ENVIRO C44 Fireplace Installation Guide

June 17, 2024
Enviro

ENVIRO C44 Fireplace

ENVIRO C44 Fireplace

REFER TO OWNER’S MANUAL FOR SPECIFIC INSTALLATION REQUIREMENTS AND ADDITIONAL PRODUCT INSTRUCTIONS

Minimum Framing Dimensions

Minimum Framing Dimensions

Depth 20” 508 mm
Width 55” 1397 mm
Header Height 38” 965 mm
Rough Opening Height 43.5” 1105mm
Enclosure Ceiling 65” 1651 mm

Note: Vent size = Co-axial 5 x 8”

Clearance to Combustibles

A – Finishing edge to side wall 7″ 229 mm
B – Minimum clearance to enclosure ceiling 65″ 1651 mm
C – Minimum clearance to mantel height See Chart See Chart
D – Front of door to edge of floor protection 60″ 0 mm
E – Minimum alcove width 60″ 1524 mm

Non-Combustible Board Placement

Minimum Venting Requirements

Minimum permitted venting is shown below. The framing height to the center of the thimble is 50”. Minimum venting must include a 12” vertical section and a 90 degree elbow which is then terminated horizontally. For a vertical termination please follow the vent pipe manufacturer’s installation instructions for vertical vent termination framing. A minimum of 1 in. (25 mm) clearance on all sides of the vertical vent pipe must be maintained. For every 12” of horizontal run there must be a 1/4” of rise. 1” of clearance between framing and venting must be maintained at all times. 2” above the venting and 3” above an elbow.

Fireplace Dimensions

Mantel Projections

Mantel graph dimensions are measured from the bottom of the fireplace, if you wish to reference the mantel height from the tiling edge subtract 15 inches (381mm) from the mantel height depicted on the graph. If you plan to install a TV above your fireplace refer to the appropriate section of the owner’s manual for available options. It is acceptable to install a combustible mantel over top of the non-combustible board. If you are activating the Cool Surface System you are eligible to subtract 12” (305mm) from the mantel height shown in this diagram. See page 6 for more details.

OPTIONAL STEP Cool Surface System Part 1

Dimensions

Dimensions
C44 CSS Front Vent – Overall Dimensions

CSS Side Vent – Dimensions

Dimensions
C44 CSS Combustible Facing Kit Dimensions

OPTIONAL STEP Cool Surface System Part 2

Framing & Rough Opening – Front Vent

Front Vent

Venting Clearances – Front Vent

Shown here are the minimum framing and clearances for the CSS when the fireplace is installed with the minimum allowable vent length:

Min. Ceiling Clearance from top of CSS outlet = 4” (10.2 cm)
Min. Ceiling Clearance in wall from top of CSS Body = 55/8” (14.3 cm)
CSS Body Min. Rear standoff = 2¾” (69.8 cm)

Front Vent

OPTIONAL STEP Cool Surface System Part 3

Framing & Clearances – CSS Side Vent

CSS Side Vent

OPTIONAL STEP Cool Surface System Part 4

Framing & Revised Mantle Clearances – Front Vent

Framing & Revised Mantle Clearances – Side Vent

TV Installation Considerations:

If you are planning to mount a TV above your fireplace some considerations must be made to ensure it is protected from the heat.

During testing temperatures did not exceed 121°F (49°C) midway up the front wall (see figures on right). There is no guarantee that these temperatures will not harm the longevity of your TV. Make sure to consult your TV manufacturer’s specifications to find the maximum allowable operating temperature. Since every home and  installation is unique, temperatures should be verified at the time of install if possible. If desired, front wall temperatures can be lowered to 104°F (40°C) with the use of a mantle (see CSS TV clearances with Mantle figure). See revised mantle clearances chart above. A TV should not be installed if temperatures exceed the manufacturers maximum allowable temperature.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Enviro User Manuals

Related Manuals