condair support.
Check valve defect.


RO membrane clogged or scaled

| Very little pure water on RO. Detected by humidifier – low water pressure| Replace RO membrane, check incoming water quality and drain valve.
RO starts over repeatedly| Expansion/pressure tank defect| Detected during optical inspection of RO. Detected by humidifier – low water pressure.| Replace tank.
System loses pressure (possible leak)| Insufficient water production. Detected by humidifier – low water pressure.| Call Condair support. Locate leak and replace defect part(s).
High-pressure switch defect| Insufficient water production. Detected by humidifier – low water pressure.| Switch needs replacement. Call Condair support.
Permeate quality decreases| Membrane defect| TDS meter in RO display will indicate a value >30. Detected by humidifier – filter exhausted.| Replace membrane.
Permeate flow decreases (below 5.3 gal/h)| Membrane scaled or clogged| Detected by humidifier – low water pressure.

Product Data

Technical parameters Unit Value
Voltage/frequency; protection VAC / Hz 110–120 / 60 *1)
Power Rating W 90
Incoming water quality   Tap water
Incoming conductivity (see page 12) µS/cm 150–1000
Incoming TDS ppm 95–700
Incoming pressure (see page 12) psi 8–50 *2)
max. permissible operating pressure psi 116
Incoming water temperature °F 41–77 *3)
RO permeate capacity @ 5 °C gal/h 4.5
Salt rejection % 95–98
Water efficiency % ≈ 50/50
Output pressure psi 43.5–87.0
Prefilter 1 Act. Carbon
Prefilter 2 Micron 5
Low pressure switch trigger psi 8
High pressure switch trigger psi 32.0–43.5
Tank sizes and types gal (liter) 3.17 (12) Expansion tank

4.8 (18) Pressure tank

Noise| dBA| <50
Connection inlet|  | Adapter to 3/8″ push to connect
Connection pure water|  | JG 3/8″ push fit
Connection drain|  | JG 1/4″ push fit
Outer dimensions RO (HxLxW)| inch| 18.3 x 14.0 x 8.5
Outer dimensions hood (HxLxW)| inch| 18.5 x 15.2 x 9.8
Outer dimensions tank 3.17 gal (12 l) DxH| inch| 12.68 X 8.15
Outer dimensions tank 4.8 gal (18 l) DxH| inch| 11.0 x 16.7
Weight RO| lbs| 18.7
Weight hood| lbs| 8.8
Weight tank 3.17 gal (12 l)| lbs| 13.2
Weight tank 4.8 gal (18 l)| lbs| 9.0

  • The Condair RO-H is energized by 24 VDC from an UL-listed class 2 power source. The system needs to be protected by a ground fault circuit interruptor ≥ 5 A.
  • If the pressure exceeds 50 psi, it is mandatory to install a pressure reducer upstream of the RO-H in the supply line, which is set to 50 psi max. pressure. A suitable pressure reducer is available from Condair (2600230).
  • The RO-H may only be connected to a cold water line.

Spare parts and Consumables

Spare parts

SAP No. Description
2600097 Low/high-pressure switch, set
2600098 Inlet/drain valve, set
2606940 Réservoir d’expansion 3,17 gal (12 litres), kit
2601023 SP Worm drive bracket 260-280/12, Set
2601024 SP Housing cover RO-H
2501660 Hydraulics Installation set
2599774 Booster pump 5bar/72.5psi, 3/8″ female

Consumables

SAP No. Description
2604425 Service-kit RO-H (2599771 & 2600099)
2599771 RO membrane 3013 400G
2600099 GAC/Sediment filter set
2600112 Disinfection fittings set, RO-H
2300001 Disinfection HaloMist HM10 Ag, 5 % – Qt

Declaration of conformity

Condair-RO-H-Reverse-Osmosis-System- \(10\)

Condair Group AG
Gwattstrasse 17
8808 Pfäffikon, Switzerland
Tel. +41 55 416 61 11
Fax +41 55 588 00 07
info@condair.com
www.condair-group.com

CONSULTING, SALES AND SERVICE:
For the download of the detailed Installation, Operation and Service Manuals please use the following QR codes.

U.S.A
1021 6th Street
Racine, WI 53403
CANADA
2740 Fenton Road
Ottawa, Ontario K1T 3T7
TEL: 1.866.667.8321
FAX: 613.822.7964
EMAIL: na.info@condair.com
WEBSITE: www.condair.com

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>